LISTING No. 7272-0026:0218 Page 1 of 1
CATEGORY: 7272--SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: Simplex50 Technology Drive,Westminster, MA 01441-0001
Contact: Steven Burgess (978)731-8483 Fax(978)731-8881
Email: steven.burgess@jci.com
DESIGN: Models 4098-9714, -9774, -9714TSP, -9714TTP,-9754-9754TSP, -9754TTP;
GSA4098-9714, and-9754 analog photoelectric type smoke detectors. Models 4098-9754,
-9779, -9754TSP, -9754TTP; GSA4098-9754 analog photoelectric type smoke detectors
employ an integral supplemental heat sensor(135°F fixed temperature and 120°F rate of
rise).This heat sensor is intended for use as a supplemental device to the smoke detector
and is not intended for use in lieu of required heat detectors.
Refer to listee's printed data sheet for additional detailed product description and operational
considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes&ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as photoelectric smoke detectors for use with listee's separately listed compatible fire
alarm control units. Units are intended for use with smoke detector bases Models
4098-9789, -978915P, -9789TTP, -9791, -9791 TSP,-9775, -9776, -9777, -9791TTP, -9792,
-9792TSP, 9792TTP,-9793, 9793TSP, -9793TTP ; GSA4098-9792, and-9793 (CSFM Listing
No. 7300-0026:0217); *4098--9794, -9794TSP,-9794TTP(CSFM Listing No. 7300-0026:0500).
Models 4098-9714, -9714TSP and-9714TTP are listed for use with Models 4098-9750,-9751,
-9752 and-9753 duct detector units(CSFM Listing No. 3240-0026:0220)and Models
4098-9755, -9755TSP and-9755TTP duct detector units(CSFM Listing No. 3240-0026:0241).
Model 4098-9714 with Model 4098-9751 is suitable for installations inside air ducts with air
velocities between 0-2000 fpm. Refer to listee's Installation Instruction Manual for details.
NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering
fires which smolder for hours before bursting into flames. Sources of these fires may include
cigarettes burning in couches or bedding. The ionization type detectors are generally more
effective at detecting fast,flaming fires that consume combustible materials rapidly and
spread quickly. Sources of these fires may include paper burning in a waste container or a
grease fire in the kitchen.
*Rev 02-01-18 gt
j;%-rc, This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
O an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021