HomeMy WebLinkAboutCSA 176 Bi Annual Pump Test December 2020 Durham Pump&Irrigation WNW P.WILSON a SONS Invoice
CL#271327 Number: 0194906-IN
Main Office: Woodland Branch:
Durham Pump,Inc. Wm.P.Wilson&Sons Date: 12/21/2020
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order/Date: 0055172 12/18/2020
Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you! I
Customer#: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#176 PHEASANT LANDING PH3
7 COUNTY CENTER DR. GUNTREN RD.
ATTN:MARGE CHICO,CA 95973
OROVILLE,CA 95965
Confirm To: JOHN CADDIE Job Name: CSA#176 Pheasant Landing Ph3
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
Item Code Description Unit WH Qty Ordered I Shipped I B.O. Price Amount
12/07/2020 COMPLETE BI-ANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
/PMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
Taxable Amount: 0.00
Non-Taxable Amount: 200.00
Net Invoice: 200.00
Signature N/A Less Discount: 0.00
Sales Tax: 0.00
Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Durham Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#176 -Pheasant Landing Ph. 3
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/7/2020
Motor Mfg: Franklin HP: 15 Meter#: 1006782900
RPM Volts 460 Phase 3 Rated Amps: 37.5
TM 80 Yes No Serial#
PG &E Acct. # Other: Pump Date Code: 07/01
Panel Mfg: Myers NEMA Size:
Type: X/L P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels - Service and Change if Necessary Discharge
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: 60 Amp
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: D's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank: Bad
Excessive or Unusual Vibration Ok/see comments Tank condition:
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 37 5 Pressure setting:
Actual: L9 36.8 L2 34.3 L3 35 7 Average: 35.6
Overload Underload Even Load
Bowl Adiustment: N/A OYes No
Comments:
Incoming voltage is 490V, 492V&490V
Pressure tank is water logged and needs to be replaced, pressure gauge broken
Gate repaired, lock is cut. Broken pressure gauge.
GPS: 39°48'49.58"N 121°47'40.91"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:1Pump Dept. Files\PUMP TESTS& INSPECTIONS\Cal Fire CSA's1176 Pheasant Landing 3\176 Reports
Durham ;i: Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#176 - Pheasant Landing Ph. 3
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/7/2020
Motor Mfg: Franklin HP: 1.5 Meter#:
RPM 3450 Volts 460 Phase 3 Rated Amps: 2 5
TM 80 Yes No Serial #
PG &E Acct. # Other:
Panel Mfg: NEMA Size:
Type: X X/L P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Type
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits I 'Unacceptable
Fuses - Replace if Necessary Replaced Size: CMR-6
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: O's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank: AP-80
nExcessive or Unusual Vibration Ok/see comments Tank condition: ok
nControl Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other: PRESS. SWITCH
Amperage: Expected: 2.5 Pressure setting:
Actual: R 2 5 Y 3 B 3.1 Average: 2.867
Overload Underload nEven Load
Bowl Adjustment: N/A Yes No
Comments:
GPS: 39° 48' 49.58"N 121° 47' 40.91"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS& INSPECTIONS\Cal Fire CSA's\176 Pheasant Landing 3\176 Reports