HomeMy WebLinkAboutCSA 183 Bi Annual Pump Inspection December 2020 ", Durham Pump&Irrigation WM.P.WILSON&SONS Invoice
CL#271327 Number: 0194907-IN
Main Office: Woodland Branch:
Durham Pump,Inc. Wm.P.Wilson&Sons Date: 12/21/2020
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530.891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order I Date: 0055174 12/18/2020
Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you!
Customer#: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#183-RARE EARTH SUED.
7 COUNTY CENTER DR. TIBERON WAY
ATTN:MARGE CHICO,CA 95973
OROVILLE,CA 95965
Confirm To: JOHN GADDIE Job Name: CSA#183 Rare Earth Subd
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
Item Code Description Unit WH Oty Ordered I Shipped I B.O. Price Amount
12/07/2020 COMPLETE BI-ANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
/PMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
Taxable Amount: 0.00
Non-Taxable Amount: 200.00
Net Invoice: 200.00
Signature N/A Less Discount: 0.00
Sales Tax: 0.00
Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Durhaint): Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#183 - Rare Earth Subdivision
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/7/2020
Motor Mfg: Franklin HP: 60 Meter#: 1005378640
RPM 7 Volts 480 Phase 3 Rated Amps: 7
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: SIEMANS NEMA Size: 3.5
Type: X X/L P/W Other:
Pump Mfg: ?Sub Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels - Service and Change if Necessary Discharge 6" Fab
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: FLSR 200 ID
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: St's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank:
Excessive or Unusual Vibration Ok/see comments Tank condition:
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 80.5 Pressure setting: Press Sw 50-70
Actual: L1 66 3 L2 64 7 L3 64 Average: 65
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
Slightly high incoming voltage. 491V, 492V, 490V
GPS:
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS& INSPECTIONS\Cal Fire CSA's\183 Rare Earth Subd\183 Reports
Durham '. Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#183 - Rare Earth Subdivision
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/7/2020
Motor Mfg: Franklin HP: 1.5 Meter#:
RPM 3450 Volts 240 Phase 1 Rated Amps: 11.5 MAX
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: NEMA Size:
Type: X X/L P/W Other:
Pump Mfg: ? Sub Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels - Service and Change if Necessary Discharge CAST 11/4
na Oiler Unit and/or Packing
- Electrical Leads & Connections - Repair and Tighten as Necessary
[ ]Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: 20 AMP BREAKER
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: id's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank: PC-266 TANK
Excessive or Unusual Vibration Ok/see comments Tank condition:
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other: PRESS. SWITCH
Amperage: Expected: 11.5 Pressure setting: 40-60
Actual: Y 11.5 B 12.5 R 1.3 Average: 8 467
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
Gate broken
GPS:
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:1Pump Dept. Files\PUMP TESTS& INSPECTIONS\Cal Fire CSA's\183 Rare Earth Subd1183 Reports