GAS SUPPRESSION SYSTEM REPORT
SYSTEM ID: Siemens Date: 12/29/20 (ANNUAL
n SEMI-ANNUAL
Customer: Feather Falls Casino & Lodge Property Address: 3 Alverda Oroville Ca
Contact: Monitoring Information: Central Station
Name: Damon Pound Central Station:
Phone: (530)533-3885 Acct#: 47-3726
Email: Phone: 1-800-722-0364
System Type: # of Systems Notes:
❑HALON
❑ CO2
E FM-200 1
n INERGEN
n OTHER
Panel Type: Model:
YES NO N/A NOTES
Panel in Normal Condition ❑✓ ❑ ❑
Panel In Trouble ❑ ❑✓ ❑
Is Power Light on ❑✓ ❑ ❑
LED Lights Verified ❑✓ ❑ ❑
Disconnect Switch ❑✓ ❑ ❑
Silence/Reset Switch Operates ❑✓ ❑ ❑
Batteries Indicate Proper Charge ❑✓ ❑ ❑
r-FoOT "ft0TMLL Fl R E II
I PROTECTION, DM &=awn, BE.
BATTERIES VOLTS/AMPS DATE PASS FAIL
Battery#1 12v/8 amp hr 12/20 0✓ ❑
Battery#2 12v/8 amp hr 12/20 1
CYLINDERS
# S/N HYD DATE AGENT CAP FULL WT INSP WT PSI
1 AA402714 11/08 22 59 N/A 360
DEVICES
TYPE QTY ALARM TROUBLE PASS FAIL N/A
SMOKE 2 0✓ 0✓ 0✓ 0 0
PULL STATION 1 0✓ 0 Q 0 0
ABORT SWITCH 1 0 0 0✓ 0 0
MAINT/DISC SWITCH 0 0 0 0 0 E
SOLINOID 1 0 0 0 0 0
AC SHUT DOWN 2 0 0 0✓ 0 0
POWER SHUNT 0 0 0 0 0 0✓
BELLS 1 0✓ 0 0✓ 0 0
HORN/STROBE 2 0✓ 0 E 0 0
OTHER 0 0 ❑ 0 0
OTHER 0 0 0 0 0
ITOOT 9
ROTECTION, INC. I Aunt scsEcuRrigi, II
DESIGN • INSTALLATION • INSPECTION • REPAIR
Redding Office:3092 Crossroads Dr. Ste. 1,Redding,CA 96003•Phone:(530)223-2492
Greater Bay Area Office:2150 Portola Ave.Ste.D-108,Livermore,CA 94551•(925)209-6164
Chico Office: 170 Erma Ct,Chico,CA 95928•Phone:(530)826-3013/Fax:(530)893-3013
Rocklin Office:4000 Alvis Ct.,Rocklin,CA 95677• Phone:(916)663-3582/Fax:(916)663-3583
C.L.C16#783132&C10#998129
YES NO QTY NOTES
Were Tested Dectors Cleaned
Proper safety signage installed ✓
Did the monitoring station receive signals ✓ _
System returned to normal condition ✓
Proper authorities/personnel been notified
Equipment % tested this inspection n25% 50% 75% ✓ 100%
Were Any Deficiencies Found? n YES n NO
Follow Up or Repairs Needed? n YES n NO
This FM-200 is located in the bus Server room.
All batteries are newly replaced.
Inspected by:
Stephen Rampenthal/Jessica Castro 12/29/20
Inspector Date