HomeMy WebLinkAboutFAI15-0052 Overhead Door Testing 2020 1300 Sumner Avenue, Cleveland, OH 44115-2851 Fax: (216)241-0105 Phone: (216)241-7333 DASMA Door&Access5ystems E-Mail:dasma@dasma.com Manufacturers Association International URL:www.dasma.com DASMA ROLLING STEEL FIRE DOOR DROP TEST FORM General NFPA 80 and Model Codes require the inspection and testing of fire doors to demonstrate proper operation, full closure, and proper reset. Perform the visual inspection before the operational check, or before the drop tests of the fire door, in order to reduce the risk of failure during the drop tests. Use the form below to record the Visual, Operational, and Drop Test results. Check Pass or Fail in the boxes. See the Guidelines for additional information. A WARN I NG Door could close rapidly and could result in death or serious injury. Perform drop test and reset per manufacturer's instructions. The drop tests, reset, repairs and/or maintenance should be performed by a trained door system technician with complete knowledge of this type of fire door and the manufacturer's instructions. Repair parts m .- a stained from the original door manufacturer. After repairs are completed, the door must be tested to assure/proper door .•eration and automatic closing capability. The fire door must be in the fully open position before the droptest. Re et the (oor following the drop test and test �J again.aiA A . G� / D� /�/ Ill Project:( . . ' 7) *\P c, oe Company: f Phone: Address: E-mail: IlWr Door Opening Size Door Mfr. Door Mfr. Visual Operational Drop Drop Location Serial No. Inspection Check Test#1 Test#2 Width Height Pass Fail Pass Fail Pass Fail Pass Fail Door 1 . I(n'a'' 9 'Zu OVerh eoa ✓ AV" 3a�� 1./ ,/ �/ 1700 X71[�� CI ���� o1/er�ead 1 N uL v/ / V. Dobe' '5 ''i lo q % Ouerheed DoerA 1L13a5 ul_ V V V ✓ Comments: ‘ Q Ck\real C 61 \ e 0 r-sa 0 Y1 ()(9 r- 3 Y�c C) cd\I \ Co 'f-. ck ©Y\ ID ,.-- - \ . P1 CV �5 N ed \,Y,;45 " mt)+5r- �- (5W) F ort --\ -rI . e(Lovnmer cXcy,t� 5 -o. , bush r- 0.1\ �-��� d t--' Tested By: Cnri--J 1f-Vra 134- bon n "" Witnessed By: t.m �A.,,...Sa��G‘. Company: —The �J©0`r' C oyyLvic'') Representing: $VAC—f� N•.-1 Wm. c t t-.DIST. Address: ''. .Q " 1 T''y 6)-. CJi co, C A Title: C CTRc\ lAt-4 Signature/Date: I4 � 0 O,- Qt7 `fir / Signature/Date:6 ../Ilk O .68) IO -12 Op- Rev.6/07 VD SMA Rolling Steel Fire Door Annual Drop Test Form - RDD-271© White—Building Owner Yellow—Service Company Page 1 Printed 10/26/20 Work Order 123464 WO No: 123464 Assigned To: ELEC Project: Type: PMI Planned Date: 08/31/20 Status: S Planned By: PM SCHEDULER PM#: 1306 Priority: Submitted By: PM SCHEDULER Safety Doc#: None Date Due: 08/31/20 Submitted Date: 09/30/20 Standard Doc#: None Building: 004 (Student&Administrative Services) Issue To: 3080475 (Hansbrough, Mike) Equipment Equipment Description Location OHDO1SAS Overhead Fire Doors#1,SAS SAS168 Welcome Center OHDO2SAS Overhead Fire Door#2,SAS SAS160 Financial Aid OHDO3SAS Overhead Fire Door#3,SAS SAS179 Admissions and Records Problem Description Door#1 cycled-no issues. Door#2 no reaction to switch up or down. Door#3 cycled-no issues. Material and Labor Requirements Equipment Part Number Description Quantity Equipment Trade Function People Hrs • Notes Completed By: Completion Date: II DASMA 1300 Sumner Avenue, Cleveland, OH 44115-2851 Fax: (216)241-0105 Phone: (216) 241-7333 Door&AccessSystems E-Mail:dasma@dasma.com Manufacturers Association International URL:www.dasma.com DASMA ROLLING STEEL FIRE DOOR DROP TEST FORM General NFPA 80 and Model Codes require the inspection and testing of fire doors to demonstrate proper operation, full closure, and proper reset. Perform the visual inspection before the operational check, or before the drop tests of the fire door, in order to reduce the risk of failure during the drop tests. Use the form below to record the Visual, Operational, and Drop Test results. Check Pass or Fail in the boxes. See the Guidelines for additional information. AWARNING Door could close rapidly and could result in death or serious injury. Perform drop test and reset per manufacturer's instructions. The drop tests, reset, repairs and/or maintenance should be performed by a trained door system technician with complete knowledge of this type of fire door and the manufacturer's instructions. Repair parts must be obtained from the original door manufacturer. After repairs are completed, the door must be tested to assure proper door operation and automatic closing capability. The fire door must be in the fully open position before the drop test. Reset $- •s G following the drop test and test again. Project: /3 t.- i f CCD 1/C., —e.,- V'1 . Company: I✓ Phone: /14/0.1„,/ 5'76— 3 7 3-Th Address: lair E-mail: Door Opening Size Door Mfr. Door Mfr. Visual Operational Drop Drop Inspection Check Test#1 Test#2 Location Serial No. Width Height Lie.,dor Pass Fail Pass Fail Pass Fail Pass Fail ,or43 i 3 V1 q '4" W voCOV4 ✓ / ✓ -/ DOs r -q'10., 1 Q. WI r► dSo(w °°°°85 I ✓ ./ N/ Voor0\a y�A, 1y,� , �;Y-18 )('413ro V - ..N1 ✓ Onncilo\a 4 \N ‘0 W► rd Sot WI coo 35 V -I -1 Comments: AI\ -\-r., dm,r VI a ie S1;d-e 1 o c.-.-S .-1/4-):+N-, 004- e n4-eri oc,45 e,yCa6,e,'r" 91a c.ek on `7oQc3, 3 L 01 P O )1 Tested By: C r; \r1-k- S-ITA n WOO Witnessed By: KALF $4�%,,N Company: .©cy L(0. Representing: B3 yrk -(,t ,.\,\ pm.GJl., 0\SI, Address: a p? S 1 V7 , C k c o l LA Title: G1�-(, \C\Ar Signature/Date: 1 " Ii' 1 0 / ( )cOSignature/Date: ►UI-Ev2(,.uE0 yolk, wook Rev.6/07 DASMA Rolling Steel Fire Door Annual Drop Test Form - RDD-271© White—Building Owner Yellow—Service Company Page 1 Printed 10/26/20 Work Order 123463 WO No: 123463 Assigned To: ELEC Project: Type: PMI Planned Date: 08/31/20 Status: S Planned By: PM SCHEDULER PM#: 1305 Priority: 4 Submitted By: PM SCHEDULER Safety Doc#: None Date Due: 09/30/20 Submitted Date: 09/30/20 Standard Doc#: None Building: 032 (Arts) Issue To: 3080475 (Hansbrough,Mike) Equipment Equipment Description Location OHDO1ARTS Overhead Fire Door#1,Arts Arts 166 Scene Shop,West Wall OHDO2ARTS Overhead Fire Door#2,ARTS Arts 166 Scene Shop, North Wall OHDO3ARTS Overhead Fire Door#3,Arts Arts SW Hall,Adjacent to 160/184 OHDO4ARTS Overhead Fire Door#4,Arts Arts North Main Entrance,Above Doorway Leading to Theatre/Gallery Problem Description Test Fire doors and roll down fire doors. *****Door#1 has dead batteries.-Tony changing today. Door#2 cycled-no issues. Door#3 would only travel down 2'at a time. upward travel-no issues. Door#4 cycled-no issues. Material and Labor Requirements Equipment Part Number Description Quantity Equipment Trade Function People Hrs Notes Completed By: Completion Date: DASMA 1300 Sumner Avenue, Cleveland, OH 44115-2851 Fax: (216)241-0105 Phone: (216)241-7333 Door&Access Systems E-Mail:dasma@dasma.com Ma nufacturers Associ a ti o n International URL:www.dasma.com DASMA ROLLING STEEL FIRE DOOR DROP TEST FORM General NFPA 80 and Model Codes require the inspection and testing of fire doors to demonstrate proper operation, full closure, and proper reset. Perform the visual inspection before the operational check, or before the drop tests of the fire door, in order to reduce the risk of failure during the drop tests. Use the form below to record the Visual, Operational, and Drop Test results. Check Pass or Fail in the boxes. See the Guidelines for additional information. AWARNING Door could close rapidly and could result in death or serious injury. Perform drop test and reset per manufacturer's instructions. The drop tests, reset, repairs and/or maintenance should be performed by a trained door system technician with complete knowledge of this type of fire door and the manufacturer's instructions. Repair parts must be obtained from the original door manufacturer. After repairs are completed, the door must be tested to assure proper door operation and automatic closing capability. The fire door must be in the fully open position before the drop test. Reset the door following the drop test and test again. !� Project: L . R . C LJvA4e CIA\e Company: Phone: Address: s•-_(---1-J1‘' ---) E-mail: Door Opening Size Door Mfr. Door Mfr. Visual Operational Drop Drop Inspection Check Test#1 Test#2 Location Serial No. Width Height Pass/ Fail Pass Fail Pass Fail Pass Fail lour. 1 0'74 10 COr I ya J ! UL 1/ / 17 .1 - of Cl 10'7 N 10 ' Co,rw�l.1 ' 00 �6-77 1/ ✓ ✓ -V citoCo; G 10 COrne.tl C{Go( lc, 1./ / V , I/ Comments: k I � lb O t3- I I Os-e, Co,-►.r�,Cr__----i o- 0 v-i CO►til . E A-1 ar w, . , • . Orocpe)C. 'b y ?dam \TOSS Tested By: CA fl 5 X le,( rt-t-t)(---A-iv, Witnessed By: ttik kv _, 1-\A.aszczO VCS� Company: ^^(�� ►"� DO(, CO1'Yt,p3.r1 V Representing:'�V�z.-cite t,� Arm ( . L T. l.... QIS Address: o',D i-V 6 ' A ' Title: G�c=i-z C‘A►-1 Signature/Date: _;1,..4,- 11_ 1 O/aGi0� Signature/Date: ►pIZ_sof z57 c Rev.6/07 y - A oiling Steel ire Door Annual DropTest Form - RDD-271© White—BuildingOwner Yellow—Service Company Page 1 Printed 10/26/20 Work Order 123465 WO No: 123465 Assigned To: ELEC Project: Type: PMI Planned Date: 08/31/20 Status: S Planned By: PM SCHEDULER PM#: 1307 Priority: Submitted By: PM SCHEDULER Safety Doc#: None Date Due: 08/31/20 Submitted Date: 09/30/20 Standard Doc#: None Building: 025 (Learning Resource Center) Issue To: 3080475 (Hansbrough, Mike) Equipment Equipment Description Location OHDO1 LRC Overhead Fire Door#1, LRC LRC 1st Floor Hall OHDO2LRC Overhead Fire Door#2, LRC LRC 2nd Floor Hall OHDO3LRC Overhead Fire Door#3, LRC LRC 3rd Floor Hall Problem Description Door#1 low end of limit switch requires adjustment.switch requires hold to travel down. Door#2 switch wired in reverse.cycled-no issues.*****Repaired Door#3 Low end of limit switch requires adjustment.switch requires hold to travel down. Material and Labor Requirements Equipment Part Number Description Quantity Equipment Trade Function People Hrs Notes Completed By: Completion Date: