HomeMy WebLinkAbout CSA 158 Bi Annual Pump Test December 2020 r,e Durham pump&Irrigation
Mt P.WILSON og SONS Invoice
CL#271327 Number: 0194903-IN
Main Office: Woodland Branch:
Durham Pump,Inc. Wm.P.Wilson&Sons Date: 12/21/2020
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order I Date: 0055167 12/18/2020
Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you!
Customer#: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#158-ISHI VALLEY
7 COUNTY CENTER DR. TULIYANI DRIVE
ATTN: MARGE CHICO,CA 95973
OROVILLE,CA 95965
Confirm To: JOHN GADDIE Job Name: CSA#158 Ishi Valley
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
Item Code Description Unit WH Qty Ordered / Shipped I B.O. Price Amount
12/07/2020 COMPLETE 81-ANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
/PMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
Taxable Amount: 0.00
Non-Taxable Amount: 200.00
Net Invoice: 200.00
Signature N/A Less Discount: 0.00
Sales Tax: 0.00
Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Durham : PUmp PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#158 Ishi Valley
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/7/20
Motor Mfg: Franklin HP: 1 Meter#: 1006908237
RPM 3450 Volts 240 Phase 1 Rated Amps: 9.8
TM 80 Yes DNo Serial#
PG &E Acct. # Other:
Panel Mfg: Franklin control box NEMA Size:
Type: X/L P/W Date code
Discharge Mfg: 1 1/4 Serial#:
Non-Running Checks: Tank Model WX-302 Manufacturer Well-X-Trol
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: N/A
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: Less than 1 Meg O's to ground
Excessive or Unusual Noise Ok
[ ]Excessive or Unusual Vibration Ok
Control Devices: H.O.A. Start Switch Time Clock
Frost Start []Time Delay Other: Pres. Sw. 30-50
Amperage: Expected:
Actual: Red: 1 Yellow: 11.4 Black: 10 1 Average:
Overload Underload Even Load
Bowl Adjustment: N/A Yes fN
Comments:
Fence enclosure falling in on all 4 sides, needs repair
GPS: 39°48'32.57"N 121°53'38.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:1Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's1158 Ishi Valley1158 Reports
Durham Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#158 Ishi Valley
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/7/20
Motor Mfg: Franklin HP: 25 Meter#: 1006908237
RPM 3450 Volts 240 Phase 3 Rated Amps: 75
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: Turnas NEMA Size: 3
Type: X/L P/W Other:
Discharge Mfg: Steel 6" Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: TR9GR
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise Ok
[ 1 Excessive or Unusual Vibration Ok
J7Control Devices: X H.O.A. X Start Switch nTime Clock
Frost Start Time Delay Other: Pressure Switch
Amperage: Expected: 5
Actual: L1: 68 L2: 75 L3: 61.1 Average: 68.03
Overload Underload ITEven Load
Bowl Adjustment: N/A Yes FINo
Comments:
Slightly overloaded with uneven load but within service factor
Gate is falling apart, needs to be repaired or replaced.
GPS: 39°48'32.57"N 121°53'38.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S.\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire GSA's\158 Ishi Valley1158 Reports