HomeMy WebLinkAboutFAI15-0052 2020 Fire Door Testing (2) ..... ..,...,... DAsmA 1300 Sumner Avenue, Cleveland, OH 44115-2851 Fax: (216)241-0105 Phone: (216)241-7333 Door&Access Systems E-Mail:dasma@dasma.com Manufacturers Association r--- ' International URL:www.dasma.com DASMA ROLLING STEEL FIRE DOOR DROP TEST FORM General NFPA 80 and Model Codes require the inspection and testing of fire doors to demonstrate proper operation, full closure, and proper reset. Perform the visual inspection before the operational check, or before the drop tests of the fire door, in order to reduce the risk of failure during the drop tests. Use the form below to record the Visual, Operational, and Drop Test results. Check Pass or Fail in the boxes. See the Guidelines for additional information. AWARNING Door could close rapidly and could result in death or serious injury. Perform drop test and reset per manufacturer's instructions. The drop tests, reset, repairs and/or maintenance should be performed by a trained door system technician with complete knowledge of this type of fire door and the manufacturer's instructions. Repair parts m. s" e stained from the original door manufacturer. After repairs are completed, the door must be tested to assure,prbper door s aeration and automatic closing capability. The fire door must be in the fully open position before the drop"rest. Re et the r oor following the drop test and test again. aggaain. /� G� / f% / / Project( • . S) �v�3p C- oA e. Company: ! 1 - Phone: Address: Mr E-mail: Wr Visual Operational Drop Drop Door Opening Size Door Mfr. Door Mfr. Inspection Check Test#1 Test#2 Location Serial No. Width Height Pass Fail Pass Fail Pass Fail Pass Fail Door I I( Y 9'Zu .OVcr1-- l A141)-5-' ✓ I ✓ V Door 77�I d' G l`6 Duet iead A 1 N 3 3B ✓ / I Door' 3 a7,�px q, %H ,due r►,ecd 11)oerA ILI 3'55 o J V v V , V Comments: PCR\rec\ Co% \ ( ora Oy) oor- - 3YS:) Co 1 \ Co ,r- 8 ©,' D 00�-- - I' . ACA'\k)5� V,►r,;-51 Incl Y- lil5wj D )rl x��- 1 . eC.Lovnine. C C ,n 54-c bu-►oi..h co c al\ a'sA(l"(` car-- Tested By: hrl -- 1/-,No 13\-r- rbu n ""Witnessed By: tqm,yts. ��Stsp_oG4a Company: 717.PV(pox—— C O YI Vick n ye Representing: $V �C— �' G1&*1. Chu 1 Wm. -.c c s Address: Lo� " 1 TV y 6-. (.111 co, CA Title: % L \ - 4 Signature/Date: ! )0/9-61Q� Signature/Date: `�� O I'^, Dg •Kms' -7A9'799vY"u Rev.6/07 o _ SMA Rolling SteeFire Door Annual Drop Test Form - RDD-271© White—Building Owner Yellow—Service Cornnanv Page 1 Printed 11/12/20 Work Order 123464 WO No: 123464 Assigned To: ELEC Project: Type: PMI Planned Date: 08/31/20 Status: RC Planned By: PM SCHEDULER PM#: 1306 Priority: Submitted By: PM SCHEDULER Safety Doc#: None Date Due: 08/31/20 Submitted Date: 09/30/20 Standard Doc#: None Building: 004 (Student&Administrative Services) Issue To: 3080475 (Hansbrough,Mike) Equipment Equipment Description Location OHDO1SAS Overhead Fire Doors#1,SAS SAS168 Welcome Center OHDO2SAS Overhead Fire Door#2,SAS SAS160 Financial Aid OHDO3SAS Overhead Fire Door#3,SAS SAS179 Admissions and Records Problem Description Door#1 cycled-no issues. Door#2 no reaction to switch up or down. Repaired 10/26 Door#3 cycled-no issues. """"'Door Co.certified/repaired. 10/26/2020 Material and Labor Requirements Equipment Part Number Description Quantity Equipment Trade Function People Hrs Notes Completed By: Completion Date: ..... ...„, DAsmA 1300 Sumner Avenue, Cleveland, OH 44115-2851 Fax: (216)241-0105 Phone:(216) 241-7333 Door&Access Systems E-Mail:dasma@dasma.com 7--\, ManuarsAssodation URL:www.dasma.com International DASMA ROLLING STEEL FIRE DOOR DROP TEST FORM General NFPA 80 and Model Codes require the inspection and testing of fire doors to demonstrate proper operation, full closure, and proper reset. Perform the visual inspection before the operational check, or before the drop tests of the fire door, in order to reduce the risk of failure during the drop tests. Use the form below to record the Visual, Operational, and Drop Test results. Check Pass or Fail in the boxes. See the Guidelines for additional information. AWARNING Door could close rapidly and could result in death or serious injury. Perform drop test and reset per manufacturer's instructions. The drop tests, reset, repairs and/or maintenance should be performed by a trained door system technician with complete knowledge of this type of fire door and the manufacturer's instructions. Repair parts must be obtained from the original door manufacturer. After repairs are completed, the door must be tested to assure proper door operation and automatic closing capability. The fire door must be in the fully open position before the drop test. Reset. , d -following the drop test and test again. Project: /3 t� i i- Cf\ 0//Ci --e'_ �' . Company: 5'7 6 - 3 F-7 Address: Phone: �°c-�--�c,� OE-mail: (?5/2 .Q,e 2311 Door Opening Size Door Mfr. Door Mfr. Visual Operational Drop Drop Location Serial No. Inspection Check Test#1 Test#2 Width Height .;rj5or Pass Fail Prail Pass Fail Pass Fail 11 se J ©or 3 61'I o n q I (AYI n asor""l o00o s5 J ✓ -./ '/ o404 o( c-r v--1' l ,nc *X 41 c rjj3 , �/ ✓ V/ 1a.4'� w ' co° WI ra Sot W I COW 35 V 4 J i .1 �cx�11 l Comments: A1\ 3-;-re- dm.r \nave SI',,-4k?. 1oC-e-S :+r' oo-4- eln-Aerloc-4S ev‘c.c c?e r�Q1a(-eok On `- oQd - 3 L M P 0 0 Tested By: C Y'2 5 v-iy,, ln-\-' 75-\--\q U O Witnessed By: 1.-NAI _1p,,.�S9c.,.4.> ,,, )1 Company: —11,Y12� 'opr- L . Representing: g E-GL ►.\t- PrN.CAI,. 0\ST Address: '� . 6— I VI/ 421, Chico ( c A Title: G.LEC-cQ\C_\A.-4 Signature/Date: A " /l- I 0 ) ) QSignature/Date: (kali%,„(,.Q7:1Z4 dkin Wook Rev.6/07 DASMA Rolling Steel Fire Door Annual Drop Test Form - RDD-271© White—Building Owner Yellnw-Service Comnanv Page 1 Printed 11/12/20 Work Order 123463 WO No: 123463 Assigned To: ELEC Project: Type: PMI Planned Date: 08/31/20 Status: RC Planned By: PM SCHEDULER PM#: 1305 Priority: 4 Submitted By: PM SCHEDULER Safety Doc#: None Date Due: 09/30/20 Submitted Date: 09/30/20 Standard Doc#: None Building: 032 (Arts) Issue To: 3080475 (Hansbrough,Mike) Equipment Equipment Description Location OHDO1ARTS Overhead Fire Door#1,Arts Arts 166 Scene Shop,West Wall OHDO2ARTS Overhead Fire Door#2,ARTS Arts 166 Scene Shop,North Wall OHDO3ARTS Overhead Fire Door#3,Arts Arts SW Hall,Adjacent to 160/184 OHDO4ARTS Overhead Fire Door#4,Arts Arts North Main Entrance,Above Doorway Leading to Theatre/Gallery Problem Description Test Fire doors and roll down fire doors. *****Door#1 has dead batteries.-Tony changing today. Door#2 cycled-no issues. Door#3 would only travel down 2'at a time. upward travel-no issues. repaired,10/26 Door#4 cycled-no issues. Door Company certified/repaired. 10/26/2020 Material and Labor Requirements Equipment Part Number Description Quantity Equipment Trade Function People Hrs Notes Completed By: Completion Date: ..... m., DAsmA 1300 Sumner Avenue, Cleveland, OH 44115-2851 Fax: (216)241-0105 Phone: (216) 241-7333 Door&AccessSystems E-Mail:dasma@dasma.com ��, ManufacturersAssodation International URL:www.dasma.com DASMA ROLLING STEEL FIRE DOOR DROP TEST FORM General NFPA 80 and Model Codes require the inspection and testing of fire doors to demonstrate proper operation, full closure, and proper reset. Perform the visual inspection before the operational check, or before the drop tests of the fire door, in order to reduce the risk of failure during the drop tests. Use the form below to record the Visual, Operational, and Drop Test results. Check Pass or Fail in the boxes. See the Guidelines for additional information. AWARNING Door could close rapidly and could result in death or serious injury. Perform drop test and reset per manufacturer's instructions. The drop tests, reset, repairs and/or maintenance should be performed by a trained door system technician with complete knowledge of this type of fire door and the manufacturer's instructions. Repair parts must be obtained from the original door manufacturer. After repairs are completed, the door must be tested to assure proper door operation and automatic closing capability. The fire door must be in the fully open position before the drop test. Reset the door following the drop test and test again. ! !� Project: L . Z Z . C . .)3r rCompany: Phone: Address: E-mail: 0 Door Opening Size Door Mfr. Door Mfr. Visual Operational Drop Drop Inspection Check Test#1 Test#2 Location Serial No. - (' Width _ Height Pass Fail Pass Fail Pass Fail Pass Fail •Tioor. l 0'7" 10 ' Corot /0214 4ci3 uL 1/ V V / V / +. Ij.%1 C qtr% f . jOtifV\101VV Cl oor ID'7'` 10 ' COrivt=t.k ' OD `4 17 ✓ V ✓ 1/ cloo (G ,2. 1 O' Corned *0'47 G ✓ 1/ ✓ t/ Comments: i , Illb OUB I !Mire, Cor ry -- -ioa... 0 V L (0 rr . /-1 co-p-fry-1 . . ' roDpe� `'10 y o.,.,e� \�oSS u � 'y d�S Tested By: CA S Y lel( i"ITC `Yl �Witnessed By: X11% IR.- 1\A,NaStitZOVA‘A. Company: ( r"C_ D on (61M,et./1. v Representing:WvTIZ---Citi=rAi-1 Cizern. COL-. Dq 3T. Address: D " 'V c , ,, _ � ' Title: E�L'�'2.,CSA►-1 All Signature/Date: 1, �-_ 0 , �o , • Signature/Date: It s,of rizn Rev.6/07 ii/A4/ oiling Steel Fire Door Annual Drop Test Form - RDD-271© White—Building Owner Yellow-Service Company Printed 11/12/20 Work Order 123465 Page 1 WO No: 123465 Assigned To: ELEC Project: Type: PMI Planned Date: 08/31/20 Status: RC Planned By: PM SCHEDULER PM#: 1307 Priority: Submitted By: PM SCHEDULER Safety Doc#: None Date Due: 08/31/20 Submitted Date: 09/30/20 Standard Doc#: None Building: 025 (Learning Resource Center) Issue To: 3080475 (Hansbrough,Mike) Equipment Equipment Description Location OHDO1LRC Overhead Fire Door#1, LRC LRC 1st Floor Hall OHDO2LRC Overhead Fire Door#2, LRC LRC 2nd Floor Hall OHDO3LRC Overhead Fire Door#3, LRC LRC 3rd Floor Hall Problem Description Door#1 low end of limit switch requires adjustment.switch requires hold to travel down. Repaired 10/26 Door#2 switch wired in reverse.cycled-no issues.*****Repaired Door#3 Low end of limit switch requires adjustment.switch requires hold to travel down. Repaired 10/26 ""'Door Co.certified/repaired 10/26/2020 Material and Labor Requirements Equipment Part Number Description Quantity Equipment Trade Function People Hrs Notes Completed By: Completion Date: ■ The Door Company 05 November 2020 Chris Boyd—Inspector Via email chris.boyd@fire.ca.gov Oroville, CA 95965 Chris, This note is to verify that we have drop tested a total of ten fire doors in three buildings at Butte College. It's our understanding that copies of the drop-test sheets certifying their proper operation at the time of the drop-test have been given to you by Butte College. Our work was completed on 10/26/2020 and included replacement of one coil cord to pass one door. Please don't hesitate to contact me directly if you have any questions. Best Regards, M ark/S. Stc�,vace ' Mark S. Stuenkel President �tsE0/), el)HYS/p44r OQDgsysre4Sr MEMBER QaowsYsr�,s� ,c)R01fj���� R`Q�FDetl7 Q Q rum °'n W� `` u4 e F IDA . n a G K J < International Door Association �� 3 ''. 51 0 OO�,........�� pJ'y � �' £nhnnrinF Ihr�iJur and Pryf f.ionnllv!! �' 4O ' Op 5�� R UES •h'Em IVO J/Nua a4 Acrrae Sysirvu lhwfur `ii oOE TFC• eibiroo- 2251 IVY ST. • P.O.BOX 3313 • CHICO,CA 95927-3313 • PHONE(530)345-5555 • FAX(530)345-3242 1623 BELTLINE RD. • P.O.BOX 994452 • REDDING,CA 96099-4452 • PHONE(530)222-5555 • FAX(530)243-5556 301-C BURNS DR.UNIT 1 • YUBA CITY,CA 95991 • PHONE(530)673-7778 • FAX(530)673-7779 Door System Design,Inc.dba The Door Company CCL #496225