HomeMy WebLinkAboutB19-1768 CF PC C; Butte County Fire Department
FIRE 116 Cay Fire Prevention Bureau
176 Nelson Avenue Oroville, CA 95965Utte County
RESCUE Office (530)538-7888
C •
www.buttecounty.net/fire ""F°R",A
NON RESIDENTIAL PLAN REVIEW LETTER
July 5,2019
ECC CONSTRUCTORS LLC
1240 BAYSHORE HIGHWAY STE 301
BURLINGAME, CA 94010
APN: 040-520-100
Building Permit Number: B19-1768 Plan Check#1
Description: WAREHOUSE(5000)W/ELEC FOR BASECAMP
Occupancy Classification: S-2/U
Fire Sprinklers: No
Building Total Area: S-2 @ 5000 sf/U @ 0 sf
Dear Applicant,
The plans you recently submitted have been reviewed by the Fire Department referencing
the 2016 edition of the California Fire Code (CFC). The numbered comments listed below in the
body of this letter must be addressed prior to Fire Department Final Inspection of your project.
1. Complete and return the attached Statement of Intended Use.
2. Access: An approved fire apparatus access road not less than 20 feet wide shall be
provided for access within 150 feet of all portions of the building.
3. Address and Building Identification: Ensure building and suites have appropriate
building identification. Identification shall be placed in a position that is plainly
visible from the street or road fronting property. Minimum 4" high and 0.5"
stroke. Post address at the street main entrance and on the main or first building
encountered. Ensure that other buildings on site are identified with same standard
as address. Buildings can be numbered, lettered or named,but must be same label
as staff on site uses.
4. Extinguishers: Extinguishers shall be 2A1OBC. One extinguisher is required for
every 3000 square feet and must be within 75' from any point. Extinguishers shall
be mounted in a conspicuous place, easily accessible and readily available, and
shall be along normal paths of travel. Extinguishers shall be mounted so that the
top of the extinguisher is no higher than 5' above finished floor. Where
extinguishers may be subject to physical damage they shall be adequately
protected.
The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. If you wish
to discuss these plan check comments, please call during our business hours or contact us by e-
mail at the address below. Permit status can be tracked by logging on to
http://www.buttecounty.net/dds and clicking Building Permits Status.
Chris Boyd John Gaddie
Deputy Fire Marshal Fire Protection Planning
530.538.6320 530.538.6320
Chris.boyd@fire.ca.gov john.gaddie@fire.ca.gov