HomeMy WebLinkAboutB19-1647 CF PC Pavia Hulling C; Butte County Fire Department
FIRE 116 Cay Fire Prevention Bureau
AJ` et,
176 Nelson Avenue Oroville, CA 95965Utte County
RESCUE Office (530)538-7888
C •
www.buttecounty.net/fire ""F°R",A
NON RESIDENTIAL PLAN REVIEW LETTER
June 17,2019
NORTH VALLEY BUILDING SYSTEMS INC
30 SEVILLE COURT
CHICO, CA 95928
APN: 047-150-070
Building Permit Number: B19-1647 Plan Check#1
Description: EQUIPMENT REPAIR SHOP(6000)LOFT(165)
Occupancy Classification: S-1/U
Fire Sprinklers: No
Building Total Area: @ 0 sf/U @ 0 sf
Dear Applicant,
The plans you recently submitted have been reviewed by the Fire Department referencing
the 2016 edition of the California Fire Code (CFC). The numbered comments listed below in the
body of this letter must be addressed prior to Fire Department Approval of your project.
1. Please complete and return the attached Statement of Intended Use. Include type
and amount of any combustible, flammable or hazardous materials.
2. Provide submittals for overhead fire door.
3. Openings in the three hour fire wall are limited to 156 square feet maximum per
CBC Section 706.8. The proposed roll up door exceeds this. If you require a door
larger than 156 square feet, change the fire wall to a fire barrier.
4. Provide a minimum of(3) 4A8OBC rated fire extinguisher mounted in an
accessible conspicuous area. Travel distance to a fire extinguisher shall not
exceed 50 feet from any point.
5. Address and Building Identification: Ensure building and suites have appropriate
building identification. Identification shall be placed in a position that is plainly
visible from the street or road fronting property. Minimum 4" high and 0.5"
stroke. Post address at the street main entrance and on the main or first building
encountered. Ensure that other buildings on site are identified with same standard
as address. Buildings can be numbered, lettered or named,but must be same label
as staff on site uses.
6. Notify Butte County Fire Department(530) 538-6320 if any hazardous
operations,processes or storage will be conducted in any unit. A special permit
from the Fire Department may be required.
The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. If you wish
to discuss these plan check comments,please call during our business hours or contact us by e-
mail at the address below. Permit status can be tracked by logging on to
http://www.buttecounty.net/dds and clicking Building Permits Status.
Chris Boyd John Gaddie
Deputy Fire Marshal Fire Protection Planning
530.538.6320 530.538.6320
Chris.boyd@fire.ca.gov john.gaddie@fire.ca.gov