HomeMy WebLinkAboutCSA 169 Bi Annual Pump Maintenance December 2020 Durham Pump&Irrigation WM.P.WILSON a SONS Invoice
CL#271327 Number: 0194908-IN
Main Office: Woodland Branch:
Durham Pump,Inc. Wm.P.Wilson&Sons Date: 12/21/2020
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order/Date: 0055176 12/18/2020
Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you!
Customer 6: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#169-PHEASANT LANDING
7 COUNTY CENTER DR. AGUSTA WAY
ATTN: MARGE CHICO,CA 95973
OROVILLE,CA 95965
Confirm To: JOHN GADDIE Job Name: CSA#169 Pheasant Landing
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
Item Code Description Unit WH Qty Ordered I Shipped / B.O. Price Amount
12/07/2020 COMPLETE BI-ANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
/PMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
Taxable Amount: 0.00
Non-Taxable Amount: 200.00
Net Invoice: 200.00
Signature N/A Less Discount: 0.00
Sales Tax: 0.00
Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Durhamf'41'. Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#169 Pheasant Landing
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/7/20
Motor Mfg: Newman HP: 40 Meter#: 1005576060
RPM 1770 Volts 460 Phase 3 Rated Amps: 59
TM 80 Yes No Serial# 326TPH/DD27K2PM
PG &E Acct. # Other:
Panel Mfg: Cuttler Hammer NEMA Size: 21/2
Type: X/L P/W Other:
Pump Mfg: Peerless 6" Serial#:
Non-Running Checks: Pump Model Manufacturer Newman
[]Lubricant Levels- Service and Change if Necessary
[]Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
[ ]Incoming Idle Voltage: _ W/I Acceptable Limits Unacceptable
OFuses - Replace if Necessary Replaced Size: 100A MCP
[ ]Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise Ok/see comments Pressure tank: n/a
Excessive or Unusual Vibration Ok/see comments Tank condition: n/a
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 59 Pressure setting: PRESS SWITCH
Actual: R 46.9 Y 47.5 B 41.3 Average: 45.23
Overload Underload Even Load
Bowl Adjustment: N/A []Yes No
Comments:
NO JOCKY PUMP
No Backspin protection, needs to be addressed
Idle voltage is a little high at around 495V. System holding 40 psi pressure.
Gate is broken, Fence Broken, hard to access
GPS: 39°47'57.43"N 121°53'5.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS& INSPECTIONS\Cal Fire CSA's\169 Pheasant Landing\169 Reports
DuthMn . Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#169 Pheasant Landing
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/7/2020
Motor Mfg: Franklin Motor HP: 1.5hp Meter#: 34422R
RPM 3450 Volts 460 Phase 3 Rated Amps: 3
TM 80 ]Yes FINo Serial it
PG &E Acct. # Other:
Panel Mfg: NEMA Size:
Type: X/L P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Type: Submersible
Lubricant Levels - Service and Change if Necessary
Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: 15 amp
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: 120,000 D's to ground
Excessive or Unusual Noise Ok Pressure tank: Clayton Mark 86 gal
Excessive or Unusual Vibration Ok Condition:
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other: Pres. Sw.
Amperage: Expected: 3
Actual: L1: L2: L3: Average: 0
Overload Underload Even Load
Bowl Adjustment: Yes No
Comments:
Pump is no longer in well
GPS:
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's1169 Pheasant Landing\169 Reports