HomeMy WebLinkAboutUP20-0001_Revised_PlansKEEFER
PSL # 491608
4338 SHORTHORN DR.
CHICO, CA 95973
T-1
TITLE SHEET
PROJECT DESCRIPTION
CONSTRUCTION:
RADIO:
VERIZON WIRELESS SIGNATURE BLOCK
DISCIPLINE:SIGNATURE:DATE:
EQUIPMENT:
SITE ACQUISITION:
MICROWAVE:
TELCO:
WO ADMINISTRATOR:
PROJECT ADMINISTRATOR:
CODE COMPLIANCE
DRIVING DIRECTIONS
PROPERTY INFORMATION:
SITE NAME:KEEFER
SITE NUMBER: 491608
SITE ADDRESS:4338 SHORTHORN DR.
CHICO, CA 95973
JURISDICTION:
TO:4338 SHORTHORN DR.
CHICO, CA 95973
A-1
A-3
SHEET
T-1
DESCRIPTION
TITLE SHEET
PLANNER:
CONSTRUCTION:
SAC WIRELESS SIGNATURE BLOCK
DISCIPLINE:SIGNATURE:
SITE ACQUISITION:
LANDLORD:
SOUTH & WEST ELEVATIONS
SITE PLAN
DATE:
A-4
NORTH & EAST ELEVATIONS
A-2 EQUIPMENT & ANTENNAS LAYOUTS
GENERAL CONTRACTOR NOTES ZONING DRAWINGS
DO NOT SCALE DRAWINGS IF NOT FULL SIZE (24 X 36)
CONTRACTOR SHALL VERIFY ALL PLANS AND EXISTING DIMENSIONS AND CONDITIONS ON THE JOB
SITE AND SHALL IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR THE SAME.
ASSESSOR'S PARCEL NUMBER
CURRENT ZONING:
TYPE OF CONSTRUCTION:
AREA OF CONSTRUCTION:
V-B
25'-0" x 25'-0" = 625 SQ FT
047-600-007
VLDR
CONSTRUCTION INFORMATION
OCCUPANCY:U
APPLICANT/LESSEE
2785 MITCHELL DRIVE, BLDG 9
WALNUT CREEK, CA 94598
OFFICE: (925) 279-6000
APPLICANT'S REPRESENTATIVE
PROPERTY OWNER:
PROJECT SUMMARYPROJECT TEAM
ARCHITECT:SURVEYOR:
UTILITY COORDINATOR:
PLANNINGSITE ACQUISITION
Call before you dig.
below.Know what's
R
TO OBTAIN LOCATION OF PARTICIPANTS
UNDERGROUND FACILITIES BEFORE
YOU DIG IN CALIFORNIA (NORTH &
CENTRAL) , CALL USA NORTH 811
TOLL FREE: 1-800-227-2600 OR
www.usanorth811.org
CALIFORNIA STATUTE
REQUIRES MIN OF 2
WORKING DAYS NOTICE
BEFORE YOU EXCAVATE
THIS PROJECT IS A VERIZON WIRELESS UNMANNED TELECOMMUNICATION WIRELESS
FACILITY. IT WILL CONSIST OF THE FOLLOWING:
·NEW VERIZON WIRELESS 25'-0" x 25'-0" LEASE AREA
·NEW VERIZON WIRELESS 8'-0" TALL CHAIN-LINK FENCE
·NEW VERIZON WIRELESS OUTDOOR EQUIPMENT 15'-0" X 8'-0" CONCRETE PAD
·NEW VERIZON WIRELESS 30KW GENERAC STANDBY GENERATOR W/210 GALLON DIESEL TANK
(UL142) ON NEW 5'-0" X 10'-0" CONCRETE PAD
·(1) NEW VERIZON WIRELESS GPS ANTENNA
·(1) NEW VERIZON WIRELESS ELECTRICAL METER ON NEW H-FRAME
·(1) NEW VERIZON WIRELESS INTERSECT CABINET & TELCO BOX ON NEW H-FRAME
·(1) NEW VERIZON WIRELESS 90'-0" HIGH MONOPINE
·(9) NEW VERIZON WIRELESS 8' HIGH PANEL ANTENNAS
·(12) NEW VERIZON WIRELESS RADIOS
·(2) NEW VERIZON WIRELESS RAYCAPS 6627
·(2) NEW VERIZON WIRELESS HYBRID CABLES
·(1) NEW STEP DOWN TRANSFORMER ON NEW 4'-2" X 4'-4" CONCRETE PAD W/3 BOLLARDS
VICINITY MAP
EQUIPMENT ELEVATIONSA-5
BUTTE COUNTY
SMITHCO SURVEYING ENGINEERING
P.O. BOX 81626
BAKERSFIELD, CA 93380
CONTACT: GREG SMITH, PLS
TELEPHONE: (661) 393-1217
GSMITH@SMITHCO.NET
SAC WIRELESS, LLC.
8880 CAL CENTER DRIVE
SUITE 170
SACRAMENTO, CA 95826
CONTACT: RAMON MORENO
TELEPHONE: (916) 751-8827
RAMON.MORENO@SACW.COM
ACCESSIBILITY REQUIREMENTS:FACILITY IS UNMANNED AND NOT FOR HUMAN
HABITATION. ACCESSIBILITY NOT REQUIRED.
·2019 CALIFORNIA ADMINISTRATIVE CODE
·2019 CALIFORNIA BUILDING CODES
·2019 CALIFORNIA ELECTRICAL CODE
·2019 CALIFORNIA FIRE CODE
·2019 CALIFORNIA ENERGY CODE
·CITY & COUNTY ORDINANCES
ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN ACCORDANCE WITH
THE CURRENT EDITIONS OF THE FOLLOWING CODES AS ADOPTED BY THE LOCAL GOVERNING
AUTHORITIES. ALL WORK SHALL CONFORM TO 2019 EDITION TITLE 24, CALIFORNIA CODE OF
REGULATIONS. NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK NOT
CONFORMING TO THE LATEST EDITIONS OF THE FOLLOWING CODES.
1.HEAD NORTHEAST ON MITCHELL DR TOWARD
OAK GROVE RD
2.TURN LEFT ONTO OAK GROVE RD
3.TURN LEFT ONTO TREAT BLVD
4.TURN RIGHT ONTO BUSKIRK AVE
5.TAKE THE RIGHT TOWARDS I- 680 N
6.KEEP LEFT AT THE FORK TO STAY ON I-680 N
7.TAKE EXIT 71A ON THE RIGHT TOWARD I-80 E
8.TAKE EXIT 56 FOR I-505 N
9.MERGE ONTO I-5 N
10.TAKE EXIT 569 FOR HAHN RD
11.TURN RIGHT ONTO HAHN RD
12.TURN LEFT ONTO LONE STAR RD
13.TURN RIGHT ONTO STATE HWY 20 E
14.TURN LEFT ONTO MARKET ST
15.CONTINUE ONTO CA-45 N/13TH ST
16. CONTINUE TO FOLLOW CA-45 N
17.TURN RIGHT ONTO CA-32 E/6TH ST
18. CONTINUE TO FOLLOW CA-32 E
19.TURN LEFT ONTO MERIDIAN RD
20.TURN RIGHT ONTO WILSON LANDING RD
21.TURN LEFT ONTO CA-99 N
22.TURN RIGHT ONTO GARDEN BROOK DR
23.TURN LEFT ONTO HEREFORD DR
24.TURN RIGHT INTO SHORTHORN DR
25.DESTINATION WILL BE ON THE LEFT
NOT TO SCALE NORTH
OWNER:WILLIAM M. LEWIS & JOANN LEWIS, TRUSTEES OF THE
LEWIS FAMILY TRUST
ADDRESS:9 SPRINGBROOC CT.
CHICO, CA 95926
PHONE:(530) 321-2919
EMAIL:wmlewis@sbcglobal.net
SAC WIRELESS, LLC.
8880 CAL CENTER DRIVE
SUITE 170
SACRAMENTO, CA 95826
CONTACT: WARREN SHEW
TELEPHONE: (312) 895-4977 EXT. 9555
WARREN.SHEW@SACW.COM
SAC WIRELESS, LLC.
8880 CAL CENTER DRIVE
SUITE 170
SACRAMENTO, CA 95826
CONTACT: WARREN SHEW
TELEPHONE: (312) 895-4977 EXT. 9555
WARREN.SHEW@SACW.COM
SAC WIRELESS, LLC.
8880 CAL CENTER DRIVE
SUITE 170
SACRAMENTO, CA 95826
CONTACT: WARREN SHEW
TELEPHONE: (312) 895-4977 EXT. 9555
WARREN.SHEW@SACW.COM
FROM:2785 MITCHELL DRIVE, BLDG 9
WALNUT CREEK, CA 94598
NOTE: THE ORIGINAL SIZE OF THIS PLAN IS 24" X 36". SCALE RATIO IS NOT VALID FOR REDUCED OR ENLARGED SHEET SIZESSHEET TITLE:
ISSUE STATUS
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
DRAWINGS IS PROPRIETARY & CONFIDENTIAL TO
VERIZON WIRELESS
ANY USE OR DISCLOSURE OTHER THAN AS IT RELATES
TO VERIZON WIRELESS IS STRICTLY PROHIBITED
2785 MITCHELL DRIVE, BLDG 9WALNUT CREEK, CA 945984338 SHORTHORN DR.CHICO, CA 95973PSL# 491608KEEFER03/19/2020 FA090% ZONING
DESCRIPTIONDATE BYREV.
TM
SAN DIEGO, CA 92126
619.736.3766
9020 ACTIVITY RD.
www.sacw.com
03/27/2020 FA1100% ZONING
05/22/2020 FA2100% ZONING
08/20/2020 FA3REVISED 100% ZONING
08/28/2020 FA4REVISED 100% ZONING
12/02/2020 FA5REVISED 100% ZONING
C-1 SITE SURVEY
C-2 SITE SURVEYSITE
SAC AE DESIGN GROUP, INC
NESTOR POPOWYCH, AIA
5015 SHOREHAM PLACE SUITE 150
SAN DIEGO, CA 92122
CONTACT: JULIAN BRIANO
TELEPHONE: (760) 219-9269
FAX: (619) 736-3106
JULIAN.BRIANO@SACW.COM 1-LINE DIAGRAM, PANEL SCHEDULE & UTILITY NOTESE-1
SITE PLAN
A-11
NORTH
1" = 30'-0" (24x36)
(OR)
SCALE:
1/2" = 30'-0" (11x17)
30'15'30'0
NEW VERIZON WIRELESS
EQUIPMENT & ANTENNA
AREA, REFER TO:
1
A-2
1
A-3
2
A-4
2
A-3
1
A-4
APN: 047-600-007
OWNER(S): WILLIAM M. LEWIS &
JOANN LEWIS, TRUSTEES OF THE
LEWIS FAMILY TRUST
SITE PLAN
EXISTING TRANSFORMER
T-3080 (NEW VERIZON
WIRELESS POWER P.O.C.)
LESSEE PROPOSED 12'-0" WIDE
CLASS II ACCESS EASEMENT
RIGHT-OF- WAY
NEW VERIZON WIRELESS U/G
ELECTRICAL ROUTE, BORING
METHOD IS USED (±520 FT)NOTE: THE ORIGINAL SIZE OF THIS PLAN IS 24" X 36". SCALE RATIO IS NOT VALID FOR REDUCED OR ENLARGED SHEET SIZESSHEET TITLE:
ISSUE STATUS
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
DRAWINGS IS PROPRIETARY & CONFIDENTIAL TO
VERIZON WIRELESS
ANY USE OR DISCLOSURE OTHER THAN AS IT RELATES
TO VERIZON WIRELESS IS STRICTLY PROHIBITED
2785 MITCHELL DRIVE, BLDG 9WALNUT CREEK, CA 945984338 SHORTHORN DR.CHICO, CA 95973PSL# 491608KEEFER03/19/2020 FA090% ZONING
DESCRIPTIONDATE BYREV.
TM
SAN DIEGO, CA 92126
619.736.3766
9020 ACTIVITY RD.
www.sacw.com
03/27/2020 FA1100% ZONING
05/22/2020 FA2100% ZONING
08/20/2020 FA3REVISED 100% ZONING
08/28/2020 FA4REVISED 100% ZONING
12/02/2020 FA5REVISED 100% ZONING
SH
O
R
T
H
O
R
N
D
R
I
V
E
CL
APN: 074-600-008
LESSEE PROPOSED 5'-0"
WIDE UTILITY EASEMENT
RIGHT-OF- WAY
EXISTING RESIDENCEPROPERTY LINENEW VERIZON WIRELESS
U/G FIBER ROUTE (±415 FT)EXISTING 5'-0" HIGH WOOD FENCENEW VERIZON WIRELESS 17"X30"
FIBER VAULT, (4) TOTAL (NEW
VERIZON WIRELESS POWER P.O.C.)
APN: 074-600-001
APN: 074-600-013
APN: 074-600-012 APN: 074-600-010
BIRDSEYE COURT90'-0"90'-0"
EXISTING TELCO RISER
EXISTING TELCO RISER
EXISTING U/G COMM. LINE
EXISTING U/G ELEC. LINE
EXISTING ACCESS
DRIVEWAY
EXISTING TREE
PROPERTY LINE PROPERTY LINEPROPERTY LINE
EXISTING TREE
(TYP.)
NEW VERIZON WIRELESS
SITE ACCESS DRIVEWAY
EXISTING 5'-0" HIGH CHAIN-LINK FENCE
EXISTING 5'-0" HIGH CHAIN-LINK FENCE(E) SEE TRAINEXISTING
CONC. AREA
EXISTING PAVED DRIVEWAYEDG
E
O
F
P
A
V
E
M
E
N
T
ED
G
E
O
F
P
A
V
E
M
E
N
T
EDGE OF PAVEMENT
EDGE OF PAVEMENT
DUI
L
D
I
N
G
S
E
T
B
A
C
K
L
I
N
E
30'-0"60'-0" EASEMENT FORINGRESS, EGRESS ANDPUBLIC UTILITIES PERSER. #86-42648, O.R50'-0"30'-0"30'-0"BUILDING SETBACK LINE
BUILDING SETBACK LINE60'-0"5'-0"
"GAMMA" SECTOR @ 265
°
ALPHA" SECT
O
R
@
8
0
°
"BE
TA
"
SECTOR
@
150
°
MICROWAVE @ 90°MICROWAVE
@
33
0
°
12'-0"359'-0"42'-0"7'-0"15'-0"12'-0"EXISTING 15' X 7' SEPTIC
EXISTING 100' LONG
LEACH LINES
EXISTING 20' LONG
LEACH LINE
EXISTING FLOW BOXES
W/8' SEPARATIONS183'-0"
EQUIPMENT &
ANTENNA LAYOUTS
3/8" = 1'-0" (24x36)
(OR)
SCALE:
3/16" = 1'-0" (11x17)
0 1'2'3'A-21EQUIPMENT LAYOUT2PANEL ANTENNA LAYOUT 3/8" = 1'-0" (24x36)
(OR)
SCALE:
3/16" = 1'-0" (11x17)
0 1'2'3'
NORTH
PANEL ANTENNAS
@ 81'-0" CENTERLINE
NEW VERIZON WIRELESS
ELECTRICAL METER, TELCO BOX &
INTERSECT CABINET W/GENERATOR
RECEPTACLE ON NEW H-FRAME
NEW VERIZON WIRELESS
90'-0" HIGH MONOPINE
(ANTENNAS NOT SHOWN
FOR CLARITY) REFER TO:
NEW VERIZON WIRELESS
OUTDOOR EQUIPMENT ON NEW
15'-0" X 8'-0" CONCRETE PAD
NEW VERIZON WIRELESS
RAYCAPS, (2) TOTAL, (1)
LOCATED AT TOWER, (1)
LOCATED AT EQUIPMENT AREA
2
-
NEW VERIZON WIRELESS
GPS ANTENNA, (1) TOTAL
NEW VERIZON WIRELESS
SERVICE LIGHTS W/6-HOUR
TIMER, (4) TOTAL
OUTLINE OF NEW VERIZON
WIRELESS MONOPINE
BRANCHES (SHOWN DASHED
FOR CLARITY)
NEW VERIZON WIRELESS
KNOX BOX
NEW PORTABLE FIRE
EXTINGUISHER (CLASS 4A-60BC)
"GAMMA" SECTOR @ 26
5
°
ALPHA" SECTO
R
@
8
0
°
"BETA
"
SECTOR
@
1
50
°
NEW VERIZON WIRELESS 8' HIGH
PANEL ANTENNAS, (9) TOTAL, (3)
PER SECTOR
NEW VERIZON WIRELESS
RAYCAPS, (2) TOTAL, (1) LOCATED
AT TOWER, (1) LOCATED AT
EQUIPMENT AREA
NEW VERIZON WIRELESS
90'-0" HIGH MONOPINE
NEW VERIZON WIRELESS RADIOS,
(12) TOTAL, (4) PER SECTOR, (9)
LICATED BEHIND ANTENNAS & (3)
LOCATED ON NEW RADIO DUAL
PIPE RING MOUNT
R12'-0"MAX.R7'-0"MIN.25'-0"NEW VERIZON WIRELESS LEASE AREANEW VERIZON WIRELESS
17"X30" FIBER VAULT, (4) TOTAL
12'-6"12'-6"R12'-
0
"
MAX.
R
7
'
-
0
"
MI
N
.R3'-
0
"
NEW VERIZON WIRELESS
ICE-BRIDGE W/(2) HYBRID
CABLESFIBERRBOX
INTERSECTCABINETMETERNORTH
POWER/
MISC
CAB.
FUTURE
MISC.
CAB.NOTE: THE ORIGINAL SIZE OF THIS PLAN IS 24" X 36". SCALE RATIO IS NOT VALID FOR REDUCED OR ENLARGED SHEET SIZESSHEET TITLE:
ISSUE STATUS
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
DRAWINGS IS PROPRIETARY & CONFIDENTIAL TO
VERIZON WIRELESS
ANY USE OR DISCLOSURE OTHER THAN AS IT RELATES
TO VERIZON WIRELESS IS STRICTLY PROHIBITED
2785 MITCHELL DRIVE, BLDG 9WALNUT CREEK, CA 945984338 SHORTHORN DR.CHICO, CA 95973PSL# 491608KEEFER03/19/2020 FA090% ZONING
DESCRIPTIONDATE BYREV.
TM
SAN DIEGO, CA 92126
619.736.3766
9020 ACTIVITY RD.
www.sacw.com
03/27/2020 FA1100% ZONING
05/22/2020 FA2100% ZONING
08/20/2020 FA3REVISED 100% ZONING
08/28/2020 FA4REVISED 100% ZONING
12/02/2020 FA5REVISED 100% ZONING
OUTLINE OF NEW VERIZON
WIRELESS MONOPINE BRANCHES
(SHOWN DASHED FOR CLARITY)
BATTERY/
CAB.NEW VERIZON WIRELESS 8'-0"
HIGH CHAIN-LINK FENCE
2'-0"15'-0"
9"3'-0"NEW VERIZON WIRELESS 12'-0"
WIDE CHAIN-LINK ACCESS GATE
1'-0"1'-0"1'-0"8"8'-0"1'-0"3'-6"25'-0"
NEW VERIZON WIRELESS LEASE AREA
8'-0"4"1'-4"LESSEE PROPOSED 12'-0" WIDE
CLASS II ACCESS EASEMENT
RIGHT-OF- WAY
NEW VERIZON WIRELESS U/G
ELECTRICAL ROUTE, BORING
METHOD IS USED (±455 FT)
LESSEE PROPOSED 5'-0"
WIDE UTILITY EASEMENT
RIGHT-OF- WAY
NEW VERIZON WIRELESS
U/G FIBER ROUTE (±748 FT)
8"
NEW VERIZON WIRELESS CLASS II
THROUGHOUT EQUIPMENT
ENCLOSURE (PARTIALLY SHOWN
FOR CLARITY)
NEW VERIZON WIRELESS 15KW DC
POLAR STANDBY GENERATOR W/54
GALLON DIESEL TANK (UL142) ON
NEW 15'-0" X 8'-0" CONCRETE PAD
1/4" = 1'-0" (11x17)
SCALE:
(OR)
1/2" = 1'-0" (24x36)0 6"1'2'2MICROWAVE ANTENNA LAYOUT
MICROWAVE @ 90°MICROWAVE
@
330
°
MICROWAVE ANTENNAS
@ 71'-0" CENTERLINE FUTURE
MISC.
CAB.
2'-0"10'-0"2'-0"5'-0"STANDBY
30KW AC
GENERATOR
NEW VERIZON WIRELESS 30KW
GENERAC STANDBY
GENERATOR W/210 GALLON
DIESEL TANK (UL142) ON NEW
5'-0" X 10'-0" CONCRETE PAD10"TYP.1'-10"TYP.1'-10"TYP.10"TYP.3'-8"TYP.NEW VERIZON WIRELESS
2'Ø MICROWAVE ANTENNA,
(1) TOTAL
NEW VERIZON WIRELESS
6'Ø MICROWAVE ANTENNA,
(1) TOTAL
NEW VERIZON WIRELESS
90'-0" HIGH MONOPINE
NORTH
OUTLINE OF NEW VERIZON
WIRELESS MONOPINE BRANCHES
(SHOWN DASHED FOR CLARITY)
6"
2'-6"4'-2"
2'-0"
5'-8"
NEW STEP DOWN
TRANSFORMER ON
NEW 4'-2" X 4'-4"
CONCRETE PAD
TRANSFORMER
NEW BOLLARD,
(3) TOTAL , (2)
FIXED & (1)
MOVABLE 1'-0"4'-4"3'-10"2'-8"2'-10"2'-10"
NORTH & EAST
ELEVATIONS
2 3/32" = 1'-0" (11x17)
SCALE:
(OR)
3/16" = 1'-0" (24x36)0 1.5'3'5'
3/32" = 1'-0" (11x17)
SCALE:
(OR)
3/16" = 1'-0" (24x36)0 1.5'3'5'A-3NORTH ELEVATIONEAST ELEVATION 1
1
A-5
GROUND LEVEL
ELEV. 0'-0" AGL
AGL 0'-0" = 196.1' NAVD 88
TOP OF NEW VERIZON WIRELESS MONOPINE BRANCHES
ELEV. 90'-0" AGL
CENTERLINE OF NEW VERIZON WIRELESS PANEL ANTENNAS
ELEV. 81'-0" AGL NEW VERIZON WIRELESS 8' HIGH
PANEL ANTENNAS, (9) TOTAL, (3)
PER SECTOR
NEW VERIZON WIRELESS RADIOS,
(12) TOTAL, (4) PER SECTOR, (9)
LICATED BEHIND ANTENNAS & (3)
LOCATED ON NEW RADIO DUAL
PIPE RING MOUNT
NEW VERIZON WIRELESS
90'-0" HIGH MONOPINE
TOP OF NEW VERIZON WIRELESS MONOPINE STRUCTURE & PANEL ANTENNA
ELEV. 85'-0" AGL
NEW VERIZON WIRELESS
HYBRID CABLES, (2) TOTAL
BOTTOM OF NEW VERIZON WIRELESS MONOPINE BRANCHES
ELEV. 20'-0" AGL
NEW VERIZON WIRELESS 8'-0" HIGH
CHAIN-LINK FENCE
NEW VERIZON WIRELESS RAYCAPS,
(2) TOTAL, (1) LOCATED AT TOWER,
(1) LOCATED AT EQUIPMENT AREA
NOTE: THE ORIGINAL SIZE OF THIS PLAN IS 24" X 36". SCALE RATIO IS NOT VALID FOR REDUCED OR ENLARGED SHEET SIZESSHEET TITLE:
ISSUE STATUS
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
DRAWINGS IS PROPRIETARY & CONFIDENTIAL TO
VERIZON WIRELESS
ANY USE OR DISCLOSURE OTHER THAN AS IT RELATES
TO VERIZON WIRELESS IS STRICTLY PROHIBITED
2785 MITCHELL DRIVE, BLDG 9WALNUT CREEK, CA 945984338 SHORTHORN DR.CHICO, CA 95973PSL# 491608KEEFER03/19/2020 FA090% ZONING
DESCRIPTIONDATE BYREV.
TM
SAN DIEGO, CA 92126
619.736.3766
9020 ACTIVITY RD.
www.sacw.com
03/27/2020 FA1100% ZONING
05/22/2020 FA2100% ZONING
08/20/2020 FA3REVISED 100% ZONING
08/28/2020 FA4REVISED 100% ZONING
12/02/2020 FA5REVISED 100% ZONING
2
A-5
GROUND LEVEL
ELEV. 0'-0" AGL
AGL 0'-0" = 196.1' NAVD 88
TOP OF NEW VERIZON WIRELESS MONOPINE BRANCHES
ELEV. 90'-0" AGL
CENTERLINE OF NEW VERIZON WIRELESS PANEL ANTENNAS
ELEV. 81'-0" AGL
NEW VERIZON WIRELESS 8' HIGH
PANEL ANTENNAS, (9) TOTAL, (3)
PER SECTOR
NEW VERIZON WIRELESS RADIOS,
(12) TOTAL, (4) PER SECTOR, (9)
LICATED BEHIND ANTENNAS & (3)
LOCATED ON NEW RADIO DUAL
PIPE RING MOUNT
NEW VERIZON WIRELESS
90'-0" HIGH MONOPINE
TOP OF NEW VERIZON WIRELESS MONOPINE STRUCTURE & PANEL ANTENNA
ELEV. 85'-0" AGL
NEW VERIZON WIRELESS
HYBRID CABLES, (2) TOTAL
BOTTOM OF NEW VERIZON WIRELESS MONOPINE BRANCHES
ELEV. 20'-0" AGL
NEW VERIZON WIRELESS 8'-0" HIGH
CHAIN-LINK FENCE
NEW VERIZON WIRELESS RAYCAPS,
(2) TOTAL, (1) LOCATED AT TOWER,
(1) LOCATED AT EQUIPMENT AREA
NEW VERIZON WIRELESS 2'Ø
MICROWAVE ANTENNA, (1) TOTAL
CENTERLINE OF NEW VERIZON WIRELESS MICROWAVE ANTENNAS
ELEV. 71'-0" AGL
NEW VERIZON WIRELESS 6'Ø
MICROWAVE ANTENNA, (1) TOTAL
CENTERLINE OF NEW VERIZON WIRELESS MICROWAVE ANTENNAS
ELEV. 71'-0" AGL
NEW VERIZON WIRELESS 6'Ø
MICROWAVE ANTENNA, (1) TOTAL
NOTE:
PAINT ALL NEW VERIZON WIRELESS
EQUIPMENT ON TOWER TO MATCH
MONOPINE
CENTERLINE OF FUTURE PANEL ANTENNAS BY OTHERS
ELEV. 61'-0" AGL
CENTERLINE OF FUTURE PANEL ANTENNAS BY OTHERS
ELEV. 61'-0" AGL
SOUTH & WEST
ELEVATIONS
123/32" = 1'-0" (11x17)
SCALE:
(OR)
3/16" = 1'-0" (24x36)0 1.5'3'5'
3/32" = 1'-0" (11x17)
SCALE:
(OR)
3/16" = 1'-0" (24x36)0 1.5'3'5'A-4WEST ELEVATION SOUTH ELEVATION
NOTE: THE ORIGINAL SIZE OF THIS PLAN IS 24" X 36". SCALE RATIO IS NOT VALID FOR REDUCED OR ENLARGED SHEET SIZESSHEET TITLE:
ISSUE STATUS
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
DRAWINGS IS PROPRIETARY & CONFIDENTIAL TO
VERIZON WIRELESS
ANY USE OR DISCLOSURE OTHER THAN AS IT RELATES
TO VERIZON WIRELESS IS STRICTLY PROHIBITED
2785 MITCHELL DRIVE, BLDG 9WALNUT CREEK, CA 945984338 SHORTHORN DR.CHICO, CA 95973PSL# 491608KEEFER03/19/2020 FA090% ZONING
DESCRIPTIONDATE BYREV.
TM
SAN DIEGO, CA 92126
619.736.3766
9020 ACTIVITY RD.
www.sacw.com
03/27/2020 FA1100% ZONING
05/22/2020 FA2100% ZONING
08/20/2020 FA3REVISED 100% ZONING
08/28/2020 FA4REVISED 100% ZONING
12/02/2020 FA5REVISED 100% ZONING
3
A-5
4
A-5
NEW VERIZON WIRELESS
KNOX BOX
NEW VERIZON WIRELESS
12'-0" WIDE CHAIN-LINK
ACCESS GATE
GROUND LEVEL
ELEV. 0'-0" AGL
AGL 0'-0" = 196.1' NAVD 88
TOP OF NEW VERIZON WIRELESS MONOPINE BRANCHES
ELEV. 90'-0" AGL
CENTERLINE OF NEW VERIZON WIRELESS PANEL ANTENNAS
ELEV. 81'-0" AGL NEW VERIZON WIRELESS 8' HIGH
PANEL ANTENNAS, (9) TOTAL, (3)
PER SECTOR
NEW VERIZON WIRELESS RADIOS,
(12) TOTAL, (4) PER SECTOR, (9)
LICATED BEHIND ANTENNAS & (3)
LOCATED ON NEW RADIO DUAL
PIPE RING MOUNT
NEW VERIZON WIRELESS
90'-0" HIGH MONOPINE
TOP OF NEW VERIZON WIRELESS MONOPINE STRUCTURE & PANEL ANTENNA
ELEV. 85'-0" AGL
NEW VERIZON WIRELESS
HYBRID CABLES, (2) TOTAL
BOTTOM OF NEW VERIZON WIRELESS MONOPINE BRANCHES
ELEV. 20'-0" AGL
NEW VERIZON WIRELESS 8'-0" HIGH
CHAIN-LINK FENCE
NEW VERIZON WIRELESS RAYCAPS,
(2) TOTAL, (1) LOCATED AT TOWER,
(1) LOCATED AT EQUIPMENT AREA
GROUND LEVEL
ELEV. 0'-0" AGL
AGL 0'-0" = 196.1' NAVD 88
TOP OF NEW VERIZON WIRELESS MONOPINE BRANCHES
ELEV. 90'-0" AGL
CENTERLINE OF NEW VERIZON WIRELESS PANEL ANTENNAS
ELEV. 81'-0" AGL NEW VERIZON WIRELESS 8' HIGH
PANEL ANTENNAS, (9) TOTAL, (3)
PER SECTOR
NEW VERIZON WIRELESS RADIOS,
(12) TOTAL, (4) PER SECTOR, (9)
LICATED BEHIND ANTENNAS & (3)
LOCATED ON NEW RADIO DUAL
PIPE RING MOUNT
NEW VERIZON WIRELESS
90'-0" HIGH MONOPINE
TOP OF NEW VERIZON WIRELESS MONOPINE STRUCTURE & PANEL ANTENNA
ELEV. 85'-0" AGL
NEW VERIZON WIRELESS
HYBRID CABLES, (2) TOTAL
BOTTOM OF NEW VERIZON WIRELESS MONOPINE BRANCHES
ELEV. 20'-0" AGL
NEW VERIZON WIRELESS 8'-0" HIGH
CHAIN-LINK FENCE
NOTE:
PAINT ALL NEW VERIZON WIRELESS
EQUIPMENT ON TOWER TO MATCH
MONOPINE
NEW VERIZON WIRELESS 2'Ø
MICROWAVE ANTENNA, (1) TOTAL
NEW VERIZON WIRELESS 6'Ø
MICROWAVE ANTENNA, (1) TOTAL
CENTERLINE OF NEW VERIZON WIRELESS MICROWAVE ANTENNAS
ELEV. 71'-0" AGL
CENTERLINE OF NEW VERIZON WIRELESS MICROWAVE ANTENNAS
ELEV. 71'-0" AGL
CENTERLINE OF FUTURE PANEL ANTENNAS BY OTHERS
ELEV. 61'-0" AGL
CENTERLINE OF FUTURE PANEL ANTENNAS BY OTHERS
ELEV. 61'-0" AGL
GROUND LEVEL
ELEV. 0'-0" AGL
3/8" = 1'-0" (24x36)
(OR)
SCALE:
3/16" = 1'-0" (11x17)
0 1'2'3'A-5SOUTH EQUIPMENT ELEVATION
WEST EQUIPMENT ELEVATION 23/8" = 1'-0" (24x36)
(OR)
SCALE:
3/16" = 1'-0" (11x17)
0 1'2'3'
EQUIPMENT
ELEVATIONS
A-5133/8" = 1'-0" (24x36)
(OR)
SCALE:
3/16" = 1'-0" (11x17)
0 1'2'3'NORTH EQUIPMENT ELEVATION
43/8" = 1'-0" (24x36)
(OR)
SCALE:
3/16" = 1'-0" (11x17)
0 1'2'3'EAST EQUIPMENT ELEVATION
GROUND LEVEL
ELEV. 0'-0" AGL
GROUND LEVEL
ELEV. 0'-0" AGL
GROUND LEVEL
ELEV. 0'-0" AGL
AGL 0'-0" = 196.1' NAVD 88
AGL 0'-0" = 196.1' NAVD 88AGL 0'-0" = 196.1' NAVD 88
AGL 0'-0" = 196.1' NAVD 88
TELCO
BOX INTERSECT ELEC.
METER
NEW VERIZON WIRELESS
HYBRID CABLES, (2) TOTAL
NEW VERIZON WIRELESS 90'-0" HIGH
MONOPINE (PARTIALLY SHOWN FOR
CLARITY)
NEW VERIZON WIRELESS
HYBRID CABLES, (2) TOTAL
NEW VERIZON WIRELESS 90'-0"
HIGH MONOPINE (PARTIALLY
SHOWN FOR CLARITY)
NEW VERIZON WIRELESS 90'-0"
HIGH MONOPINE (PARTIALLY
SHOWN FOR CLARITY)
NEW VERIZON WIRELESS
GPS ANTENNA, (1) TOTAL
NEW VERIZON WIRELESS
HYBRID CABLES, (2) TOTAL
NEW VERIZON WIRELESS 90'-0"
HIGH MONOPINE (PARTIALLY
SHOWN FOR CLARITY)
NEW VERIZON WIRELESS
ICE-BRIDGE
NEW VERIZON WIRELESS GPS
ANTENNA, (1) TOTAL
NEW VERIZON WIRELESS
OUTDOOR EQUIPMENT ON NEW
15'-0" X 8'-0" CONCRETE PAD
NEW VERIZON WIRELESS
GPS ANTENNA, (1) TOTAL
NEW VERIZON WIRELESS RAYCAPS,
(2) TOTAL, (1) LOCATED AT TOWER,
(1) LOCATED AT EQUIPMENT AREA
NEW VERIZON WIRELESS
OUTDOOR EQUIPMENT ON NEW
15'-0" X 8'-0" CONCRETE PAD
NEW VERIZON WIRELESS
HYBRID CABLES, (2) TOTAL
NEW VERIZON WIRELESS
ICE-BRIDGE
NEW VERIZON WIRELESS
SERVICE LIGHTS W/6-HOUR
TIMER, (4) TOTAL
NOTE: THE ORIGINAL SIZE OF THIS PLAN IS 24" X 36". SCALE RATIO IS NOT VALID FOR REDUCED OR ENLARGED SHEET SIZESSHEET TITLE:
ISSUE STATUS
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
DRAWINGS IS PROPRIETARY & CONFIDENTIAL TO
VERIZON WIRELESS
ANY USE OR DISCLOSURE OTHER THAN AS IT RELATES
TO VERIZON WIRELESS IS STRICTLY PROHIBITED
2785 MITCHELL DRIVE, BLDG 9WALNUT CREEK, CA 945984338 SHORTHORN DR.CHICO, CA 95973PSL# 491608KEEFER03/19/2020 FA090% ZONING
DESCRIPTIONDATE BYREV.
TM
SAN DIEGO, CA 92126
619.736.3766
9020 ACTIVITY RD.
www.sacw.com
03/27/2020 FA1100% ZONING
05/22/2020 FA2100% ZONING
08/20/2020 FA3REVISED 100% ZONING
08/28/2020 FA4REVISED 100% ZONING
12/02/2020 FA5REVISED 100% ZONING
NEW VERIZON WIRELESS
ELECTRICAL METER, TELCO
BOX & INTERSECT CABINET
W/GENERATOR RECEPTACLE
ON NEW H-FRAME
NEW PORTABLE
FIRE EXTINGUISHER
(CLASS 4A-60BC)
TELCO
RBOX
POWER/
MISC
CAB.
BATTERY/
CAB.
NEW VERIZON WIRELESS
ELECTRICAL METER, TELCO
BOX & INTERSECT CABINET
W/GENERATOR RECEPTACLE
ON NEW H-FRAME
NEW VERIZON WIRELESS SERVICE
LIGHTS W/6-HOUR TIMER, (4) TOTAL
NEW VERIZON WIRELESS
8'-0" HIGH CHAIN-LINK
FENCE (PARTIALLY SHOWN
FOR CLARITY)
NEW VERIZON WIRELESS
8'-0" HIGH CHAIN-LINK FENCE
(PARTIALLY SHOWN FOR
CLARITY)
NEW VERIZON WIRELESS
8'-0" HIGH CHAIN-LINK FENCE
(PARTIALLY SHOWN FOR
CLARITY)
NEW VERIZON WIRELESS
SERVICE LIGHTS W/6-HOUR
TIMER, (4) TOTAL
NEW VERIZON WIRELESS
ELECTRICAL METER, TELCO
BOX & INTERSECT CABINET
W/GENERATOR RECEPTACLE
ON NEW H-FRAME
NEW VERIZON WIRELESS
8'-0" HIGH CHAIN-LINK
FENCE (PARTIALLY SHOWN
FOR CLARITY)
FUTURE
MISC.
CAB.
FUTURE
MISC.
CAB.
BATTERY/
CAB.
NEW VERIZON WIRELESS
OUTDOOR EQUIPMENT ON NEW
15'-0" X 8'-0" CONCRETE PAD
STANDBY
30KW AC
GENERATORNEW VERIZON WIRELESS 30KW
GENERAC STANDBY
GENERATOR W/210 GALLON
DIESEL TANK (UL142) ON NEW
5'-0" X 10'-0" CONCRETE PAD
STANDBY
30KW AC
GENERATOR
STANDBY
30KW AC
GENERATOR
NEW VERIZON WIRELESS 30KW
GENERAC STANDBY
GENERATOR W/210 GALLON
DIESEL TANK (UL142) ON NEW
5'-0" X 10'-0" CONCRETE PAD
NEW VERIZON WIRELESS 30KW
GENERAC STANDBY
GENERATOR W/210 GALLON
DIESEL TANK (UL142) ON NEW
5'-0" X 10'-0" CONCRETE PAD
NEW VERIZON WIRELESS
OUTDOOR EQUIPMENT ON NEW
15'-0" X 8'-0" CONCRETE PAD
NEW STEP DOWN
TRANSFORMER ON
NEW 4'-2" X 4'-4"
CONCRETE PAD
NEW STEP DOWN
TRANSFORMER ON NEW
4'-2" X 4'-4" CONCRETE PAD
NEW BOLLARD, (3) TOTAL ,
(2) FIXED & (1) MOVABLE
N.T.S.
SCALE E-11
M G2P
TO MISC. CABINET
GG
150A
2"C-3#1/0, 1#6 GROUND, COPPER,
THHN/THWN-2
CKT 22
EXISTING
VERIZON
WIRELESS
MISC.
CABINET
EXISTING
48V DC
POWER
PLANT
CKTS (1,3) (5,7) (6,8) (9,11) (13,15) (17,19) (21,23) (25,27) & (29)
CKT 10 &12
NTS
SCALE:
NTS
SCALE:2
1-LINE DIAGRAM,
PANEL SCHEDULE
& UTILITY NOTES
1-LINE DIAGRAM
WP / J BOX
SERVICE LIGHTS
(TYP. OF 4)
1"C - 2#12, 1#12 GROUND
COPPER, THHN/THWN-2
6-HR WIND UP
TIMER SWITCH
1"C - 2#12, 1#12
GROUND, COPPER,
THHN/THWN-2
4 (3/4" C - 6# 10, 1# 10 GROUND
COPPER, THHN/ THWN-2) & 3/4" C-
2#12, 1#12 GROUND, COPPER THHN /
THWN-2
1"C - 2#12, 1#12 GROUND
COPPER, THHN/THWN-2
(STANDBY GENERATOR
BATTERY CHARGER)
1"C - 2#12, 1#12 GROUND
COPPER, THHN/THWN-2
(STANDBY GENERATOR BLOCK
HEATER)
NEW VERIZON WIRELESS 30KW
GENERAC STANDBY GENERATOR
W/210 GALLONS DIESEL TANK UL142
ANCHORED TO CONCRETE SLAB
1"C FOR ALARM WIRING TO MISC.
CABINET
#4 AWG PER GENERAC
REQUIREMENTS
MAIN GROUND
RING SYSTEM
2"C - 3 #4/0, 1#6 GROUND, COPPER
THHN/THWN-2 (UP TO 150 FT)
PANEL SCHEDULE
KEY NOTES:
2
3
200A/2P ILC 120/240 V, 1 PHASE, 3
WIRE, MAIN PANEL BY INTERSECT,
INC- NEMA 3R ENCLOSURE
INTERSECT LOAD CENTETR
W/ 30 CIRCUIT POSITIONSNEW 3/4"-1#6 GROUND,
COPPER BONDED TO MAIN
GROUND SYSTEM
2
NEW INTEGRATED LOAD CENTER (PANEL A) INTERSECT
INC MANUFACTURE (AA 300-3R SERIES MODEL AA 3003R -
458 - 6M - 3S) W/200AMP/2POLE, ATS, 120/208 V, 1-PHASE,
3WIRE, 42KAIC W/30 POSITIONS PROVIDED BY VERIZON
WIRELESS.
NEW AUTOMATIC TRANSFER SWITCH GENERAC ASCO
SERIES 300L, 200 AMP, 120/208V, 1PHASE, 3 WIRE, 2 POLE,
42 KAIC
ATS
3
CKT 18
CKT 20
LOAD PHASE 1
ADDITIONAL 25% CONTINUOUS LOAD =
DESCRIPTION C
16,000
8
B NO.PHASE 1
6
4
2
PHASE 2 CB DESCRIPTION
15,600
TOTAL LOAD (PHASE 1 & 2) =
LOAD PHASE 2
48VDC POWER PLANT
RECTIFIER #1 3
16
1
14
5
18
7
9
11
31,600
TOTAL LOAD 32,000
TOTAL AMPS 134 AMPS=
=
CKT NO.CKT
13
15
19 20
21 22
23 24
25 26
60A
2P
27 28
29 30
17
20A
2P
2P
20A
2P
2P
2P
2P
2P
2P
20A
15A
1P
SURGE SUPPRESSOR-
-
2,400 -
-
-
-
-
-
-
-
-
-
-48VDC POWER PLANT INTERIOR OUTLET
48VDC POWER PLANT
RECTIFIER #2
48VDC POWER PLANT
RECTIFIER #3
48VDC POWER PLANT
RECTIFIER #4
48VDC POWER PLANT
RECTIFIER #5
48VDC POWER PLANT
RECTIFIER #6
48VDC POWER PLANT
RECTIFIER #7
48VDC POWER PLANT
RECTIFIER #8
SPACE
SPACE
SPACE
SPACE
-
-
-
-
2,400
-
400
SERVICE/ TECH LIGHTS
MISC. CABINET RECEPTACLE #11P
20A
1P
1,200
3,600
3,600
2,600
2,900
20A
20A
20A
20A
20A
20A
1,200
1,200
2,000
1,800
1,200
-
-
20AMISC. CABINET RECEPTACLE #21P
MAIN ELECTRICAL PANEL
120/240 V, 1 PHASE, 3 WIRE, 200 AMP BUS
200 AMP/2P, ATS MAIN BREAKER
MANUFACTURED BY INTERSECT, INC MODEL AA3003R SERIES
10
12
STDBY GENERATOR BATT. CHARGER
STDBY GENERATOR BLOCK HEATER20A
1P1,800
-NOTE: THE ORIGINAL SIZE OF THIS PLAN IS 24" X 36". SCALE RATIO IS NOT VALID FOR REDUCED OR ENLARGED SHEET SIZESSHEET TITLE:
ISSUE STATUS
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF
DRAWINGS IS PROPRIETARY & CONFIDENTIAL TO
VERIZON WIRELESS
ANY USE OR DISCLOSURE OTHER THAN AS IT RELATES
TO VERIZON WIRELESS IS STRICTLY PROHIBITED
2785 MITCHELL DRIVE, BLDG 9WALNUT CREEK, CA 945984338 SHORTHORN DR.CHICO, CA 95973PSL# 491608KEEFER03/19/2020 FA090% ZONING
DESCRIPTIONDATE BYREV.
TM
SAN DIEGO, CA 92126
619.736.3766
9020 ACTIVITY RD.
www.sacw.com
03/27/2020 FA1100% ZONING
05/22/2020 FA2100% ZONING
08/20/2020 FA3REVISED 100% ZONING
08/28/2020 FA4REVISED 100% ZONING
12/02/2020 FA5REVISED 100% ZONING
20AMISC. CABINET RECEPTACLE #11P
20AMISC. CABINET RECEPTACLE #21P20A
1P
EXISTING
VERIZON
WIRELESS
MISC.
CABINET
1"C - 2#12, 1#12
GROUND, COPPER,
THHN/THWN-2
CKT 14 &16
EXISTING TRANSFORMER T-3080
(NEW VERIZON WIRELESS
POWER P.O.C.)
G
N
MMELECTRICAL SERVICE
TERMINATION
UNDERGROUND PULL
BOX, NEMA 3R. UNISTRUT
MOUNTED. 400A, 1 PHASE,
3 WIRE, 120/240
SCI = 18,000 AMPS
CAT
#R9000EE G
N
6"X6"X36" NEMA 3R SCREW
COVER WIREWAY
NEW 3/4" C W/ #2 GROUND COPPER
BONDED TO 5/8" X 8' LONG COPPER
CLAD STEEL GROUND ROD
NEW 3/4" C W/ #2 GROUND COPPER
BONDED TO 5/8" X 8' LONG
COPPERCLAD STEEL GROUND ROD
CAT # 224MTBP 200A FUSIBLE
PULL-OUT
#2 GROUND COPPER
(2) ELECTRICAL METERING 200
AMPERE, 120/240 VOLT, 1 PHASE,
3 WIRE
NEW (1) 2" CONDUIT BY GC AND
CONDUCTORS BY P.P. (± 520 FT)
NEW PG&E/ VERIZON WIRELESS ELECTRICAL
METER 120/240 V, 1 PHASE, 3 WIRE, 100 AMP,
28 KVA, NEMA 3R ENCLOSURE.
1
1
UTILITY GENERAL NOTES:
1.ALL NEW GROUNDINGS FOR ELECTRICAL ROUTE METER MUST BE DONE PER CEC, NEC
& LOCAL BUILDING & SAFETY REQUIREMENTS.
2.ALL NEW CONDUIT FROM ELECTRICAL ROUTE METER TO THE SITE MUST BE RGS
CONDUITS. INSTALL WEATHERPROOF PULL BOXES AS REQD. PER CEC, NEC & LOCAL
BLDG. & SAFETY REQUIREMENTS & MUST HAVE TRAFFIC COVERS.
3.ALL NEW PULL BOXES MUST BE HOT-DIPPED GALVANIZED AND WEATHERPROOF
4.ALL NEW WIRE SPLICES PULL BOXES DONE PER CEC & NEC.
5.FIELD VERIFY EXACT ELECTRICAL CONDUIT ROUTE.
6.VERIZON WIRELESS NEW METER/MAIN NEED TO BE LABELED & ALL CLEARANCE FOR
ELECTRICAL EQUIPMENT BY CEC & NEC.
7.NEW GROUND RODS MAY BE USED FOR SITE GROUNDING IF DESIRED RESISTANCE IS
ACHIEVED.
8.CONTRACTOR TO INSTALL UTILITY CONDUIT (LATERAL).
9.UTILITY POINTS OF SERVICE AND WORK / MATERIALS SHOWN ARE BASED UPON
PRELIMINARY INFORMATION PROVIDED BY THE UTILITY COMPANY AND ARE FOR BID
PURPOSES ONLY.
10.CONTRACTOR SHALL COORDINATE WITH UTILITY COMPANY FOR FINAL AND EXACT
WORK / MATERIALS REQUIREMENTS AND CONSTRUCT TO UTILITY COMPANY
ENGINEERING PLANS AND SPECIFICATIONS ONLY. CONTRACTOR SHALL FURNISH AND
INSTALL ALL CONDUIT, PULL ROPES, CABLES, PULL BOXES, CONCRETE ENCASEMENT
OF CONDUIT (IF REQUIRED), TRANSFORMER PAD, BARRIERS, POLE RISERS,
TRENCHING, BACKFILL, PAY ALL UTILITY COMPANY FEES AND INCLUDE ALL
REQUIREMENTS IN SCOPE OF WORK.
NTS
SCALE:
NTS
SCALE:3UTILITY NOTES
GGGGGG
NEW 11"X17" HAND HOLE AS
NEEDED
NEW 50 KVA TRANSFORMER 1PHASE
3 WIRE 120/240V CSD 42KVA
T
2"C (U/G-PVC SCH 40 ±) 3 #3/0, 1#6
GROUND, COPPER THHN/THWN-2
NEW 3/4" C W/ #2 GROUND,
COPPER BONDED TO 5/8" X 10'
LONG COPPERCLAD STEEL
GROUND ROD
3416 AIC