HomeMy WebLinkAbout4009-9602 DATASHEET ( AUTOCALL TrueAlert Addressable Notification UL, ULC Approved and CSFM 4009 IDNAC Repeater; Power and Distance Extender Listed* Features — - — 4009 IDNAC Repeaters provide enhanced power delivery to IF TrueAlert/TrueAlert ES addressable notification appliances FIRE controlled by IDNAC SLCs: • Output voltage in alarm is maintained by an efficient switching — regulator at 29 VDC during both AC input and battery backup conditions allowing strobes to operate at lower current • With lower current strobes and regulated output voltage,wiring Extended distance can be extended 2 to 3 times that of conventional notification, distance and appliance loading can be increased,or smaller wire gauge can be used, current all resulting in installation savings with high assurance that appliances FIRE that operate during normal system testing will operate during worst case alarm conditions Repeated IDNAC SLC 4009 IDNAC Repeaters receive an IDNAC SIC input and provide a repeated 3 A SLC output to extend SLC distance and power: •Appliance control and address limit remains with the host IDNAC control panel.Repeater status is communicated to the control panel 4009 IDNAC for system diagnostics and also locally indicated -_ - Repeater • Repeater output extends supervisory capacity by up to 139 additional unit loads or 3 A • Input SLC connection can be Class B or Class A — •— • Repeater output can be a Class A loop or a Class B output with internal Simplex Fire Alarm connections for up to four(4)T-tapped output branches(Class A F°RE Control Panel with output requires A009-9814 Class A Adapter) IDNAC SLC(4100ES • Operation requires one IDNAC SLC address;Repeaters can be shown for reference) connected as one in series,or up to five(5)in parallel •AC power input is 120 VAC or 220-240 VAC,50/60 Hz,auto-select FIRE •An on-board battery charger is provided with low AC battery disconnect selectable per Repeater(required for ULC listed ( } applications) FORE • Operation is compatible with TrueAlert ES and TrueAlert addressable notification appliances and accessories IDNAC SLC •Available with platinum or red cabinet • Listed to UL 864 and ULC 5527 Multiple wiring options are available: • Wiring options include Class B multiple branch(up to 4)output,Class A loop extension,and Class A riser to Class B branches or a Class A loop Figure 1: 4009 IDNAC Repeater Extends output Distance and Current of IDNAC SLC • When the Repeater is part of a Class A loop from the IDNAC SLC source Class A Adapter A009-9814: panel,up to twice the distance for the loop is available;(Class A loop repeating requires A009 9814 Class A Adapter) • Required when extending a Class A loop or to provide a Class A local loop SLC output • Operation provides short circuit isolation between input and output terminals for improved IDNAC SLC survivability Built-in battery Charger • Power supply charges up to 12.7 Ah batteries for in cabinet mounting and up to 25 Ah batteries with model A009-9801 external battery cabinet Available auxiliary output: • A 200 mA,29 VDC constant auxiliary output is available;operation is maintained during battery backup *This product has been approved by the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code.See CSFM Listings 7300-2269 0553 and 7300-2269:0558 for allowable values and/or conditions concerning material presented in this document.Additional listings may be applicable;contact your local product supplier for the latest status. AC4009-0004 Rev. 6 01/2020 I�NAUTOCALL 4009 IDNAC Repeater; Power and Distance Extender Introduction Repeating IDNAC SLCs Autocall fire alarm control panels with IDNAC SLC outputs provide individual address and control of TrueAlert and TrueAlert ES addressable notification appliances.When an IDNAC SLC reaches the current limit or the distance limit of the source IDNAC SLC,use of 4009 IDNAC Repeaters extends the IDNAC SLC with an additional 3 A of SLC current and up to 139 unit loads of additional supervisory capacity. With IDNAC SLCs,a constant 29 VDC source voltage is maintained in alarm,even during battery standby,allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification,or support for more appliances per IDNAC SLC,or use of smaller gauge wiring,or combinations of these benefits,all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions. Description Three wiring configurations Three wiring configurations are available to provide a variety of system solutions:Class B branch extension,Class A loop extension,and Class A riser to Class B branch extension or Class A loop output. Class B branch input wiring Class B branch input wiring allows T-tapped connections to up to five(5)parallel connected 4009 IDNAC Repeaters.Each Repeater has on-board output terminal connections for up to four(4)output branch circuits,and additional branch circuits can be externally T-tapped as required.(Refer to Wiring Reference,Class B Input with Class B Branch Circuit Outputs for additional details.) Class A loop extensions use a single 4009 IDNAC Repeater to extend the current and distance of a single Class A loop allowing the loop distance to be doubled. The Repeater communicates and repeats bi-directionally allowing Class A loop operation to be maintained in the event of an open circuit.This wiring connection requires use of the A009-9814 Class A adapter.(Refer to Wiring Reference,Class A Loop Extension for additional details.) Class A Riser to Class B Branches or Class A Loops For applications requiring a combination of wiring types,a Class A riser can drive up to five(5)4009 IDNAC Repeaters with each Repeater capable of driving either single or multiple Class B branch output(s)or a Class A loop output.In this wiring application,the Repeater does not repeat in the Class A riser loop,it is connected as an appliance with Class A in/out wiring.To create a Class A loop output,the Repeater must be equipped with a A009-9814 Class A Adapter.(Refer to Wiring Reference,Class A Riser Input with Class A Loop and Class B Branch Outputs for additional details.) Product Selection Table 1:IDNAC Repeater Selection (Model Cabinet Color (Description A009-9601(BA) 1Platinum 14009 IDNAC Repeater with cabinet;provides a single 3 A IDNAC SLC output,200 mA auxiliary power output, A009-9602(BA) (Red land battery charger;120/240 VAC,50/60 Hz input,auto-select Table 2:Aftermarket Accessories(installed on-site,select per system requirements) Model Description A009-9814 Class A Adapter Module,mounts on repeater controller board;required for Class A output A2975-9813 Platinum semi-flush box trim 11 7/16"(37 mm)wide,four corners and trim pieces for top,bottom, A2975-9812 Red semi-flush box trim land sides;(will need to be cut to fit 4009 IDNAC Repeater cabinet) Table 3:External Accessories(select per system requirements) Model Description Comments A4905-9929 Remote TrueAlert Communications Isolator Refer to data sheet AC4905-0001 for details A009-9801 External Battery Cabinet for 25 Ah batteries 161/4"W x 13'/2"H x 5 3/4"D(413 mm x 343 mm x 146 mm);refer to data sheet AC2081-0006 for details Table 4:Battery Selection(select battery size per system requirements;two batteries are required for 24 VDC operation) Model Description 2081-9272 6.2 Ah Battery,12 VDC 2081-9274 10 Ah Battery,12 VDC 2081-9275 18 Ah Battery,12 VDC Requires A009-9801 External Battery Cabinet Page 2 AC4009-0004 Rev.6 01/2020 I�NAUTOCALL 4009 IDNAC Repeater; Power and Distance Extender Wiring Reference, Class B Input with Class B Branch Circuit Outputs 4009 IDNAC Repeaters Class B Branch Extensions (5 maximum) IDNAC SLC input • IDNAC SLC output H L= S—L 1. ff ORS PORE FFOTE€ `4 OW J, FOWW. FORE `FOWIE� Milialliiiiiliiiiiiibliiiiiiiii Class B IDNAC SLC Class B IDNAC SLC I Class B wiring can ODnE PE RE FI R Mri..,,..,i .._ . .i.._ iialii be"T-tapped" a Simplex Fire Alarm Control I Panel with IDNAC SLC Class B IDNAC SLC (4100ES shown for reference) . J _ _ _ Wiring Notes: — IFOWg WORE MAO 1. Up to five(5)4009 IDNAC Repeaters can be I wired in parallel as shown on this diagram. > Class B IDNAC SLC 2. IDNAC SLC communications can be repeated only once between the source and the - addressable appliance. I 3.The 4009 IDNAC Repeater extends distance and current of the input IDNAC SLC; it — 11-7 -1 requires one address and consumes four(4) h -FORE FoWE MN unit loads. Class B IDNAC SLC + + - - _ _ _WERE,� HIRE u rei U L'W la .__F 0 Bk..- .___FLEAK__, FRRE = -5 = Each 4009 IDNAC Repeater has duplicate output =— �'L ) terminals rated for two wires each, allowing up to 123_ _ _one pow_ four(4)Class B branch circuit T-taps to be made in the cabinet; additional T-taps may be made in external wiring junction cabinets or boxes —S Int ��,— J— _ Sorg- PDWE a Class B IDNAC SLC Branch Circuits Figure 2: Wiring Reference Page 3 AC4009-0004 Rev.6 01/2020 ( AUTOCALL 4009 IDNAC Repeater; Power and Distance Extender Wiring Reference, Class A Loop Extension Class A IDNAC SLC Loop with 4009 IDNAC Repeater Extending Loop Range and Power 4009 IDNAC Repeater Requires optional 4009-9814 Class A Adapter Module set for Loop mode - - -- <- Class A loop secondary direction - — - - 4� — 8 1 ® ® ® ® 1 is I — Class A loop primary direction I a , ti _ _ ® ® ® ©— — — — Class A loop secondary direction O 'I Simplex Fire Alarm Control Panel with IDNAC SLC;requires optional Dual Class A IDNAC Isolator(DCAI),refer to individual panel documentation for details(4100ES with EPS shown for reference) Notes: 1.Only one 4009 IDNAC Repeater can be wired in a Class A loop.(IDNAC SLC communications can be repeated only once between the source and the addressable appliance.) 2.The 4009 IDNAC Repeater extends distance and current of the Class A IDNAC SLC loop;it requires one address and consumes four(4)unit loads. 3. Under normal operating conditions(no open circuit wiring),appliances 1 through 4 are powered by the Panel Power Supply and appliances 5 through 9 are powered from the 4009 IDNAC Repeater. 4. Under open circuit conditions,an open circuit in the panel side of the primary path will result in the Panel Power Supply powering appliances 5 through 9 and the 4009 IDNAC Repeater will receive IDNAC SLC input from the return path and then power appliances 1 through 4,or as many as remain connected. Figure 3: Wiring Reference Page 4 AC4009-0004 Rev. 6 01/2020 •AUTOCALL 4009 IDNAC Repeater; Power and Distance Extender Wiring Reference, Class A Riser Input with Class A Loop and Class B Branch Outputs Simplex Fire Alarm Control Panel with IDNAC SLC; Requires optional 4009-9814 Class A Adapter requires optional Dual Class A IDNAC Isolator(DCAI), Module set for Branch Mode to create a local refer to individual panel documentation for details Class A loop circuit output (4100ES with EPS shown for reference) Class A Loop Extension IDNAC SLC input (mil' (T Q — C J Pin pine ROBE �RIW i S k,,piEx 4DD51Dw.<REREn*ER ® Class A Loop 1 Q p=igaq____ ®— C 4009 IDNAC Repeaters ff�— °�"� ff'ff — —� --_i,�� I Class B Branch Extension FORE `IWE simpiEx aaos lorvnc PE, eina -__FIRE R9pE IDNAC SLC shown as a Class A Riser with each IDNAC Repeater wired in/out(not T-tapped); IN only two(2)are shown,maximum is five(5) OUT Wiring detail reference(repeaters + are wired same as appliances) Figure 4: Wiring Reference 4009 IDNAC Repeater Mounting and Module Placement Reference Cabinet depth 16-1/4"(413 mm; - F-4-1/8"(105 mm)' 1 10-29/32"(277 mm; I Door,5/8" I (16 mm)thick [ a __ IIIIIIIIIIII IIIIII,, I I a 0 Knockoutsi (343 mm) n 0 E.0 O Exposed cabinet Optional dimension for—e 1 Class A Adapter Module semi-flush mount .-4) (° 1"(25.4 mm, for screw 1�/8"(35 mm)with or nail mounting holes it io SE M Iiririv ��^"0 a ) TT q^q^q^q^pRp� �' pl semi-flush trim 'z .._Battery location(dotted line)no conduit entry) Al s or wiring in this area,12.7 Ah maximum ll^ O _ r Optional Semi-Flush Trim Kit--.6. Shaded Area is Non-power limited 1-3/16"wide(30 mm), 3/8"(9.5 mm)thick Wall surface reference for semi-flush mount- Figure 5: Placement Reference Page 5 AC4009-0004 Rev.6 01/2020 •AUTOCALL 4009 IDNAC Repeater; Power and Distance Extender 4009 IDNAC Repeater Specifications Table 5:Input Ratings Specification Rating Voltage Range 120 VAC,50/60 Hz,or 220/230/240 VAC,50/60 Hz,+10%,-15%,auto-select 120 VAC Current 12.5 A 220/230/240 VAC Current 11.25 A IDNAC Input Ratings 117 VDC minimum 11 address,4 unit loads Table 6:24 VDC Requirements for Battery Calculations Specification Panel IDNAC Appliances Auxiliary Load Standby Currents 70 mA 0.8 mA each Output current(voltage is from battery) Alarm Currents 96 mA 4.5 A maximum with 3 A IDNAC SLC load and 200 mA Auxiliary 1.37 x output current(voltage output load(actual alarm current depends on connected and converter is on when in Alarm) activated appliances and devices) Table 7:Output Ratings Specification Rating IDNAC SLC Output 3 A maximum @ 29 VDC for Special Application appliances Compatible Special Application Autocall TrueAlert ES and TrueAlert addressable notification appliances;contact your Autocall product Appliances representative for compatible appliances IDNAC Repeater Loading and SLC Each repeater uses four unit loads on the IDNAC channel it receives power from and supports up to 139 Address Usage additional unit loads.Most appliances are 1 unit load;Multi-Tone appliances are 2 unit loads;Repeaters and Isolators are 4 unit loads.Refer to individual appliance and device specifications for unit load requirements and rated SLC loading specifications. Each repeater uses one IDNAC SLC device address-the IDNAC Repeater does not increase the IDNAC channel device address capacity.Refer to the Host IDNAC SLC specifications for the device address capacity specifications on the IDNAC channel. Auxiliary Output Current 1200 mA maximum Voltage 129 VDC nominal with AC present or when Repeater is on battery standby and in Alarm 124 VDC nominal when on battery standby and not in Alarm Table 8:IDNAC SLC Wiring Specifications(refer to installation instructions for more information) Specification Rating Recommended wire type UTP,unshielded twisted pair Maximum wire length allowed with"T-Taps"for class B wiring 110,000 ft(3048 m) Maximum wire length to any appliance 14000 ft(1219 m) Wiring Connections 1Terminal blocks for 18 to 12 AWG Table 9:Repeater Status Indicators Specification Rating Green AC Power LED On with AC present,off during brownout or no AC condition Red Communications LED(COMM) (Blinks when Repeater is communicating with the host control panel Yellow System Status LEDs 4 LEDs provide up to 16 different trouble status indications;an on-board trouble scroll button allows review should multiple troubles occur Table 10:A009-9814 Class A Adapter Module Option(required for Class A loop extension or for Class A output) Specifications Rating IDNAC SLC Output Voltage 3 A maximum @ 29 VDC for Special Applications appliances Two connections,Port A and Port B,function varies by application(loop extension or local loop),Port A and Port B are isolated from each other Status LEDs Two yellow trouble LED indicators,one for each port Table 11:Environmental and Technical Publications Reference Specification Rating Operating Temperature 32°F to 120°F(0°C to 49°C) Operating Humidity Range 1Up to 93%RH at 90°F(32°C) Installation Instructions 14009 IDNAC Repeater I579-1019AC (Class A Adapter Module I579-1080AC ©2020 johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable,contact your local Autocall product supplier for the latest status.Listings and approvals under Tyco Fire&Security GmbH,and the product names listed in this material are marks and/or registered marks.Unauthorized use is strictly prohibited.NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association(NFPA). AC4009-0004 Rev.6 01/2020