Loading...
HomeMy WebLinkAboutFAI21-0001 CF FA 2021 269 TECHNOLOGY WAY #5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION System Record of Inspection and Testing To be completed by the system inspector or Tester at the time of the inspection or test. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets, data, or calculations as necessary to provide a complete record. Page 1 of 5 Inspection Type: ❑Q1 111Q2 ❑Q3 111Q4 ❑S1 ❑S2 ❑Annual Pass ❑Fail Inspection Test Start Date:1-21-21 Inspection Test Start Time:4:00 Inspection Test End Date:1-22-21 Inspection Test End Time:12:30 Technician:Nicole Beard Helper: Tyler Linarez 1.Property Information Name of Property:North Butte Courthouse (Pride) Address: 1775 Concord Ave. Chico,Ca 95928 Description of Property:A-B-S1 Name of Property Representative:Don Lucy Address: 1775 Concord Ave. Chico,Ca 95928 Phone#: (916)474-9524 Fax#: Email: donald.lucy@prideindustries.com Authority having jurisdiction over property:Chico Fire Dept. Phone#:888-987-5322 Fax#: Email: 2.Testing and Monitoring Information Testing Organization:INTEGRATED FIRE SYSTEMS, INC. Address:269 TECHNOLOGY WAY SUITE 5, ROCKLIN CA 95765 Phone#:888-987-5322 Fax#:530-637-5299 Email: Monitoring Organization: INTEGRATED FIRE SYSTEMS, INC. Account#: IFS3321-F Address:269 TECHNOLOGY WAY SUITE 5, ROCKLIN CA 95765 Phone#:888-987-5322 I Fax#:530-637-5299 Email: Entity to which alarms are retransmitted:Central Station- NMC Phone#:866-952-6840 3.Documentation Onsite location of the required record documents and site-specific software:On-Site W/Maintenance 4.Description of System or Service 4.1 Control Unit Manufacturer:EST Model Number: EST 3 FACP Location: Basement Primary Electrical Room 4.2 Software Firmware Firmware Revision Number:5.20 4.3 System Power 4.3.1 Primary(Main)Power Nominal Voltage: 120 Amps:6 Location:Basement Primary Electrical Room Over-current Protection Type:CB Amps:20 Disconnecting Means Location: PNL ELS#11 2015 National Fire Protection Association 269 TECHNOLOGY WAY #5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA Llcs #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page 2 of 5 Inspection Test Start Date:1-21-21 Inspection Test End Date:1-22-21 Name of Property: North Butte Courthouse(Pride) 4.Description of System or Service(Continued) 4.3.2 Secondary Power Type: Back Up Batteries Location:On Board Battery Type(if applicable):SLA Calculated capacity of batteries to drive the system:12v 26Ah X2 In Standby Mode(hours):24 In Alarm Mode(Minutes):15 5.Notifications Made Prior to Testing Monitoring Organization Contact:TMS Time:4:00 Building Management Contact:Justin/Bill Time:4:00 Building Occupants Contact:Staff Time:4:00 Authority Having Jurisdiction Contact: Time: Other,if required Contact: Time: 6.Testing Results 6.1 Control Unit and Related Equipment Description Visual Functional Comments Inspection Test Control Unit Lamps/LEDs/LCDs Fuses Trouble Signals Disconnect Switches Ground-fault monitoring Supervision Local Annunciator Remote Annunciator Qty(2) Master Control Room, Front Lobby Entry. Remote Power Panels Qty(5) Basement Electrical, 1st FIr Electrical Room, 2nd FIr Electrical Room Other(specify 6.2 Secondary Power Description Visual Functional Coments Inpsection Test Battery Condition Installed 1-25-2021 Duracell Load Voltage L: 13V R: 12.79V Discharge Test L: Pass load testR:Pass load test Charge Test Replaced Remote Panel Batteries Qty(10) In BPS 2015 National Fire Protection Association 269 TECHNOLOGY WAY #5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAx INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page 3 of 5 Inspection Test Start Date:1-21-21 Inspection Test End Date:1-22-21 Name of Property: North Butte Courthouse(Pride) 4.3 Notification Appliance Power Extender Panels NAC Power Supply Name: EST BPS6A NAC Power Supply Number: 1 Location:Basement Electrical Room 4.3.1 Primary Power Input Voltage of Power Extender Panel: 120 Power Extender Panel Amps:3 4.1.4 Batteries Location: On Board Type:Duracell Nominal Voltage: 12 Amp/Hr Rating:8 ❑✓ Batteries are marked with date of manufacture Battery#1 Code/Date:HEF08d Battery#2 Code/Date:HEF08d Battery#1 In-Service Date: 1-22-21 Battery#2 In-Service Date: 1-22-21 Battery Test Notes: New Install Battery#1 Voltage at time of Inspection: 12.64 Battery#2 Voltage at time of Inspection: 12.64 Description Visual Functional Comments Inspection Test Battery#1 Condition New Battery#2 Condition New Load Voltage 12.64v Load Voltage 12.64v Discharge Test 8Ah Discharge Test 8Ah Charger Test Pass Charger Test N/A Other(specify) 4.3 Notification Appliance Power Extender Panels NAC Power Supply Name: EST BPS6A NAC Power Supply Number: 2 Location:1st Fir Electrical 158 4.3.1 Primary Power Input Voltage of Power Extender Panel: 120 Power Extender Panel Amps:3 4.1.4 Batteries Location: On Board Type:Duracell Nominal Voltage: 12 Amp/Hr Rating:8 ❑✓ Batteries are marked with date of manufacture Battery#1 Code/Date:HEF08Ij Battery#2 Code/Date:HEF08t Battery#1 In-Service Date: 1-22-21 Battery#2 In-Service Date: 1-22-21 Battery Test Notes: New Install Battery#1 Voltage at time of Inspection: 12.82 Battery#2 Voltage at time of Inspection: 12.82 Description Visual Functional Comments Inspection Test Battery#1 Condition New Battery#2 Condition New Load Voltage 12.82V Load Voltage 12.82V Discharge Test 8Ah Discharge Test 8Ah Charger Test Pass Charger Test N/A Other(specify) 2015 National Fire Protection Association 269 TECHNOLOGY WAY #5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Extra Booster Page 1 of 2 Inspection Test Start Date:1-21-21 Inspection Test End Date:1-22-21 Name of Property: North Butte Courthouse (Pride) 4.3 Notification Appliance Power Extender Panels NAC Power Supply Name: EST BPS6A NAC Power Supply Number: 3 Location:1st Fir Electrical Room 187 4.3.1 Primary Power Input Voltage of Power Extender Panel: 120 Power Extender Panel Amps:3 4.1.4 Batteries Location: On Board Type:Duracell Nominal Voltage: 12 Amp/Hr Rating:8 ❑✓ Batteries are marked with date of manufacture Battery#1 Code/Date:HEFO8d Battery#2 Code/Date:HEF08J Battery#1 In-Service Date: 1-22-21 Battery#2 In-Service Date: 1-22-21 Battery Test Notes:New Install Battery#1 Voltage at time of Inspection: 12.82 Battery#2 Voltage at time of Inspection: 12.82 Description Visual Functional Comments Inspection Test Battery#1 Condition New Battery#2 Condition New Load Voltage 12.82V Load Voltage 12.82 Discharge Test 8Ah Discharge Test 8Ah Charger Test Pass Charger Test N/A Other(specify) 4.3 Notification Appliance Power Extender Panels NAC Power Supply Name: EST BPS6A NAC Power Supply Number: 4 Location:2nd Fir Electrical Room 271 4.3.1 Primary Power Input Voltage of Power Extender Panel: 120 Power Extender Panel Amps:3 4.1.4 Batteries Location: On Board Type:Duracell Nominal Voltage: 12 Amp/Hr Rating:8 ❑✓ Batteries are marked with date of manufacture Battery#1 Code/Date:HEF08d Battery#2 Code/Date:HEF08d Battery#1 In-Service Date: 1-22-21 Battery#2 In-Service Date: 1-22-21 Battery Test Notes: New Install Battery#1 Voltage at time of Inspection: 12.82 Battery#2 Voltage at time of Inspection: 12.82 Description Visual Functional Comments Inspection Test Battery#1 Condition Good Battery#2 Condition Good Load Voltage 12.82V Load Voltage 12.82V Discharge Test 8Ah Discharge Test 8Ah Charger Test Pass Charger Test N/A Other(specify) 2015 National Fire Protection Association 269 TECHNOLOGY WAY #5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Extra Booster Page 2 of 2 Inspection Test Start Date:1-21-21 Inspection Test End Date:1-22-21 Name of Property: North Butte Courthouse(Pride) 4.3 Notification Appliance Power Extender Panels NAC Power Supply Name: EST BPS6A NAC Power Supply Number: 5 Location:2nd Fir Electrical Room 254 4.3.1 Primary Power Input Voltage of Power Extender Panel: 120 Power Extender Panel Amps:3 4.1.4 Batteries Location: On Board Type:Duracell Nominal Voltage: 12 Amp/Hr Rating:8 ❑✓ Batteries are marked with date of manufacture Battery#1 Code/Date:HEF08J Battery#2 Code/Date:HEF08J Battery#1 In-Service Date: 1-22-21 Battery#2 In-Service Date: 1-22-21 Battery Test Notes: New Install Battery#1 Voltage at time of Inspection: 12.82 Battery#2 Voltage at time of Inspection: 12.82 Description Visual Functional Comments Inspection Test Battery#1 Condition New Battery#2 Condition New Load Voltage 12.82V Load Voltage 12.82V Discharge Test 8Ah Discharge Test 8Ah Charger Test Pass Charger Test N/A Other(specify) 4.3 Notification Appliance Power Extender Panels NAC Power Supply Name: Fire Alarm secondary power NAC Power Supply Number: Location:Basement Electrical Room 4.3.1 Primary Power Input Voltage of Power Extender Panel: 120 Power Extender Panel Amps:3 4.1.4 Batteries Location: On board Type:Duracell Ultra Nominal Voltage:12 Amp/Hr Rating: 100 ❑ Batteries are marked with date of manufacture Battery#1 Code/Date: Battery#2 Code/Date: Battery#1 In-Service Date:1-30-19 Battery#2 In-Service Date: 1-30-19 Battery Test Notes:Tested battery loads with CELLCHECKER: PULSE LOAD BATTERY TESTER Battery#1 Voltage at time of Inspection: 13.34 Battery#2 Voltage at time of Inspection: 13.29 Description Visual Functional Comments Inspection Test Battery#1 Condition Good Battery#2 Condition Good Load Voltage 13.34V Load Voltage 13.29V Discharge Test Pass Discharge Test Pass Charger Test Pass Charger Test N/A Other(specify) 2015 National Fire Protection Association 269 TECHNOLOGY WAY #5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA Llcs #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page 4 of 5 Inspection Test Start Date:1-21-21 Inspection Test End Date:1-22-21 Name of Property: North Butte Courthouse(Pride) 6.3 Alarm and Supervisory Alarm Initiating Device Attach supplementary device test sheets for all initiating devices. 6.4 Notification Appliances Attach supplementary appliance test sheets for all notification appliances. 6.5 Interface Equipment Attach supplementary interface component test sheets for all interface components. Circuit Interface/Signaling Line Circuit Interface/Fire Alarm Control Interface 6.6 Supervisory Station Monitoring Description Visual Functional Comments Inspection Test Alarm Signal Alarm Restoration Trouble Signal Trouble Restoration Supervisory Signal Supervisory ✓ Restoration 6.7 Public Emergency Alarm Reporting System Description Visual Functional Comments Inspection Test Alarm Signal N/A Alarm Restoration N/A Trouble Signal N/A Trouble Restoration N/A Supervisory Signal N/A Supervisory N/A Restoration 7.Notifications That Testing Is Complete Monitoring Organization Contact:TMS Time: 12:30 Building Management Contact:Justin/Bill Time: 12:30 Building Occupants Contact:Staff Time: 12:30 Authority Having Jurisdiction Contact: Time: Other,if required Contact: Time: 2015 National Fire Protection Association 171D 269 TECHNOLOGY WAY #5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA tics #908904 C7. C 10, C 16 MONITORING • TESTING • INSPECTION Page 5 of 5 Name of Property: North Butte Courthouse (Pride) 8.System Restored to Normal Operation Date: 1/22/21 Time: 12:30 9.Defects or Malfunctions Not Corrected at Conclusion of System Inspection,Testing,or Maintenance Item Fix/Fail Note Deficiencies and Comments 1 ,/ Atrium Smoke detectors test prior to inspection By Pride and was verified through Boldnet. 2 ,/ Devices 0044, 0056, 0061 & FIRE OUTPUTS to be tested when FM200 is tested 3 ,/ OS&Y: Right side comes in as SUPERVISORY, Left side comes in as TROUBLE 4 ,/ Basement Waterflows are above tile/lid and there is no ITV. Basement Vestibule 025, Basement Restricted Circulation 047, and Basement By Elev 5. This is originally installation and completion of AHJ with record of completion. Test all accessible waterflow switches mechanically. Note other waterflows setup same way , but accessible to test mechanically. 5 1 All basement devices read differently on panel then Boldnet. Devices currently labeled as it comm 10.Certification This system,as specified herein,has been inspected and tested according to all NFPA standards cited herein. ❑Pass ❑Fail Signature: .0Printed Name:Nicole Beard Date: 1-22-21 Organization:INTEGRATED FIRE SYSTEMS,INC. Title:Technician Phone#:888-987-5322 2015 National Fire Protection Association Ctr—F0 269 TECHNOLOGY WAY #5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA LICS #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Notification Appliance, Initiating Device and Interface Component Supplementary Record of Inspection and Testing This form is a supplement to the System Record of Inspection and Testing. This form is to be completed by the system inspection and testing contractor at the time of the inspection and/or test. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Attach additional sheets, data, or calculations as necessary to provide a complete record. Pagel of 10 Inspection Type: ❑Q1 ❑Q2 ❑Q3 ❑Q4 ❑S1 S2 ❑✓ Annual Inspection Test Start Date: 1-21-21 Inspection Test Start Time:4:00 Inspection Test End Date: 1-22-21 Inspection Test End Time: 12:30 Account#: IFS3321-F 1.Property Information Name of Property:North Butte Courthouse (Pride) Address:1775 Concord Ave. Chico,Ca 95928 2.Notification Appliance and/or Initiating Device Test Results NA= Notification Appliance ID= Initiating Device IC= Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass SMOKE DETECTOR i 1 2ND FL ELEC RM 254 i SMOKE DETECTOR / 2 2ND FL CIRC BY CRTRM 4 SMOKE DETECTOR / 3 2ND FL STAIRWELL S104 SMOKE DETECTOR / 4 2ND FL JURY DELIBERATE 250 RR WEST SMOKE DETECTOR / 5 2ND FL JURY DELIBERATE 250 RR EAST SMOKE DETECTOR / 6 2ND FL JURY DELIBERATE 250 SMOKE DETECTOR / 7 2ND FL VISITING JUDGE 253 SMOKE DETECTOR / 8 2ND FL JUDICAL CHAMBER 255 RR SMOKE DETECTOR / 9 2ND FL JUDICAL CHAMBER 255 SMOKE DETECTOR / 10 2ND FL ELEV 6 LOBBY SMOKE DETECTOR / 11 2ND FL TELECOM 257 SMOKE DETECTOR / 12 2ND FL NORTH CELL 238 BY CRTRM 4 SMOKE DETECTOR / 13 2ND FL ELEV 5 LOBBY SMOKE DETECTOR / 14 2ND FL SOUTH CELL 235 BY CRTRM 4 SMOKE DETECTOR / 15 2ND FL INTRVW 236 EAST BY CRTRM 4 SMOKE DETECTOR / 16 2ND FL INTRVW 237 WEST BY CRTRM 4 SMOKE DETECTOR / 17 2ND FL RESTRICT CIRC BY CRTRM 3 SMOKE DETECTOR / 18 2ND FL JUDICAL CHAMBER 258 RR SMOKE DETECTOR / 19 2ND FL JUDICAL CHAMBER 258 SMOKE DETECTOR / 20 2ND FL JUDICAL 260 RR SMOKE DETECTOR / 21 2ND FL JUDICAL CHAMBER 260 SMOKE DETECTOR / 22 2ND FL CRTRM NORTH SMOKE DETECTOR / 23 2ND FL CRTRM 3 MIDDLE SMOKE DETECTOR / 24 2ND FL CRTRM 3 SOUTH SMOKE DETECTOR / 25 2ND FL SOUND LCK 231 BY CRTRM 3 2015 National Fire Protection Association (IFS 269 TECHNOLOGY WAY#5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAx INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page2 of 10 2.Notification Appliance and/or Initiating Device Test Results(Continued) NA=Notification Appliance ID=Initiating Device IC=Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass SMOKE DETECTOR 1 26 2ND FL CONF 232 BY CRTRM 3 SMOKE DETECTOR 1 27 2ND FL WE CONF 233 BY CRTRM 3 1 SMOKE DETECTOR / 28 2ND FL RESTRICTED CIRC BY CRTRM 3 SMOKE DETECTOR 1 I 129 2ND FL JUDICAL CHAMBER 262 SMOKE DETECTOR 1 I 130 2ND FL JUDICAL 262 RR I SMOKE DETECTOR 1 I 131 2ND FL JUDICAL CHAMBER 264 RR I SMOKE DETECTOR 1 I 132 2ND FL JUDICAL CHAMBER 264 1 SMOKE DETECTOR 1 I 133 2ND FL CRTRM 2 NORTH I SMOKE DETECTOR / 34 2ND FL CRTRM 2 MIDDLE I SMOKE DETECTOR 1 35 2ND FL CRTRM 2 SOUTH I SMOKE DETECTOR / I 136 2ND FL SOUND LCK BU CRTRM 2 1 SMOKE DETECTOR I 1 1 I 137 2ND FL EAST CONF 222 BY CRTROOM 2 1 SMOKE DETECTOR I 1 1 I 138 2ND FL WEST CONF 223 BY CRTROOM 2 1 SMOKE DETECTOR I 1 1 I 139 2ND FL ELEV 4 LOBBY 1 SMOKE DETECTOR I 1 1 I 140 2ND FL NW STAIRWELL S103 I SMOKE DETECTOR V 41 2ND FL WEST TELECOM 269 1 SMOKE DETECTOR / 42 2ND FL NORTH CELL 218 CRTROOM 1 SMOKE DETECTOR / 43 2ND FL ELEV 3 LOBBY I SMOKE DETECTOR / 44 2ND FL SOUTH CELL 217 BY CRTRM 1 1 SMOKE DETECTOR / 45 2ND FL INTRVW CELL EAST BY CRTRM 1 1 SMOKE DETECTOR 1 1 46 2ND FL WEST INTRVW CELL BY CRTRM 1 1 SMOKE DETECTOR 1 ✓ 147 2ND FL NE CRTRM 1 1 SMOKE DETECTOR 1 1 148 2ND FL SE CRTRM 1 SMOKE DETECTOR 1 1 149 2ND FL SW CRTRM 1 I SMOKE DETECTOR 1 150 2ND FL NW CRTRM 1 1 SMOKE DETECTOR / 51 2ND FL JURY DELIBERATION 267 RR I SMOKE DETECTOR / 52 2ND FL JURY DELIBERATION 267 SMOKE DETECTOR 1 53 2ND FL JURY DELIBERATION 268 RR SMOKE DETECTOR 1 54 2ND FL ELECTRICAL ROOM 271 WEST I SMOKE DETECTOR I 55 2ND FL RESTRICTED BY CRTRM 1 1 SMOKE DETECTOR ✓ 56 2ND FL RESTRICTED CIRC RR 272 SMOKE DETECTOR I 1 ✓ I 57 2ND FL LAW LIBRARY 270 1 SMOKE DETECTOR I 1 ✓ I 158 2ND FL RESTRICTED CIRC RR 273 I SMOKE DETECTOR 11 1 I 159 J 2ND FL HALLWAY BY BREAKROOM I SMOKE DETECTOR 1 160 2ND FL WEST RESEARCH 277 V SMOKE DETECTOR / 61 2ND FL EAST RESEARCH 276 —1—/-1 SMOKE DETECTOR / 62 2ND FL WORK AREA 279 SMOKE DETECTOR / 63 2ND FL OPEN OFFICE 274 1 SMOKE DETECTOR 1 64 2ND FL MANAGERS OFFICE 282 I 1 SMOKE DETECTOR / 65 2ND FL CEO OFFICE 281 I I See main System Record of Inspection and Testing for additional information,certifications,and approvals. 2015 National Fire Protection Association (IFS 269 TECHNOLOGY WAY#5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page3 of 10 -11 2.Notification Appliance and/or Initiating Device Test Results(Continued) NA=Notification Appliance ID=Initiating Device IC=Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass SMOKE DETECTOR / 66 2ND FL ADMIN CONFERENCE 280 SMOKE DETECTOR / 67 2ND FL ADMIN 283 SMOKE DETECTOR / 68 2ND FL SETTLEMENT CONF 201 SMOKE DETECTOR / 69 2ND FL JANITOR CLOSET 284 SMOKE DETECTOR / 70 2ND FL RECEPTION 200 SMOKE DETECTOR / 71 2ND FL RESEARCH CENTER 202 ./ SMOKE DETECTOR / 72 2ND FL CHILD WAITING 205 RR SMOKE DETECTOR V 73 2ND FL CHILD WAITING VESTIBULE 203 SMOKE DETECTOR / 74 2ND FL CHILD WAITING 204 SMOKE DETECTOR / 75 2ND FL WEST HALL BY CHILD WAITING SMOKE DETECTOR / 176 2ND FL MENS RESTROOM 207 SMOKE DETECTOR / 177 2ND FL NE CRTRM 4 SMOKE DETECTOR / 78 2ND FL SE CRTRM 4 SMOKE DETECTOR / 79 2ND FL SW CRTRM 4 SMOKE DETECTOR / 80 2ND FL NW CRTRM 4 SMOKE DETECTOR / 181 2ND FL CONFERENCE BY CRTRM 4 SMOKE DETECTOR / 182 2ND FL SOUND LCK 241 BY CRTRM 4 SMOKE DETECTOR / 83 2ND FL WEST CONF 243 BY CRTRM 4 SMOKE DETECTOR / 84 2ND FL PUBLIC CIRC BY CRTRM 3 SMOKE DETECTOR 1 I 85 2ND FL SE STAIRWELL S102 SMOKE DETECTOR / 86 2ND FL PUBLIC CIRC BY CRTRM 3 SMOKE DETECTOR / 187 2ND FL PUBLIC CIRC BY CRTRM 3 SMOKE DETECTOR / 188 2ND FL PUBLIC CIRC BY CRTRM 2 SMOKE DETECTOR / 89 2ND FL PUBLIC BY CRTRM 1 SMOKE DETECTOR / 90 2ND FL EA CONF BY CRTRM 1 SMOKE DETECTOR / 91 2ND FL SOUND LCK 211 BY CRTRM 1 SMOKE DETECTOR / 92 2ND FL WEST CONF 213 BY CRTRM 1 SMOKE DETECTOR 1 I 93 2ND FL PUBLIC CIRC 244 BY SW ENTRY STR SMOKE DETECTOR 1 I 94 2ND FL ELEVATOR 1 &2 LOBBY SMOKE DETECTOR / 95 2ND FL WOMENS 208 1 SMOKE DETECTOR / 96 2ND FL CRTRM 4 MIDDLE EAST SMOKE DETECTOR / 97 2ND FL CRTRM 1 MIDDLE WEST 1 SMOKE DETECTOR / 98 2ND FL CRTRM 4 MIIDDLE EAST 1 SMOKE DETECTOR / 99 2ND FL CRTRM 1 MIDDLE WEST ./ SMOKE DETECTOR / 100 2ND FL STAIR S101 ENTRY SMOKE DETECTOR 1 101 ATRIUM 101 NORTH SMOKE DETECTOR / 102 ATRIUM 101 SOUTH ./ SMOKE DETECTOR 1 103 ATRIUM 101 WEST SMOKE DETECTOR I 1 I 1104 PENTHOUSE ELEVATOR 6 LOBBY 11 SMOKE DETECTOR I 1 I 1105 2ND FL PUBLIC CIRC BY CRTRM 1 11 See main System Record of Inspection and Testing for additional information,certifications,and approvals. 2015 National Fire Protection Association (IFS 269 TECHNOLOGY WAY#5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAx INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page4 of 10 2.Notification Appliance and/or Initiating Device Test Results(Continued) NA=Notification Appliance ID=Initiating Device IC=Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass WATERFLOW V 126 2ND FL RESTRICTED CIRC 245 TAMPER ✓ 1127 2ND FL RESTRICTED CIRC 245 V WATERFLOW i I 1128 2ND FL HOLDING 234 BY CRTRM 3 V TAMPER ✓ I 1129 I2ND FL HOLDING CELL BY CRTRM 3 WATERFLOW / I 1130 2ND FL RESTRICTED CIRC BY CRTRM 1 V TAMPER / I 131 2ND FL RESTRICTED BY CRTRM 1 V WATERFLOW V I 132 2ND FL HOLDING CELL BY CRTRM 1 V TAMPER I I 133 2ND FL HOLDING CELL BY CRTRM 1 PULL STATION V 135 2ND FL BY NE STAIRWELL S104 PULL STATION V 136 2ND FL NW STAIRWELL S103 PULL STATION ✓ I 137 2ND FL SE STAIRWELL S102 V PULL STATION V I 138 2ND FL ENTRY STAIRWELL S101 V DUCT DETECTOR / I 145 PENTHOUSE AHU 4 V DUCT DETECTOR I / I 1146 I PENTHOUSE AHU 3 V DUCT DETECTOR I / I 1147 PENTHOUSE AHU 2 V DUCT DETECTOR I V 1148 PENTHOUSE AHU 1 SMOKE DETECTOR V 1251 1ST FL FLOOR ELECTRICAL ROOM 158 V SMOKE DETECTOR V 252 1ST FL CUSTODIAN CLOSET 157 SMOKE DETECTOR V 253 1ST FL STAFF BREAK ROOM 160 SMOKE DETECTOR V 254 1ST FL NORTH RR BY STAFF AREA 163 SMOKE DETECTOR V I 1255 1ST FL SOUTH RR BY STAFF AREA 1612 V SMOKE DETECTOR V I 256 1ST FL MAIL ROOM 156 V SMOKE DETECTOR V I 257 1ST FL STAFF ENTRY 155 V SMOKE DETECTOR V I 258 1ST FL BOILER ROOM 154 V SMOKE DETECTOR / 259 1ST FL CIRC BY NE STAIRS V SMOKE DETECTOR V 260 1ST FL NORTH INVESTIGATION 141 SMOKE DETECTOR V 261 1ST FL OPEN WORK AREA 150 V SMOKE DETECTOR V 262 1ST FL STORAGE 143 BY OPEN WORK AREA SMOKE DETECTOR / 263 1ST FL ELEVATOR 6 LOBBY V SMOKE DETECTOR V 264 1ST FL TELECOM ROOM 152 V SMOKE DETECTOR ✓ 265 1ST FL STORAGE 151 BY COURT OPERAT V SMOKE DETECTOR 1 ✓ I 1266 1ST FL WELNNES 172 V SMOKE DETECTOR 1 ✓ I 1267 1ST FL SE COURT OPERATIONS 170 V SMOKE DETECTOR 1 / I 268 1ST FL E MIDDLE COURT OPER 170 V SMOKE DETECTOR / 269 1ST FL MANAGERS OFFICE 164 SMOKE DETECTOR V 270 1ST FL ACCOUNTING 165 V SMOKE DETECTOR V 271 1ST FL NE COURT OPERATATIONS 170 SMOKE DETECTOR V 272 1ST FL NORTH MIDDLE COURT OPERA 170 SMOKE DETECTOR V 273 1ST FL NORTH WEST COURT OPERA 170 SMOKE DETECTOR V 274 1ST FL MIDDLE COURT OPERATIONS 170 I 1 See main System Record of Inspection and Testing for additional information,certifications,and approvals. 2015 National Fire Protection Association (IFS 269 TECHNOLOGY WAY#5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAx INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page 5 of 10 2.Notification Appliance and/or Initiating Device Test Results(Continued) NA=Notification Appliance ID=Initiating Device IC=Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass SMOKE DETECTOR V 275 1ST FL WEST MIDDLE COURT OPERAT 170 SMOKE DETECTOR V 276 1ST FL EAST ACTIVE FILES 173 J SMOKE DETECTOR / 277 1ST FL EAST ACTIVE FILES 173 V SMOKE DETECTOR V I 1278 1ST FL SOUTH MIDDLE CT OPERATIONS 1701 V SMOKE DETECTOR V I 1279 1ST FL SOUTH COURT OPERATIONS 170 J SMOKE DETECTOR V I 280 1ST FL ELEVATOR 4 LOBBY V SMOKE DETECTOR V I 281 1ST FL WEST TELECOM ROOM 178 V SMOKE DETECTOR V 282 1ST FL RESTRICTED CIRC 177 BY MENS RR SMOKE DETECTOR V 283 1ST FL MENS RESTROOM 175 SMOKE DETECTOR V 284 1ST FL WOMENS RESTROOM 176 1 SMOKE DETECTOR I V I 285 1ST FL RESTRICTED CIR BY WOMENS RR V SMOKE DETECTOR I V I 286 1ST FL STORAGE 180 BY MULTI PURP RM I V SMOKE DETECTOR I ✓ I 1287 1ST FL MULTI PURPOSE ROOM 181 i SMOKE DETECTOR I ✓ I 1288 1ST FL JURY ASSEMBLY 190 V SMOKE DETECTOR I ✓ I 1289 1ST FL JURY ASSEMBLY EAST RR 193 V SMOKE DETECTOR V 1290 1ST FL VESTIBULE 191 BY JURY ASSEM SMOKE DETECTOR V 1291 1ST FL WEST RR 192 BY JURY ASSEM V SMOKE DETECTOR V 292 1ST FL VENDING 194 SMOKE DETECTOR V 293 1ST FL STAFF 184 SMOKE DETECTOR V 294 1ST FL WEST ELEC RM 187 1 SMOKE DETECTOR I ✓ I 1295 1ST FL CUSTODIAL CLOSET 186 V SMOKE DETECTOR I ✓ I 1296 1ST FL LOBBY 108 BY SECURITY SCREEN I V SMOKE DETECTOR I ✓ I 1297 1ST FL SECURITY SCREENING 103 SMOKE DETECTOR I ✓ I 1298 1ST FL EXIT 102 BY SECURITY SCREEN I V SMOKE DETECTOR / 299 1ST FL LOBBY 188 BY JURY ASSEMBLY I V SMOKE DETECTOR V 300 1ST FL NORTH EAST CRTRM 5 SMOKE DETECTOR V 301 1ST FL EAST MIDDLE CRTRM 5 V SMOKE DETECTOR V 302 1ST FL NORTH CELL 120 1 SMOKE DETECTOR V 303 1ST FL ELEV RM 3 LOBBY HOLDING 117 V SMOKE DETECTOR V 304 1ST FL SOUTH CELL 119 V SMOKE DETECTOR ✓ 305 1ST FL INTERVIEW 118 V SMOKE DETECTOR I 1 ✓ I 1306 1ST FL WEST MIDDLE CRTRM V SMOKE DETECTOR I I ✓ I 1307 1ST FL NORTH WEST CRTRM V SMOKE DETECTOR I I ✓ I 1308 1ST FL SOUTH WEST CRTRM 5 V SMOKE DETECTOR V 1309 1ST FL SOUTH EAST CRTRM 5 SMOKE DETECTOR V 310 1ST FL EXIT 116 BY CRTRM 5 I v l SMOKE DETECTOR V 311 1ST FL DIRECTOR 138 SMOKE DETECTOR V 312 1ST FL MEDIATOR 137 SMOKE DETECTOR V 313 1ST FL SOUT INVESTIGATOR 142 I ✓ I SMOKE DETECTOR / 314 1ST FL MEDIATOR 136 I ✓ I See main System Record of Inspection and Testing for additional information,certifications,and approvals. 2015 National Fire Protection Association (IFS 269 TECHNOLOGY WAY#5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page6 of 10 2.Notification Appliance and/or Initiating Device Test Results(Continued) NA=Notification Appliance ID=Initiating Device IC=Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass SMOKE DETECTOR / 315 1ST FL CIRCULATION 133 SMOKE DETECTOR 1 316 1ST FL MEDIATOR 135 1 SMOKE DETECTOR / 317 1ST FL MEDIATOR 134 SMOKE DETECTOR / I 318 1ST FL PLAY AREA 132 SMOKE DETECTOR / I 319 1ST FL RR 145 BY MEDIATOR I SMOKE DETECTOR / I 320 1ST FL RR 144 BY MEDIATOR ORIENTATION I SMOKE DETECTOR / 321 1ST FL MEDIATION ORENTATON 146 1 SMOKE DETECTOR / 322 1ST FL SELF HELP 130 1 SMOKE DETECTOR 1 323 1ST FL FAMILY LAW FACILITATOR 149 1 SMOKE DETECTOR I / 324 1ST FL SHARP COORDINATOR 148 1 SMOKE DETECTOR / 325 1ST FL ATTORNEY MAIL 124 1 SMOKE DETECTOR / 326 1ST FL CIRC 171 BY ATTORNEY MAIL 1 SMOKE DETECTOR / 327 1ST FL EAST PUBLIC COUNTER 121 1 SMOKE DETECTOR 1 1328 1ST FL WEST PUBLIC COUNTER 121 SMOKE DETECTOR / 1329 1ST FL FAMILY COURT SERVICES 131 SMOKE DETECTOR V 1330 1ST FL PUBLIC CIRC 109 BY SE STAIRS SMOKE DETECTOR 1 1331 1ST FL PUBLIC 109 BY ATTORNEY MAIL SMOKE DETECTOR / 332 1ST FL PUBLIC CIRC 109 BY POR SMOKE DETECTOR / 333 1ST FL PUBLIC CIRC 109 BY PUBLIC COUNT I SMOKE DETECTOR / 334 1ST FL PUBLIC CIRC 109 BY CRTRM 5 SMOKE DETECTOR / 335 1ST FL EAST CONF 112 BY CRTRM 5 I SMOKE DETECTOR / 336 1ST FL SOUND LCK BY CRTRM 5 I SMOKE DETECTOR / 337 1ST FL WEST CONF BY CRTRM 5 I SMOKE DETECTOR / 338 1ST FL MECH RM 114 BY CRTRM 5 1 SMOKE DETECTOR / 339 1ST FL ELEV EQUIP RM 115 1 HEAT DETECTOR / 340 1ST FL ELEV EQUIP RM 115 SMOKE DETECTOR / 341 1ST FL PUBLIC CIRC 109 BY CRTRM 5 SMOKE DETECTOR / 342 1ST FL ELEV 1 &2 LOBBY SMOKE DETECTOR 1 I 343 1ST FL WOMENS RR 107 BY SEC SCREEN I SMOKE DETECTOR 1 I 1344 1ST FL MENS RR 106 BY SEC SCREENING SMOKE DETECTOR 1 I 1345 1ST FL INTERVIEW 104 I (SMOKE DETECTOR 1 I 1346 1ST FL PUBLIC CIRC BY SW ENTRY STAIRS I SMOKE DETECTOR / I 347 1ST FL PUBLIC DOC REVIEW RM 122 1 WATERFLOW / I 376 1ST FL COURT OPERATIONS 170 I 1 TAMPER / I 377 1ST FL COURT OPERATIONS 170 V WATERFLOW / 378 1ST FL RESTRICTED CIRC 177 1 TAMPER / 379 1ST FL RESTRICTED CIRC 177 WATERFLOW / 380 1ST FL HOLDING CELL 117 I TAMPER / 381 1ST FL HOLDING CELL 117 I 1 PULL STATION / 385 1ST FL SE STAIRWELL S102 I I See main System Record of Inspection and Testing for additional information,certifications,and approvals. 2015 National Fire Protection Association (IFS 269 TECHNOLOGY WAY#5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page7 of 10 IN 2.Notification Appliance and/or Initiating Device Test Results(Continued) NA=Notification Appliance ID=Initiating Device IC=Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass PULL STATION 1 387 1ST FL EXIT 102 1 WATERFLOW 1 388 1ST FL FIRE SPRINKLER CLST 147 BSMNT 1 TAMPER 1 389 1ST FL FIRE SPRINKLER CLST 147 BSMNT 1 WATERFLOW 1 390 1ST FL FIRE SPINKLER CLST 147 PENTHSE TAMPER ✓ 391 1ST FL FIRE SPRINKLER CLST 147 PENTHSE 1 WATERFLOW 1 392 1ST FL FIRE SPRINKLER CLST 147 2ND FL I- 1 TAMPER 1 393 1ST FL FRE SPRINKLER CLST 147 2ND FL 1 WATERFLOW 1 394 1ST FL FIRE SPRINKLER CLST 147 1ST FL 1 TAMPER 1 395 1ST FL FIRE SPRINKLER CLST 147 1ST FL 1 PULL STATION 1 397 1ST FL STAFF ENTRY 155 1 PULL STATION 1 398 1ST FL NE STAIRS S104 1 PULL STATION 1 399 1ST FL NW STAIRS S103 1 SMOKE DETECTOR 1 D0001 BSMNT PRIMARY ELEC RM 023 1 SMOKE DETECTOR 1 D0002 BSMNT SAFETY EQUIP WEAPON STRG 024 1 SMOKE DETECTOR 1 D0003 BSMNT MASTER CONTROL RM 028 1 SMOKE DETECTOR 1 D0004 BSMNT MASTER CONTROL RM 028 HALL 1 SMOKE DETECTOR 1 D0005 BSMNT MASTER CONTROL RR 029 1 SMOKE DETECTOR 1 D0006 BSMNT SECURITY OFFICERS STAFF RM 030 1 SMOKE DETECTOR 1 D0007 BSMNT CUSTODY CIRC SOUTH 019 1 SMOKE DETECTOR 1 D0008 BSMNT CUSTODY CIRC NORTH 019 1 SMOKE DETECTOR 1 D0009 BSMNT SEC OFFICER STAFF RR EAST 031 1 SMOKE DETECTOR 1 D0010 BSMNT SEC OFFICER STAFF RR WEST 032 SMOKE DETECTOR 1 D0011 BSMNT ELEC RM EAST 050 1 SMOKE DETECTOR 1 D0012 BSMNT ELEC RM WEST 050 SMOKE DETECTOR 1 D0013 BSMNT ELEV 5&5 MACH RM SW 048 1 SMOKE DETECTOR 1 D0014 BSMNT ELEV 5&6 MACH RM SE 048 1 HEAT DETECTOR 1 D0015 BSMNT ELEV 5&6 MACH RM NE 048 1 HEAT DETECTOR 1 D0016 BSMNT ELEV 5&6 MACH RM NW 048 1 SMOKE DETECTOR 1 D0017 BSMNT ELEV 6 LOBBY 047 1 SMOKE DETECTOR 1 D0018 BSMNT CUSTODIAN CLST 035 1 SMOKE DETECTOR 1 D0019 BSMNT RSTRICTD CIRC 047 BY STAFF RM 1 SMOKE DETECTOR 1 I D0020 BSMNT VESTIBULE 025 BY MPOE 1 SMOKE DETECTOR 1 I D0021 BSMNT MPOE DATA CLST 026 1 SMOKE DETECTOR 1 I D0022 BSMNT CELL 007 1 SMOKE DETECTOR 1 D0023 BSMNT CELL 009 1 SMOKE DETECTOR ,/ D0024 BSMNT NW CELL ENTRY 013 1 SMOKE DETECTOR 1 D0025 BSMNT CELL 010 1 SMOKE DETECTOR 1 D0026 BSMNT NE CELL ENTRY 014 1 SMOKE DETECTOR I 1 I D0027 BSMNT CIRC EA 052 BY SEC VESTIBULE I 1 SMOKE DETECTOR I 11 I D0028 BSMNT SECURE VESTIBULE 018 11 See main System Record of Inspection and Testing for additional information,certifications,and approvals. 2015 National Fire Protection Association (IFS 269 TECHNOLOGY WAY#5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAx INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page8 of 10 2.Notification Appliance and/or Initiating Device Test Results(Continued) NA=Notification Appliance ID=Initiating Device IC=Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass SMOKE DETECTOR V D0030 BSMNT ELEV 5 LOBBY SMOKE DETECTOR ✓ D0029 BSMNT SECURE CIRC 052 V SMOKE DETECTOR / D0031 BSMNT CELL ENTRY 017 SOUTH V SMOKE DETECTOR ,/ I I D0032 I BSMNT CELL 004 V SMOKE DETECTOR L I 1D0033 I BSMNT CELL 005 V SMOKE DETECTOR I I I D0035 I BSMNT CELL 006 V SMOKE DETECTOR V I D0036 I BSMNT CELL 003 V SMOKE DETECTOR V D0037 I BSMNT CELL 002 SMOKE DETECTOR V D0038 BSMNT CELL 001 SMOKE DETECTOR V D0039 BSMNT SECURITY STAFF WEST LCKR 034 1 SMOKE DETECTOR ✓ I D0040 I BSMNT SECURITY STAFF EAST LCKR 033 J SMOKE DETECTOR V I D0041 I BSMNT IT LAB EAST 046 V SMOKE DETECTOR V I I D0042 I BSMNT IT ADMIN 049 SMOKE DETECTOR V I I D0043 I BSMNT IT LAB WEST 046 I SMOKE DETECTOR V I I D0044 I BSMNT SERVER RM SOUTH 044 SMOKE DETECTOR V I D0045 BSMNT STORAGE RM 043 I SMOKE DETECTOR V I D0046 BSMNT RSTRICTD CIRC 047 BY SRVR RM V SMOKE DETECTOR V D0047 BSMNT ELEV 4 LOBBY I SMOKE DETECTOR V D0048 BSMNT ELEV 3&4 MACH RM 045 SMOKE DETECTOR V D0049 BSMNT ELEV 3&4 MACH RM 045 I HEAT DETECTOR ✓ D0050 BSMNT ELEV 3&4 MACH RM 045 V SMOKE DETECTOR ✓ I D0051 BSMNT ELEV 3&4 MACH RM 045 V SMOKE DETECTOR V I D0052 BSMNT RESTRICTED CIRC BY IT LAB V SMOKE DETECTOR ✓ I D0053 BSMNT SPECIAL ENVIRONMENT REC 036 I SMOKE DETECTOR I I I D0054 BSMNT INACTIVE RECORD STORAGE 037 I SMOKE DETECTOR 1 I 100055 BSMNT EXHIBIT STORAGE 038 1 SMOKE DETECTOR V I D0056 BSMNT VAULT 039 SMOKE DETECTOR V I D0057 BSMNT WORKSHOPR MAINT STORAGE 040 I SMOKE DETECTOR V I D0058 BSMNT SECURE VESTIBULE 041 V SMOKE DETECTOR V I D0059 BSMNT ELEV 3 LOBBY V SMOKE DETECTOR V I D0060 I BSMNT SECURE CIRC 052 V SMOKE DETECTOR ✓ I D0061 I BSMNT COMPUTER SERVER 044 SMOKE DETECTOR ✓ I 100062 I BSMNT WORKSHOP MAINT STORAGE N 040 V SMOKE DETECTOR V I 100063 I BSMNT WORKSHOP MAINT STORAGE S 040 V SMOKE DETECTOR V. 100064 BSMNT EXHIBIT STORAGE 038 SMOKE DETECTOR V. D0065 BSMNT CELL 8 v l PULL STATION V D0066 BSMNT IN CUSTODY CIRC 019 I TAMPER V D0270 DBL CHK ASSEMBLY NEAR VECHICLE RAMP PULL STATION ✓ D0068 BSMNT BY STAIR S103 I / I WATERFLOW ✓ D0069 BSMNT VESTIBULE 025 I 1 See main System Record of Inspection and Testing for additional information,certifications,and approvals. 2015 National Fire Protection Association (IFS 269 TECHNOLOGY WAY#5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAX INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page 9 of 10 2.Notification Appliance and/or Initiating Device Test Results(Continued) NA=Notification Appliance ID=Initiating Device IC=Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass TAMPER V 512 BSMNT VESTIBULE 025 WATERFLOW ✓ D0155 BSMNT RESTRICTED CIRC 047 V TAMPER / 514 BSMNT RESTRICTED CIRC 047 V WATERFLOW ✓ 1515 BSMNT BY ELEV 5 V TAMPER V I I D0158 BSMNT BY ELEV 5 V FIRE OUTPUT V I 517 BSMNT VICTAULIC ALARM STRG 043 FIRE OUTPUT V I 520 BSMNT FM200 ALARM COMP SRVR 044 FIRE OUTPUT V 528 BSMNT HEAT TRACE AC FAIL FIRE OUTPUT V 529 BSMNT HEAT TRACE ALARM SUPERVISION FIRE OUTPUT V 518 BSMNT VICTAULIC SUPV STRG 043 FIRE OUTPUT ✓ I 522 BSMNT FM200 TRBLE COMP SRVR 044 I I I I I I I I**,t********NAC'S********** Strobes I I I Qty 62 Throughout Site Floors Basement and Flr's 1-3 Speaker/Strobes I Qty 108 Throughout Site Floors Basement and Flr's 1-3 --- I I I I I I I I -77 I I See main System Record of Inspection and Testing for additional information,certifications,and approvals. 2015 National Fire Protection Association (IFS 269 TECHNOLOGY WAY#5 ROCKLIN, CA 95765 530-637-5322 OFFICE 530-637-5299 FAx INTEGRATED FIRE SYSTEMS, INC. CA Lics #908904 C7. C10, C16 MONITORING • TESTING • INSPECTION Page 10 of 10 2.Notification Appliance and/or Initiating Device Test Results(Continued) NA= Notification Appliance ID=Initiating Device IC=Interface Component Device Type NA ID IC Address/Circuit Location Fail Pass THIS PAGE INTENTIONALLY LEFT BLANK I I I I I I I I I I I I I I I I I I I I See main System Record of Inspection and Testing for additional information,certifications,and approvals. 2015 National Fire Protection Association