ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection: ;;uu13wab152 Date: 5/14/20
Site: Honcut School Customer: Palermo Schools
Street: 68 School Street Contact: Carlos Aguilar
City/State: Oroville, CA Phone#: 530-864-8619
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep Carlos Aguilar 530-864-8619
B. Fire Department Oroville Cal Fire 538-6841
C. Central Station N/A
D. Central Station Acct#
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? I X
On Test Time: 2:00 Return to Service Time: 3:00
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H.8 Date Batteries Installed: Note 1
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? 1
Condition of Batteries: Note#
Battery Voltage with AC Power: Note 1 Battery Voltage without AC Power: Note 1
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: Firelite Model# MS-4012 System Type: Hardware
Location of Annunciators:
Location of Primary Power Source:Outside Port 1 Panel# 1 Breaker 13
Comments: Note#
Note#
FCPS: Manufacturer: Model# Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
FCPS: Manufacturer: Model# Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
FCPS: Manufacturer: Model# Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
Owner/Rep: / Phone#: Date:
Inspector: Mat Machado Phone#: 530-362-2609 Date:5/14/20
Owners Rep Sign: Date:5/14/20 Inspector Sign:
ALARM AND DETECTION REPORT Page 2 of 3
Property Site: Honcut School
Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators
5. Zones
6. Manual Stations (Pull) 4 4 X
Hardwire
Addressable
7. Detectors
Photoelectric
Ionization
Heats/Fixed or R of R
Flame
Duct(See#15)
8. Horn/Strobe 5 5 X
Strobe Only
Bell
Speakers
Horn 1 1 X
9.
x
10. Automatic Door Release X
11. Water Flow switches X
Did W/F Ring Outside Bell? X
Did W/F Activate Alarm Panel? X
12. Tamper Switches X
13. PIV X
OS &Y X
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X
17. Is system reset for normal conditions? X
18. Is system restored to operational service? X
19. Have Proper Authorities (see#1)been notified system is back in service? X
List Proper Authorities:Butte sheriff department
20. Indicate %of equipment tested this report 25% 50% 75% VJI00%
21. Indicate %of equipment tested YTD 25% 50% 75% 100%
Comments for any"no"answers or explanations (Note#):
5/14/20C/' >
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Honcut School Page 3 of 3
Zone or DEVICE
DEVICE SLC #
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PS Rm 1 S. Exit X 1 1
PS Rm 1 N. Exit X 1 2
PS Rm 2 X 2 1
PS Rm 3 X 2 2
LEGEND
PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual
ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch
PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch
IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder
DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve
SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual Ply—Post Indicator Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - - -
NOTE # COMMENT
1 Batteries at FACP are out of date
Discrepancies Found? Ill Yes I I No
See Discrepancy Report? I I I Yes I I No
5/14/20
C)S
Owners Rep Sign: Date: Inspector Sign: