Roland Erickson PV Plan Set 1.2
EMPIRE SOLAR GROUP 9 EXCHANGE PL, SUITE 400 SALT LAKE CITY, UT 84111 VICINITY MAP AERIAL MAP PV-1 REV #1: 2/19/2021 REV #2: REV #3: LICENSE HOLDER SIGNATURE: SAM PARTIDA ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL COMPLY WITH THE FOLLOWING APPLICABLE CODES: ·2019 CBC / 2018 IBC ·2019 CRC / 2018 IRC ·2019 CEC / 2020 NEC ·2019 CMC / 2018 UMC ·2019 CPC / 2018 UPC ·2019 CFC / 2018 IFC ·2019 BUILDING ENERGY EFFICIENCY STANDARDS ·2019 CALIFORNIA ENERGY CODE TITLE 24 ·2019 CALIFORNIA HEALTH AND SAFETY CODE ·CEC ARTICLE 690 ·CFC ARTICLE 605.11 ·IEEE STANDARD 929 ·UL STANDARD 1741 ·OSHA 29 CFR 1910.269 ·WHERE APPLICABLE, RULES OF THE PUBLIC UTILITIES COMMISSION REGARDING SAFETY AND RELIABILITY ·THE AUTHORITY HAVING JURISDICTION ·MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS ·2017 LAEC, 2017 LABC, 2017 LAMC, 2013 NATIONAL FIRE ALARM CODE (NFPA 72), 2016 CALIFORNIA ENERGY CODE, 2017 LA GREEN CODE ·ELECTRICAL EQUIPMENT SHALL BE LISTED BY A CITY OF LOS ANGELES RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT GOVERNING CODES PV-1 - COVER PAGE PV-2 - PROPERTY PLAN PV-3 - SITE PLAN PV-4 - 1-LINE DIAGRAM & CALCULATIONS PV-5 - LABELS PV-6 - ELECTRICAL PHOTOS PV-7 - OPTIMIZER MAP- PV-8 - PLACARD SHEET INDEX: GENERAL 1.1. UTILITY SHALL BE NOTIFIED BEFORE ACTIVATION OF PV SYSTEM. 2.110.2 APPROVAL: ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION. 3.CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO INITIATING CONSTRUCTION. 4.CONTRACTOR SHALL REVIEW ALL MANUFACTURER INSTALLATION DOCUMENTS PRIOR TO INITIATING CONSTRUCTION. 5.ALL EQUIPMENT AND ASSOCIATED CONNECTIONS OF INVERTERS, MODULES, PV SOURCE CIRCUITS, BATTERY CONNECTIONS, ETC. AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL BE INSTALLED ONLY BY QUALIFIED PERSONNEL (CEC 690.4(E)). 6.THE CONTRACTOR OR OWNER MUST PROVIDE ROOF ACCESS (LADDER TO ROOF) FOR THE ALL REQUIRED INSPECTIONS. LADDERS MUST BE OSHA APPROVED, MINIMUM TYPE I WITH A 250 LB RATING, IN GOOD CONDITION AND DESIGNED FOR ITS INTENDED USE. 7.SMOKE ALARMS AND CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED ONTO THE EXISTING DWELLING AS PER THE 2013 CRC. THESE SMOKE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED OUTSIDE EACH BEDROOM AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. THESE ALARMS MAY BE SOLELY BATTERY OPERATED IF THE PHOTOVOLTAIC PROJECT DOES NOT INVOLVE THE REMOVAL OF INTERIOR WALL AND CEILING FINISHES INSIDE THE HOME; OTHERWISE, THE ALARMS MUST BE HARD WIRED AND INTERCONNECTED. (CRC R314, R315) 8.SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED PER CRC SECTIONS R314 AND 315 TO BE VERIFIED AND INSPECTED BY THE INSPECTOR IN THE FIELD. 9.CONTRACTOR SHALL VERIFY THAT THE ROOF STRUCTURE WILL WITHSTAND THE ADDITIONAL LOADS. 9.LAG SCREWS SHALL PENETRATE A MINIMUM 2" INTO SOLID SAWN STRUCTURAL MEMBERS AND SHALL NOT EXCEED MANUFACTURER RECOMMENDATIONS FOR FASTENERS INTO ENGINEERED STRUCTURAL MEMBERS. 10.AN ACCESS POINT SHALL BE PROVIDED THAT DOES NOT PLACE THE GROUND LADDER OVER OPENINGS SUCH AS WINDOWS OR DOORS ARE LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION AND IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES, OR SIGNS. (CRC R331.4.2) 11.WHERE DC CONDUCTORS ARE RUN INSIDE BUILDING, THEY SHALL BE CONTAINTED IN A METAL RACEWAY; THEY SHALL NOT BE INSTALLED WITHIN 10" OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE COVERED BY THE PV MODULES AND EQUIPMENT. (CEC 690.31(E)(1)) 12.PLUMBING AND MECHANICAL VENTS THROUGH THE ROOF SHALL NOT BE COVERED BY SOLAR MODULES - NO BUILDING, PLUMBING, OR MECHANICAL VENTS TO BE COVERED, OBSTRUCTED OR ROUTED AROUND SOLAR MODULES. 13.ALL FIELD-INSTALLED JUNCTION, PULL, AND OUTLET BOXES LOCATED BEHIND MODULES SHALL BE ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF A MODULE SECURED BY REMOVABLE FASTENERS. ELECTRICAL 1.WIRING MATERIALS SHALL COMPLY WITH MAXIMUM CONTINUOUS CURRENT OUTPUT AT 25°C AND MAXIMUM VOLTAGE AT 600V; WIRE SHALL BE WET RATED AT 90°C. 2.EXPOSED PHOTOVOLTAIC SYSTEM CONDUCTORS ON THE ROOF WILL BE USE-2 OR PV TYPE WIRE. 3.PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED. THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATE COLOR-CODING, MARKING TAPE, TAGGING OR OTHER APPROVED MEANS 4.ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE RAIN-TIGHT AND APPROVED FOR USE IN WET LOCATIONS. (CEC 314.15) 5.WHERE CONDUCTORS ARE INSTALLED UNDERGROUND, SECTION 300.5 OF THE CEC MUST BE FOLLOWED TO ENSURE PROPER PROTECTION. 6.ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS. (CEC 250.90, 250.96) 7.WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, CONTRACTOR SHALL SIZE THEM ACCORDING TO APPLICABLE CODES. 8.REMOVAL OF A UTILITY-INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BUILDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PV SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTOR. 9.FOR GROUNDED SYSTEMS, THE PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS SHALL BE PROVIDED WITH A GROUND-FAULT PROTECTION DEVICE OR SYSTEM THAT DETECTS A GROUND FAULT, INDICATES THAT FAULT HAS OCCURRED, AND AUTOMATICALLY DISCONNECTS ALL CONDUCTORS OR CAUSES THE INVERTER TO AUTOMATICALLY CEASE SUPPLYING POWER TO OUTPUT CIRCUITS. (CEC 690.35(C)) 10.FOR UNGROUNDED SYSTEMS, THE INVERTER IS EQUIPPED WITH GROUND FAULT PROTECTION AND A GFI FUSE PORT FOR GROUND FAULT INDICATION. 11.PV MODULE FRAMES SHALL BE BONDED TO RACKING RAIL OR BARE COPPER GEC/EGC PER THE MODULE MANUFACTURER'S LISTED INSTRUCTION SHEET. 12.PV MODULE RACKING RAIL SHALL BE BONDED TO BARE COPPER G.E.C VIA WEEB LUG, ILSCO GBL-4DBT LAY-IN LUG, OR EQUIVALENT LISTED LUG. 13.THE PHOTOVOLTAIC INVERTER WILL BE LISTED AS UL 1741 COMPLIANT. 14.RACKING AND BONDING SYSTEM TO BE UL2703 RATED. 15.ANY REQUIRED GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT. (CEC 250.64(C)) 16.WHEN BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, THE BREAKERS SHALL NOT READ "LINE AND LOAD". 17.WHEN APPLYING THE 120% RULE OF CEC 705.12(D)(2), THE SOLAR BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUS FROM THE MAIN BREAKER PER 705.12(D)(7). 18.THE WORKING CLEARANCE AROUND THE EXISTING ELECTRICAL EQUIPMENT AS WELL AS THE NEW ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH CEC 110.26(A) ERIKSON , ROLAND 62 ARCHER AVE GRIDLEY, CALIFORNIA 95948 LICENSE # 1062912 JOB #: 16724 DATE: 2/19/2021 DRAWN BY: KM COVER PAGE PARCEL MAP ERIKSON RESIDENCE PHOTOVOLTAIC SYSTEM 62 ARCHER AVE GRIDLEY, CALIFORNIA 95948 SYSTEM SIZE: 3.30 kW-DC | 3.80 kW-AC MODULE: (10) SILFAB SIL-330 HL INVERTER: ( 1 ) SOLAREDGE SE3800H-US N EMPIRE SOLAR GROUP 9 EXCHANGE PL, SUITE 400 SALT LAKE CITY, UT 84111 SCALE: 0.002076 SINGLE FAMILY HOME PROPERTY LINE SEPTIC TANK AND LEACH LINE LEACH FIELD PROPOSED 10 PANEL GROUND MOUNT DR I V E W A Y LEGEND: PROPERTY LINE: ERIKSON , ROLAND 62 ARCHER AVE GRIDLEY, CALIFORNIA 95948 LICENSE # 1062912 PROPERTY PLAN PV-2 DRIVEWAY: 62 ARCHER AVE LICENSE HOLDER SIGNATURE: SAM PARTIDA APN: 024-020-021 358'-4" 196'-2" 231' 100'-11" 112'-3" 106'-3" 64'-1" 133'-11" 142'-10" 179'-10" 69'-6" JOB #: 16724 DATE: 2/19/2021 DRAWN BY: KM 35'-3" 39'-9" 28'-4" N EMPIRE SOLAR GROUP 9 EXCHANGE PL, SUITE 400 SALT LAKE CITY, UT 84111 SYSTEM LEGEND UM MP AC MAIN SERVICE METER AND SERVICE POINT MAIN SERVICE PANEL UTILITY AC DISCONNECT SCALE: 1/16" = 1'-0" TRENCHING MODULE INFORMATION MODULE TYPE SILFAB SIL-330 HL MAX DESIGN LOAD (WIND & SNOW)83.5 & 112.8 LB/FT2 MODULE WEIGHT 41 LBS/MODULE MODULE DIMENSIONS (H X L X D)66.9" X 39.4" X 1.5" MODULE AREA 18.30 FT2 I ( 1 ) SOLAREDGE SE3800H-US INVERTER WITH INTEGRATED DC DISCONNECT (10) SILFAB SIL-330 HL WITH SOLAREDGE P340 OPTIMIZERS MOUNTED UNDER EACH MODULE. SECTION 1: 10 MODULES AZIMUTH: 180° PITCH: 25° GROUND MOUNT GROUND MOUNT STRING DETAIL SOLAREDGE STRINGS STRING DETAIL SOLAREDGE STRINGS STRING DETAIL SOLAREDGE STRINGS STRING DETAIL SOLAREDGE STRINGS STRING # 1: 10 MODULES STRING DETAIL SOLAREDGE STRINGS 1 ERIKSON , ROLAND 62 ARCHER AVE GRIDLEY, CALIFORNIA 95948 LICENSE # 1062912 SITE PLAN PV-3 LICENSE HOLDER SIGNATURE: SAM PARTIDA WIND UPLIFT AT ATTACHMENT POINTS IS PROVIDED WITH THE ENGINEERING LETTER. SUPPORT LOCATIONS HAVE BEEN OPTIMIZED TO WITHSTAND UPLIFT PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 3.30 kW AC SYSTEM SIZE: 3.80 kW UM AC PANELS TILTED AT 25 DEGREES MP I TRENCHING 65 FEET 2" PVC SCHEDULE 80 MIN. 18" DEEP JOB #: 16724 DATE: 2/19/2021 DRAWN BY: KM EMPIRE SOLAR GROUP 9 EXCHANGE PL, SUITE 400 SALT LAKE CITY, UT 84111 ERIKSON , ROLAND 62 ARCHER AVE GRIDLEY, CALIFORNIA 95948 LICENSE # 1062912 GROUND MOUNT DETAILS PV-3.1 LICENSE HOLDER SIGNATURE: SAM PARTIDA 20'-6" 10'-2" JOB #: 16724 DATE: 2/19/2021 DRAWN BY: KM EMPIRE SOLAR GROUP 9 EXCHANGE PL, SUITE 400 SALT LAKE CITY, UT 84111 PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 3.300 kW AC SYSTEM SIZE: 3.800 kW INVERTER: ( 1 ) SOLAREDGE SE3800H-US MODULE: (10) SILFAB SIL-330 HL NOTES: ·MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM - INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE ATTACHED FOR SPECIFICATIONS ·IF APPLICABLE: ·PV DC SYSTEM IS UNGROUNDED ·PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH NEC 250.58 AND 690.47(A) ·PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS SHALL COMPLY WITH NEC 690.1(G) ·BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM SIGNAGE, PAGE ·BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP; WHEN PRESENT, THE GEC TO BE CONTINUOUS ·INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A ·CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS PV MODULE ELECTRICAL SPECIFICATIONS MODULE TYPE SILFAB SIL-330 HL POWER MAX (PMAX)330W OPEN CIRCUIT VOLTAGE (VOC)40.1V SHORT CIRCUIT CURRENT (ISC)10.4A MAX POWER-POINT VOLTAGE (VMP)33.6V MAX POWER-POINT CURRENT (IMP)9.8A SERIES FUSE RATING 20A INVERTER ELECTRICAL SPECIFICATIONS INVERTER TYPE SOLAREDGE SE3800H-US MAX INPUT DC VOLTAGE 480V MAX INPUT CURRENT 10.5A NOMINAL DC INPUT VOLTAGE 380V MAXIMUM OUTPUT POWER 3800W MAXIMUM CONT. OUTPUT CURRENT 16A CEC EFFICIENCY 99% POWER OPTIMIZER ELECTRICAL SPECIFICATIONS OPTIMIZER TYPE SOLAREDGE P340 RATED INPUT DC POWER 340W MAXIMUM INPUT VOLTAGE (VOC)48V MAXIMUM SHORT CIRCUIT CURRENT (ISC)11A MAXIMUM DC INPUT CURRENT 13.75A MAXIMUM OUTPUT CURRENT 15A MAXIMUM OUTPUT VOLTAGE 60V MINIMUM STRING LENGTH 8 MAXIMUM POWER PER STRING 5700W (6000W WITH SE7600- SE11400) BUSBAR CALCULATIONS - PV BREAKER - 120% RULE MAIN BUS RATING 125 MAIN DISCONNECT RATING 100 PV BREAKER RATING 20 (MAIN BUS RATING x 1.2) - MAIN DISCONNECT RATING >= OCPD RATING (125A x 1.2) - 100 A >= 20A, OK CONDUCTOR AND CONDUIT SCHEDULE TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE 1 PV WIRE #10 2 - L1 L2 FREE AIR N/A 1 BARE COPPER #6 1 - BARE FREE AIR N/A 2 THWN-2 #10 2 - L1 L2 EMT 3/4" 2 THWN-2 EGC #10 1 - GND EMT 3/4" 3 THWN-2 #10 3 - L1 L2 N EMT 3/4" 3 THWN-2 EGC #10 1 - GND EMT 3/4" P340 DC OPTIMIZERS 10 SILFAB SIL-330 HL IN STRING #1 OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS INVERTER TYPE SOLAREDGE 3800H-US # OF INVERTERS 1 MAX CONTINUOUS OUTPUT CURRENT 16A (# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <= OCPD RATING ( 1 x 16A x 1.25)= 20.00A <= 20A, OK ERIKSON , ROLAND 62 ARCHER AVE GRIDLEY, CALIFORNIA 95948 LICENSE # 1062912 1-LINE DIAGRAM & CALCULATIONS PV-4 LICENSE HOLDER SIGNATURE: SAM PARTIDA MAIN PANEL UPGRADE REQUIRED. 100A MAIN BREAKER / 125A MAIN BUS RATING MAIN SERVICE DISCONNECT 100 A/2P FACILITY GROUND (E) GROUND ROD + (E) WATER PIPE BOND (N)PV OCPD 2P 20A (N)125A RATED MAIN SERVICE PANEL (N) AC DISCONNECT MIN. 30A 240V NEMA 3R NON-FUSIBLE, VISIBLE LOCKABLE LABELED UTILITY SERVICE 120/240V SINGLE PHASE METER # 107546050 UTILITY INTERACTIVE INVERTER SOLAREDGE SE3800H-US SOLAREDGE RAPID SHUTDOWN KIT & INTEGRATED DC DISCONNECT JOB #: 16724 DATE: 2/19/2021 DRAWN BY: KM EMPIRE SOLAR GROUP 9 EXCHANGE PL, SUITE 400 SALT LAKE CITY, UT 84111 ! WARNING ! DUAL POWER SOURCES. SECOND SOURCE IS PV SYSTEM LABEL 7 PHOTOVOLTAIC AC DISCONNECT OPERATING CURRENT: 40 A AC OPERATING VOLTAGE: 240 V AC LABEL 5 AT POINT OF INTERCONNECTION, MARKED AT DISCONNECTING MEANS [NEC 690.54] ! WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. LABEL 3 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.13 AND 690.15] PHOTOVOLTAIC DC DISCONNECT UTILITY AC DISCONNECT LABEL 10 AT EACH DC DISCONNECTING MEANS [NEC 690.13(B)] LABEL 12 AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(G)] LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 13 AT EACH AC DISCONNECTING MEANS [NEC 690.13(B)] ! CAUTION ! PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED ! WARNING ! POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVISE LABEL 14 AT POINT OF INTERCONNECTION OVERCURRENT DEVICE [NEC 705.12(B)(2)(3)(B)] LABEL 9 AT UTILITY METER [NEC 690.56(B)] LABEL 4 AT EACH DC DISCONNECTING MEANS [NEC 690.53] LABEL 11 AT RAPID SHUTDOWN SWITCH [NEC 690.56(C)]. LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 8 LABELING NOTES 1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. 1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED. 1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535] PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION [NEC 690.56(B)] AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 7 OR LABEL 8 MUST IDENTIFY PHOTOVOLTAIC SYSTEM [NEC 705.12(B)(4)] WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS. PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN BATHROOMS [NEC 690.4(D),(E)] TURN RAPID SHUTDOWN SWICH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY LABEL 1 AT RAPID SHUTDOWN SYSTEM [NEC 690.56(C)(1)(A)]. ! WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPLOSED TO SUNLIGHT LABEL 2 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.15] MAXIMUM VOLTAGE: 480 V DC MAXIMUM CIRCUIT CURRENT:15 A DC MAX RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED):15 A DC ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B) LABEL 6 AT RAPID SHUTDOWN DISCONNECT SWITCH [NEC 690.56(C)(3)]. ERIKSON , ROLAND 62 ARCHER AVE GRIDLEY, CALIFORNIA 95948 LICENSE # 1062912 ELECTRICAL LABELS PV-5 LICENSE HOLDER SIGNATURE: SAM PARTIDA LABELS ARE NOT DRAWN TO SCALE #03-359 LOCAL CODES MAIN SERVICE PANEL FOR ILLUSTRATION ONLY (NOT ACTUAL MSP) MAIN SERVICE METER PV SUB PANEL (IF USED) AC DISCONNECT UTILITY AC DISCONNECT (IF USED) STRING INVERTER (IF USED)JUNCTION BOX (IF USED) #XX-XXX-XXX PRODUCTION METER 4 5 7 89 10 13 2 2 2 2 2 1 6 6 6 FOR MICRO INVERTERS ONLY (NO KNIFE SWITCH DISCONNECT) 611 11 1414 3 3 3 3 DC DISCONNECT (IF USED) BI-DIRECTIONAL METER WARNING: PHOTOVOLTAIC POWER SOURCE PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS WARNING THIS SERVICE METER IS ALSO SERVED BY A PHOTOVOLTAIC SYSTEM JOB #: 16724 DATE: 2/19/2021 DRAWN BY: KM EMPIRE SOLAR GROUP 9 EXCHANGE PL, SUITE 400 SALT LAKE CITY, UT 84111 ERIKSON , ROLAND 62 ARCHER AVE GRIDLEY, CALIFORNIA 95948 LICENSE # 1062912 ELECTRICAL PHOTOS PV-6 LICENSE HOLDER SIGNATURE: SAM PARTIDA JOB #: 16724 DATE: 2/19/2021 DRAWN BY: KM EMPIRE SOLAR GROUP 9 EXCHANGE PL, SUITE 400 SALT LAKE CITY, UT 84111 FOR INSTALLER USE ONLY ERIKSON , ROLAND 62 ARCHER AVE GRIDLEY, CALIFORNIA 95948 LICENSE # 1062912 OPTIMIZER MAP PV-7 LICENSE HOLDER SIGNATURE: SAM PARTIDA JOB #: 16724 DATE: 2/19/2021 DRAWN BY: KM N C A U T I O N P O W E R T O T H I S B U I L D I N G I S S U P P L I E D F R O M T H E F O L L O W I N G S O U R C E S W I T H D I S C O N N E C T S L O C A T E D A S S H O W N ! ! S E R V I C E 1 O F 1 I N V E R T E R U T I L I T Y M E T E R A C D I S C O N N E C T 6 2 A R C H E R A V E , G R I D L E Y , C A L I F O R N I A 9 5 9 4 8 M A I N S E R V I C E P A N E L * Chubb provides error and omission insurance to Silfab Solar Inc. Monocrystalline PV Module 120 Half-Cell SIL-330 HL JUST-IN-TIME TOPPERFORMER BAAARRA DOMESTIC PRODUCTION Silfab Solar manufactures PV modules in two automated locations within North America. Our 500+ North American team is ready to help our partners win the hearts and minds of customers, providing customer service and product delivery that is direct, efficient and local. AESTHETICALLY PLEASING All black sleek design, ideal for high-profile residential or commercial applications. PID RESISTANT PID Resistant due to advanced cell technology and material selection. In accordance to IEC 62804-1. INDUSTRY LEADING WARRANTY All our products include an industry leading 25-year product workmanship and 30-year performance warranty. 35+ YEARS OF SOLAR INNOVATION Leveraging over 35+ years of worldwide experience in the solar industry, Silfab is dedicated to superior manufacturing processes and innovations such as Bifacial and Back Contact technologies, to ensure our partners have the latest in solar innovation. NORTH AMERICAN QUALITYSilfab is the leading automated solar module manufacturer in North America. Utilizing premium quality materials and strict quality control management to deliver the highest efficiency, premium qualityPV modules. HALF-CELL TECHNOLOGY Designed to improve the module’s performance and durability. BAA / ARRA COMPLIANT Silfab panels are designed and manufactured to meet Buy American Act Compliance. The US State Department, US Military and FAA have all utilized Silfab panels in their solar installations. LIGHT AND DURABLE Engineered to accommodate low load bearing structures up to 5400Pa. The light-weight frame is exclusively designed for wide-ranging racking compatibility and durability. QUALITY MATTERS Total automation ensures strict quality controls during the entire manufacturing process at our ISO certified facilities. Si l f a b - S I L - 3 3 0 - H L - B - 2 0 2 0 0 6 1 8 • N o r e p r o d u c t i o n o f a n y k i n d i s a l l o w e d . D a t a a n d i n f o r m a t i o n i s s u b j e c t t o m o d i f i c a t i o n s w i t h o u t n o t i c e . © S i l f a b , 2 0 2 0 . Silfab Solar Inc. 240 Courtneypark Drive East Mississauga ON L5T 2Y3 Canada Tel +1 905-255-2501 | Fax +1 905-696-0267 info@silfabsolar.com | www.silfabsolar.com Silfab Solar Inc. 800 Cornwall Ave Bellingham WA 98225 USA Tel +1 360-569-4733 2019 TOP PERFORMER PV MODULERELIABILITY SCORECARD Electrical Specifications SIL-330 HL mono PERC Test Conditions STC NOCT Module Power (Pmax)Wp 330 249.4 Maximum power voltage (Vpmax)V 33.6 30.2 Maximum power current (Ipmax)A 9.8 8.3 Open circuit voltage (Voc) V 40.1 37.3 Short circuit current (Isc) A 10.4 8.5 Module efficiency %19.4 18.3 Maximum system voltage (VDC)V 1000 Series fuse rating A 20 Power Tolerance Wp 0 to +10 Measurement conditions: STC 1000 W/m² • AM 1.5 • Temperature 25 °C • NOCT 800 W/m² • AM 1.5 • Measurement uncertainty ≤ 3%• Sun simulator calibration reference modules from Fraunhofer Institute. Electrical characteristics may vary by ±5% and power by 0 to +10W. Temperature Ratings SIL-330 HL mono PERC Temperature Coefficient Isc 0.064 %/°C Temperature Coefficient Voc -0.28 %/°C Temperature Coefficient Pmax -0.36 %/°C NOCT (± 2°C)45 °C Operating temperature -40/+85 °C Mechanical Properties and Components SIL-330 HL mono PERC Metric Imperial Module weight 18.6 kg ±0.2 kg 41 ±0.4 lbs Dimensions (H x L x D)1700 mm x 1000 mm x 38 mm 66.9 in x 39.4 in x 1.5 in Maximum surface load (wind/snow)*4000 Pa rear load / 5400 Pa front load N/m2 83.5/112.8 lb/ft^2 Hail impact resistance ø 25 mm at 83 km/h ø 1 in at 51.6 mph Cells 120 Half Cells - Si mono PERC5 busbar 120 Half Cells - Si mono PERC5 busbar Glass 3.2 mm high transmittance, tempered, DSM antireflective coating 0.126 in high transmittance, tempered, DSM antireflective coatingCables and connectors (refer to installation manual)1350 mm, ø 5.7 mm, MC4 compatible 53.1 in, ø 0.22 in, MC4 compatible Backsheet High durability black backsheet, superior hydrolysis resistance,multi-layer dielectric film Frame Anodized Aluminum (Black) Bypass diodes 3 diodes-30SQ045T (45V max DC blocking voltage, 30A max forward rectified current) Junction Box UL 3730 Certified, IP67 rated Warranties SIL-330 HL mono PERC Module product workmanship warranty 25 years** Linear power performance guarantee 30 years ≥ 97% end 1st year ≥ 90% end 12th year ≥ 82% end 25th year ≥ 80% end 30th year Certifications SIL-330 HL mono PERC Product UL 61730***, IEC 61215/61730***, CEC listed***, IEC 62716 Ammonia Corrosion; IEC61701:2011 Salt Mist Corrosion Certifed, UL Fire Rating: Type 2 Factory ISO9001:2015 * Warning. Read the Safety and Installation Manual for mounting specifications and before handling, installing and operating modules. **12 year extendable to 25 years subject to regis-tration and conditions outlined under “Warranty” at www.silfabsolar.com. ***Certification and CEC listing in progress. Third-party generated pan files from Fraunhofer-Institute for Solar Energy Systems ISE are available for download at: www.silfabsolar.com/downloads Modules Per Pallet: 26 Pallets Per Truck: 36 Modules Per Truck: 936 39.37"(1000mm) 2 .3 6 "(6 0 m m ) 1 6 .7 "(4 2 5 m m ) 3 3 .4 6 "(8 5 0 m m ) 1 6 .7 "(4 2 5 m m ) 7 .8 7 "(2 0 0 m m ) 38.11"(968mm) 4 7 .2 4 "(1 2 0 0 m m ) 6 6 .9 3 "(1 7 0 0 m m ) 1.5"(38mm) 6 6 .9 3 "(1 70 0 m m ) 1 .5 "(38 mm ) 1.02"(26mm) 0 .0 7 "(0 .1 8 mm ) 0 .47 "(1 2 m m ) 0.28"(7mm) 0.39"(10mm) 7X12(x4) Mounting Hole Drainage (x8) C C Grounding Hole I N V E R T E R S solaredge.com Optimized installation with HD-Wave technology Specifically designed to work with power optimizers Built-in module-level monitoring Outdoor and indoor installation Optional: Revenue grade data, ANSI C12.20 Class 0.5 (0.5% accuracy) Record-breaking efficiency Fixed voltage inverter for longer strings Integrated arc fault protection and rapid shutdown for NEC 2014 and 2017, per article 690.11 and 690.12 Extremely small UL1741 SA certified, for CPUC Rule 21 grid compliance Single Phase Inverter with HD-Wave Technology for North America SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US / SE7600H-US / SE10000H-US / SE11400H-US 12-25 YEARWARRANTY SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US OUTPUT Rated AC Power Output 3000 3800 @ 240V3300 @ 208V 5000 6000 @ 240V5000 @ 208V 7600 10000 11400 @ 240V10000 @ 208V VA Maximum AC Power Output 3000 3800 @ 240V3300 @ 208V 5000 6000 @ 240V5000 @ 208V 7600 10000 11400 @ 240V10000 @ 208V VA AC Output Voltage Min.-Nom.-Max. (211 - 240 - 264)Vac AC Output Voltage Min.-Nom.-Max. (183 - 208 - 229)----Vac AC Frequency (Nominal)59.3 - 60 - 60.5(1)Hz Maximum Continuous Output Current @240V 12.5 16 21 25 32 42 47.5 A Maximum Continuous Output Current @208V -16 -24 --48.5 A GFDI Threshold 1 A Utility Monitoring, Islanding Protection, Country Configurable Thresholds Yes INPUT Maximum DC Power @240V 4650 5900 7750 9300 11800 15500 17650 W Maximum DC Power @208V -5100 -7750 --15500 W Transformer-less, Ungrounded Yes Maximum Input Voltage 480 Vdc Nominal DC Input Voltage 380 400 Vdc Maximum Input Current @240V(2)8.5 10.5 13.5 16.5 20 27 30.5 Adc Maximum Input Current @208V(2)-9 -13.5 --27 Adc Max. Input Short Circuit Current 45 Adc Reverse-Polarity Protection Yes Ground-Fault Isolation Detection 600k Sensitivity Maximum Inverter Efficiency 99 99.2 % CEC Weighted Efficiency 99 99 @ 240V98.5 @ 208V % Nighttime Power Consumption < 2.5 W ADDITIONAL FEATURES Supported Communication Interfaces RS485, Ethernet, ZigBee (optional), Cellular (optional) Revenue Grade Data, ANSI C12.20 Optional(3) Rapid Shutdown - NEC 2014 and 2017 690.12 Automatic Rapid Shutdown upon AC Grid Disconnect STANDARD COMPLIANCE Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07 Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI) Emissions FCC Part 15 Class B INSTALLATION SPECIFICATIONS AC Output Conduit Size / AWG Range 1" Maximum / 14-6 AWG 1" Maximum /14-4 AWG DC Input Conduit Size / # of Strings / AWG Range 1" Maximum / 1-2 strings / 14-6 AWG 1" Maximum / 1-3 strings / 14-6 AWG Dimensions with Safety Switch (HxWxD)17.7 x 14.6 x 6.8 / 450 x 370 x 174 21.3 x 14.6 x 7.3 / 540 x 370 x 185 in / mm Weight with Safety Switch 22 / 10 25.1 / 11.4 26.2 / 11.9 38.8 / 17.6 lb / kg Noise < 25 <50 dBA Cooling Natural Convection Operating Temperature Range -13 to +140 / -25 to +60(4) (-40˚F / -40˚C option)(5)˚F / ˚C Protection Rating NEMA 4X (Inverter with Safety Switch) (1) For other regional settings please contact SolarEdge support (2) A higher current source may be used; the inverter will limit its input current to the values stated (3) Revenue grade inverter P/N: SExxxxH-US000NNC2(4) For power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note-na.pdf(5) -40 version P/N: SExxxxH-US000NNU4 Single Phase Inverter with HD-Wave Technology for North America SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/ SE7600H-US / SE10000H-US / SE11400H-US © SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are trademarks of their respective owners. Date: 03/2019/V01/ENG NAM. Subject to change without notice. P O W E R O P T I M I Z E R solaredge.com PV power optimization at the module-level Specifically designed to work with SolarEdge inverters Up to 25% more energy Flexible system design for maximum space utilization Fast installation with a single bolt Next generation maintenance with module- level monitoring Meets NEC requirements for arc fault protection (AFCI) and Photovoltaic Rapid Shutdown System (PVRSS) Module-level voltage shutdown for installer and firefighter safety Superior efficiency (99.5%) Mitigates all types of module mismatch losses, from manufacturing tolerance to partial shading Power Optimizer For North America P320 / P340 / P370 / P400 / P405 / P505 25 YEARWARRANTY © SolarEdge Technologies Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are trademarks of their respective owners. Date: 08/2019/V02/ENG NAM. Subject to change without notice. (6) For detailed string sizing information refer to: http://www.solaredge.com/sites/default/files/string_sizing_na.pdf(7) It is not allowed to mix P405/P505 with P320/P340/P370/P400 in one string(8) A string with more than 30 optimizers does not meet NEC rapid shutdown requirements; safety voltage will be above the 30V requirement(9) For SE14.4KUS/SE43.2KUS: It is allowed to install up to 6,500W per string when 3 strings are connected to the inverter (3 strings per unit for SE43.2KUS) and when the maximum power difference between the strings is up to 1,000W(10) For SE30KUS/SE33.3KUS/SE66.6KUS/SE100KUS: It is allowed to install up to 15,000W per string when 3 strings are connected to the inverter (3 strings per unit for SE66.6KUS/SE100KUS) and when the maximum power difference between the strings is up to 2,000W Power Optimizer For North America P320 / P340 / P370 / P400 / P405 / P505 Optimizer model (typical module compatibility) P320 (for 60-cell modules) P340 (for high-power 60-cell modules) P370 (for higher- power60 and 72-cellmodules) P400 (for 72 & 96-cell modules) P405 (for thin film modules) P505 (for highercurrent modules) INPUT Rated Input DC Power(1)320 340 370 400 405 505 W Absolute Maximum Input Voltage (Voc at lowest temperature) 48 60 80 125(2)87(2)Vdc MPPT Operating Range 8 - 48 8 - 60 8 - 80 12.5 - 105 12.5 - 87 Vdc Maximum Short Circuit Current (Isc) 11 10.1 14 Adc Maximum DC Input Current 13.75 12.5 17.5 Adc Maximum Efficiency 99.5 % Weighted Efficiency 98.8 98.6 % Overvoltage Category II OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current 15 Adc Maximum Output Voltage 60 85 Vdc OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) Safety Output Voltage per Power Optimizer 1 ± 0.1 Vdc STANDARD COMPLIANCE EMC FCC Part15 Class B, IEC61000-6-2, IEC61000-6-3 Safety IEC62109-1 (class II safety), UL1741 Material UL94 V-0 , UV Resistant RoHS Yes INSTALLATION SPECIFICATIONS Maximum Allowed System Voltage 1000 Vdc Compatible inverters All SolarEdge Single Phase and Three Phase inverters Dimensions (W x L x H)129 x 153 x 27.5 / 5.1 x 6 x 1.1 129 x 153 x 33.5 / 5.1 x 6 x 1.3 129 x 159 x 49.5 / 5.1 x 6.3 x 1.9 129 x 162 x 59 / 5.1 x 6.4 x 2.3 mm / in Weight (including cables)630 / 1.4 750 / 1.7 845 / 1.9 1064 / 2.3 gr / lb Input Connector MC4(3)Single or dual MC4(3)(4)MC4(3) Input Wire Length 0.16 / 0.52 m / ft Output Wire Type / Connector Double Insulated / MC4 Output Wire Length 0.9 / 2.95 1.2 / 3.9 m / ft Operating Temperature Range(5) -40 - +85 / -40 - +185 ˚C / ˚F Protection Rating IP68 / NEMA6P Relative Humidity 0 - 100 % (1) Rated power of the module at STC will not exceed the optimizer “Rated Input DC Power”. Modules with up to +5% power tolerance are allowed(2) NEC 2017 requires max input voltage be not more than 80V(3) For other connector types please contact SolarEdge(4) For dual version for parallel connection of two modules use the P405. In the case of an odd number of PV modules in one string, installing one P405 dual version power optimizer(5) For ambient temperature above +85°C / +185°F power de-rating is applied. Refer to Power Optimizers Temperature De-Rating Technical Note for more details. PV System Design Using a SolarEdge Inverter(6)(7) Single Phase HD-Wave Single phase Three Phase 208V Three Phase 480V Minimum String Length (Power Optimizers) P320, P340, P370, P400 8 10 18P405 / P505 6 8 14Maximum String Length (Power Optimizers)25 25 50(8) Maximum Power per String 5700 (6000 with SE7600-US - SE11400-US)5250 6000(9)12750(10)W Parallel Strings of Different Lengths or Orientations Yes Geo Logic Groundscrews General Information Model Number N 76 x 1600 x 3.75-3x 16M A. Shaft Diameter 76mm (3 Inches) B. Length 1600mm (63") C. Weight (lbs.) 27 lbs. Construction Continous CNC welded helix Material ISO 630 FE 360 A steel Hot dipped galvanized to DIN EN ISO 1461 Wall thickness specific for rocky substrates Typical load limits observed in Western soils Vertical uplift: 6000 Lbs. Vertical uplift to Failure: 8000+ lbs. Lateral Load with 90% recovery: 2850 lbs. General Notes Groundscrews should be installed by qualified installers. The examples of application contained in the catalog, on the internet or in other media can help you decide which type of screw is right for your application. The number and the required size of the respective screws depends on different factors such as, soil, weight and the wind and snow loads of the respective superstructures. On large scale applications, it is recommended that foundations (the number and the size of the screws) be based on a static calculation. We deny any liability for damages or failures, due to errors in static calculations. ECO Foundation Systems Inc. of Sacramento, California Tel: 916-913-0306 - Email: info@ecofoundationsystems.com www.ecofoundationsystems.com Geo Logic Groundscrews Dimensions Model Number NF 76 x 1600 -3.75 3x 16M A. Shaft Outside Diameter 76mm (3" Inches) B. Length 1600mm (63") C. Inner Diameter 68mm (2 5/8") D. Max. Depth Setting 1500mm (48") E. Set Nut Size 16mm General Notes Groundscrews should be installed by qualified installers. The examples of application contained in the catalog, on the internet or in other media can help you decide which type of screw is right for your application. The number and the required size of the respective screws depends on different factors such as, soil, weight and the wind and snow loads of the respective superstructures. On large scale applications, it is recommended that foundations (the number and the size of the screws) be based on a static calculation. We deny any liability for damages or failures, due to errors in static calculations. It is recommended that pipe be inserted a minimum depth of 12 inches below set screws. Set screws must be torqued to a minimum of 45 ft. lbs.. ECO Foundation Systems Inc. of Sacramento, California Tel: 916-913-0306 - Email: info@ecofoundationsystems.com www.ecofoundationsystems.com TECHTIPS ALTERNATIVE FOUNDATION METHODS FORGROUND MOUNT SYSTEMS There are various foundation methods for ground-based solar installations outside of poured concrete. This document will discuss each option in detail, and go over the unique considerations associated with each foundation type. GROUND MOUNT SYSTEM In the IronRidge Ground Mount System, poured concrete piers are used as the standard foundation type. The concrete piers provide excellent resistance to vertical and lateral loads, and can be constructed with readily available materials. Using Ground-based Design Assistant and concrete piers gives you standardized design options that will meet a wide range of requirements—and are backed by stamped engineering letters. This approach lowers engineering and permitting costs, enables faster timelines, and reduces risk. However, the Ground Mount System can also be installed using alternative foundation methods such as helical piles, earth screws, driven piers, or above-ground ballast blocks. Each of these foundation methods comes with its own set of challenges, considerations, and benefits. Concrete Piers Driven Piers Helical Piles Ballasted TECHTIPS © 2016 IronRidge, Inc. All rights reserved. Visit www.ironridge.com or call 1-800-227-9523 for more information. Version 1.10 HELICAL PILES/EARTH SCREWS PILE-DRIVEN OR VIBRATORY-DRIVEN PIERS BALLASTED SYSTEM These products provide very good resistance to uplift, but provide minimal resistance to lateral loads compared to the standard IronRidge concrete foundations. Lower lateral load resistance results in: • Shorter E-W pier spans • More piers (foundations) • Additional bracing All of these factors will increase system costs. From an installation standpoint, these anchors may be faster to install, but increased material, equipment and engineering costs may outweigh any labor savings. To design a Ground Mount system with these anchors, a Professional Engineer (PE) will need to know the bearing capacity of the soil. For smaller systems, manufacturers of these anchors will come on-site to conduct pull tests to evaluate pullout strength and lateral resistance failure with their anchors. For larger systems, a soils report is typically required in addition to the pull tests. After the capacity of the anchor is determined, the PE can compare it to the reaction forces acting on each footing (provided by Ground-based Design Assistant) to determine the allowable pier spans. The PE can then provide a letter for the foundation design. This foundation method requires analysis to understand the bearing capacity and corrosivity of the soil (performed by a Geotechnical Engineer). From an installation standpoint, specialized equipment and operators are required to install these types of foundations which increases the overall system costs.Additionally, this option does not utilize a helical blade or screw, which means that it will have a lower resistance to uplift forces. This necessitates deeper foundations. As with a helical pile or earth screw foundation, a PE will be required to determine the pier depth and spacing, and provide a letter for the foundation design. This is a common foundation method especially for brownfield sites, such as landfills, where there is a cap layer that cannot be penetrated. Ballast foundations can be either cast-in-place or pre-cast depending on project requirements and shipping costs. To design a system with this foundation type, a PE must determine how large the concrete blocks need to be based on the reaction forces of the system (provided by Ground-based Design Assistant). The PE can then provide a letter for the foundation design. 2'-6" CL EQ DISTANCE EQ DISTANCE 14' MAX VARIES CL 7'-6" 87.10 TILT ANGLE VARIES 6" MAX 6" MAX C B D A 2" GALVANIZED PIPE FINAL GRADE XR1000 RAIL MODULE MOUNTING SYSTEM BONDING END CLAMP (CAMO) 3/8" MODULE GAP(TYP) MODULE MOUNTING SYSTEM BONDING MID CLAMP (UFO) MODULE XR1000 RAIL CROSS PIPE XR1000 RAIL CONNECTION DETAIL TO HORIZONTAL CROSS PIPE (CONNECTOR, RAIL SGA 2") DETAIL D 1/8" MIN MODULE MOUNTING SYSTEM BONDING END CLAMP (UFO) MODULE XR1000 RAIL DESIGN CRITERIA & MATERIAL SPECIFICATIONS: PER ASCE 7-10/WIND LOADING MAXIMUM MODULE WEIGHT IS 3 psf ALUMINUM XR1000 RAIL MODULE HARDWARE 300 SERIES STAINLESS STEEL AND ALUMINUM A380 APPROVED PIPE: - ASTM A53 GR B, GALV. SCHD 40 - ALLIED MECHANICAL TUBING, 50 KSI, 12 GA, GALV EXHIBIT: EX-0001 4 MODULE ROWS, 2" PIPE OR DETAIL A DETAIL C DETAIL B (MODULE REMOVED FOR CLARITY) 10/16/2018 -- -- -- -- 10/16/2018 -- -- -- TC -- B GROUND MOUNT SYSTEM 2" PIER, 4 SOLAR MODULE ROWS WEIGHT:SHEET 1 OF 5 Q.A. MFG APPR. ENG APPR. CHECKED DRAWN DIMENSIONS ARE IN INCHES.TOLERANCES: .XX: +/- .030XXX: +/- .010ANGLES: +/- 1° REV.A DWG. NO.SIZE SCALE:1:25 EX-0001 EQ DISTANCE 14' MAX EQ DISTANCE 85.44 TILT ANGLE VARIES 7'-6" VARIESCL 2'-6" CL 6" MAX 6" MAX C B D A 3" GALVANIZED PIPE FINAL GRADE XR1000 RAIL MODULE MOUNTING SYSTEM BONDING END CLAMP (CAMO) DETAIL C 3/8" MODULE GAP(TYP) MODULE MOUNTING SYSTEM BONDING MID CLAMP (UFO) MODULE XR1000 RAIL XR1000 RAIL CONNECTION DETAIL TO HORIZONTAL CROSS PIPE (CONNECTOR, RAIL SGA 3") CROSS PIPEDETAIL D 1/8" MIN MODULE MOUNTING SYSTEM BONDING END CLAMP (UFO)OR DETAIL A MODULE XR1000 RAIL EXHIBIT: EX-0001 4 MODULE ROWS, 3" PIPE DETAIL B (MODULE REMOVED FOR CLARITY) 10/16/2018 DESIGN CRITERIA & MATERIAL SPECIFICATIONS: PER ASCE 7-10/WIND LOADING MAXIMUM MODULE WEIGHT IS 3 psf ALUMINUM XR1000 RAIL MODULE HARDWARE 300 SERIES STAINLESS STEEL AND ALUMINUM A380 APPROVED PIPE: - ASTM A53 GR B, GALV. SCHD 40 - ALLIED MECHANICAL TUBING, 50 KSI, 8 GA, GALV APPROVED 3" PIPE - ALLIED MECHANICAL TUBING- 45 ksi YIELD STRENGTH- GALVANIZED (ALLIED FLOCOAT, GATORSHIELD, OR HOT DIPPED) TOP CAP SET SCREW INSTALL TORQUE: 16 ft*lbs ALLIED MECH. TUBING, 8 GA - ASTM A53 GR B- 35 ksi YIELD STRENGTH- HOT DIPPED GALVANIZED TOP CAP SET SCREW INSTALL TORQUE: 20 ft*lbs SCHD. 40 PIPE B GROUND MOUNT SYSTEM 3" PIER, 4 SOLAR MODULE ROWS WEIGHT:SHEET 2 OF 5 REV.A DWG. NO.SIZE SCALE:1:25 EX-0001 7'-6" 0.4 X L (MAX) 0.4 X L (MAX) (L)PIER SPACING (L)PIER SPACING SOLAR MODULE XR1000 RAIL MODULE SUPPORT CROSS PIPE PLAN VIEW (6 PIER LAYOUT SHOWN) SLOPE DOWN CL CL CL EXHIBIT: EX-0001 10/16/2018 B GROUND MOUNT SYSTEM, 4 SOLAR MODULE ROWS WEIGHT:SHEET 3 OF 5 REV.A DWG. NO.SIZE SCALE:1:25 EX-0001 2'-6" CL VARIES (L)PIER SPACING VARIES CL A FINAL GRADE NORTH VIEW CL CL MAX GAP 1/2" U-BOLT 1 PIECE CAST ALUMINUM TOP CAP GALVANIZED PIPE 12.0" 6.0" 3.5"TYP 1.25" 6.0" INTERNAL SPLICE CROSS PIPE 4X SELF DRILLING SCREWS (1/4"-14 x 3/4") 4X 9 FT-LBS CROSS PIPE THREADED COUPLING EXHIBIT: EX-0001 SPLICING CROSS PIPE 10/16/2018 ALLIED MECHANICAL TUBE SPLICE SCH. 40 PIPE SPLICEALLIED MECHANICAL TUBE OR SCH. 40 PIPE SPLICE DETAIL A B GROUND MOUNT SYSTEM, 4 SOLAR MODULE ROWS WEIGHT:SHEET 4 OF 5 REV.A DWG. NO.SIZE SCALE:1:25 EX-0001 TILT ANGLE VARIES 14' MAX EQ DISTANCE EQ DISTANCE 87.10 D/3 FOUNDATION DEPTH-D PIER DIA 2500 PSI CONCRETE FOUNDATION GALVANIZED PIPE ADD BRACE WHEN REQUIRED FINAL GRADE NOTE: THE ATTACHED SPAN TABLES ARE BASED ON USING DRILLED CAST-IN-PLACE CONCRETE PIER FOUNDATION SYSTEM. OTHER FOUNDATION SYSTEMS (EG. SCREW ANCHORS, DRIVEN PIERS) ARE PERMISSIBLE BUT MAY REQUIRE ADDITIONAL BRACING AND/OR REDUCED SPAN. PLEASE CONTACT IRONRIDGE FOR MORE INFORMATION. EXHIBIT: EX-0001 CONCRETE FOUNDATION DETAILS 10/16/2018 B GROUND MOUNT SYSTEM, 4 SOLAR MODULE ROWS WEIGHT:SHEET 5 OF 5 REV.A DWG. NO.SIZE SCALE:1:25 EX-0001 Cut Sheet v1.20 Microinverter Bonding Hardware .26 .61 .75 .24 1/4-20 THD .59 7/16" Head 1/4-20 THD .24 1 2 1)Bolt, T CSTM 1/4-20 x .75 2)Nut, Flange Hex 1/4-20 Item Number Description 1 Bolt, T CSTM 1/4-20 X .75" Lock SS 2 Nut, Flange, Hex 1/4-20 SS Part Number Description BHW-M1-01-A1 Microinverter Bonding Hardware, T-Bolt Property Value Material 300 Series Stainless Steel Finish Clear Property Value Material 300 Series Stainless Steel Finish Clear Microinverter Bonding Hardware Cut Sheet v1.0 3.0 6.5 .19 2.0 3.9 8.0 3.0 6.5 8.0 2.75 .19 2.0 6 7 2 1 3 4 5 1) Rail, Pipe Attaching Bracket 2" Bracket 3" Bracket Part Number Description GM-BRC-002 GROUND MOUNT BONDED RAIL CONNECTOR - 2” GM-BRC-003 GROUND MOUNT BONDED RAIL CONNECTOR - 3” Property Value Material AluminumFinishMill Property ValueMaterialAluminumFinishMill Item Number Component Qty in Kit 1 RAIL, 2" PIPE ATTACHING BRKT 1 2 UBOLT, CUSTOM SGA PIPE 1 3 WASHER, FLAT 3/8 GALV 2 4 WASHER, LOCK 3/8 GALV 2 5 NUT, HEX 3/8-16 GALV 2 6 BOLT, BOND 3/8-16 X .75 LG SQ HEAD 2 7 NUT, FLANGE HEX 3/8-16 SS 2 Bonded Rail Connector Cut Sheet v1.0 2.78 3.75 3/8-16 THD .375 3.91 5.00 3/8-16 THD .375 .75 .56 3/8-16 THD .35 .41 .81 .07 .41 .09 .56 3/8-16 THD .33 .75 .24 3/8-16 THD .56 2) U-bolt, Custom SGA Pipe 7) Nut, Flange Hex 3/8-16 SS 6)Bolt, Bond 3/8-16 X .75 LG SQ Head 3) Washer, Flat 3/8 Galv 4) Washer, Lock 3/8 Galv 5) Nut, Hex 3/8-16 Galv 2" U-Bolt 3" U-Bolt Property Value Material SteelFinishHot-Dip Galvanized Property Value Material SteelFinishHot-Dip Galvanized Property Value Material Stainless SteelFinishClear Property Value Material Stainless Steel Finish Clear Property Value Material SteelFinishHot-Dip Galvanized Property Value Material SteelFinishHot-Dip Galvanized Property Value Material SteelFinishHot-Dip Galvanized Cut Sheet v1.0 1 5 78 6 1.00 .53 See Table for Length .70 .25 See Table for Width 2 3 4 1) Brace, Tube CBR SQ Part Number Description Brace Tube Length Brace Tube Width 70-0200-CBR SGA 2” (7.5’) Brace Assembly (bulk)88.5"2.0" 70-0300-CBR SGA 3” (7.5’) Brace Assembly (bulk)87.0"2.5" 70-0205-CBR SGA 2” (9’) Brace Assembly, 5-Panel (bulk)106.5"2.0" 70-0305-CBR SGA 3” (9’) Brace Assembly, 5-Panel (bulk)105.0"2.5" Property Value Material Aluminum Finish Mill Item Number Component Qty in Kit 1 BRACE, TUBE CBR SQ 1 2 SLEEVE, PIPE BRACE 2 3 NUT, JAM 1/2-13 STEEL HDG 4 4 SCREW, SET 1/2-13 X 1.50 CUP PNT 4 5 BOLT, 1/2-13 HEX GALV 2 6 WASHER, FLAT 1/2 GALV 4 7 WASHER, LOCK SPRING 1/2 GALV 2 8 NUT, HEX 1/2-13 GALV 2 Diagonal Brace Cut Sheet v1.0 .75 1/2-13 THD .31 .50 1.50 .38 1/2-13 THD .75 3.5 for SGA 2" .36 4.0 for SGA 3" 1/2-13 THD .53 1.06 .10 0.53 .13 .75 1/2-13 THD .45 2.50 1/2-13 THD 3.55 2.56 .53 1.50 2.50 1/2-13 THD 2.06 2.43 .53 1.50 3) Nut, Jam 1/2-13 Steel HDG 4) Screw, Set 1/2-13 x 1.50 Cup PNT 5) Bolt, 1/2-13 Hex Galv 6) Washer, Flat 1/2 Galv 7) Washer, Lock Spring 1/2 Galv 8) Nut, Hex 1/2-13 Galv 2) Sleeve, Pipe Brace SGA 2" SGA 3" Property Value Material SteelFinishHot-Dip Galvanized Property Value Material SteelFinishHot-Dip Galvanized Property ValueMaterialSteelFinishHot-Dip Galvanized Property Value Material SteelFinishHot-Dip Galvanized Property Value Material SteelFinishHot-Dip Galvanized Property Value Material SteelFinishHot-Dip Galvanized Property ValueMaterialSteelFinishHot-Dip Galvanized Property Value Material SteelFinishHot-Dip Galvanized Cut Sheet v1.10 1 3 2 KIT, 4 PCS, END CLAMP TABLE 1: END CLAMP PART NUMBERS AND HEIGHT MILL PART NUMBER BLACK PART NUMBER HEIGHT "X" in [mm]ALLOWABLE MODULE THICKNESS in [mm] 29-7000-125 29-7000-125B 1.25 [32]1.22 - 1.28 [31.0 - 32.5] 29-7000-130 29-7000-130B 1.30 [33]1.28 - 1.32 [32.5 - 33.5] 29-7000-134 29-7000-134B 1.34 [34]1.31 - 1.37 [33.3 - 34.8] 29-7000-224 29-7000-224B 1.41 [36]1.37 - 1.45 [34.8 - 36.8]29-7000-150 29-7000-150B 1.50 [38]1.48 - 1.46 [37.5 - 38.5] 29-7000-157 29-7000-157B 1.57 [40]1.53 - 1.61 [39.0 - 41.0]29-7000-165 29-7000-165B 1.65 [42]1.62 - 1.68 [41.1 - 42.7] 29-7000-171 29-7000-171B 1.71 [43]1.68 - 1.74 [42.7 - 44.2]29-7000-214 29-7000-214B 1.81 [46]1.77 - 1.85 [45.0 - 47.0] 29-7000-187 29-7000-187B 1.875 [48]1.84 - 1.90 [46.7 - 48.3] 29-7000-204 29-7000-204B 1.97 [50]1.93 - 2.01 [49.0 - 51.1] 29-7000-230 29-7000-230B 2.30 [58]2.26 - 2.32 [57.4 - 58.9] End Clamp Cut Sheet v1.10 1.50 (Dim "X" See Table 1) .50 .125 1.38 .28 THRU .44 .59 1/4-20 Thread .24 .44 1.00 .16 1/4-20 Thread 2) BOLT, 1/4-20 X 1.00" HEX CS SST 3) Nut, Flange Hex 1/4-20 SST 1) Clamp, End Cut Sheet v1.0 1 3 2 1.00 1.16 .48 1.00 Kit, 4pcs, Grounding Mid Clamp 1) Integrated Grounding Mid Clamp Kit, 4pcs, Grounding Mid Clamp Grounding Mid Clamp Cut Sheet v1.0 .44 .59 1/4-20 THD .24 .44 .26 SEE TABLE .19 1/4-20 THD 2) Bolt, T Cstm 1/4-20 3) Nut, Flange Hex 1/4-20 SST