HomeMy WebLinkAboutB19-0776 CF PC May 31, 2019 BCM CONSTRUCTION COMPANY INC 2990 HIGHWAY 32 STE 100 CHICO, CA 95973 APN: 029-240-043 Building Permit Number: B19-0776 Plan Check #1 Description: T.I. ADD/DEMO SOME WALLS ADA UPGRADES Occupancy Classification: / U Fire Sprinklers: No Building Total Area: @ 0 sf / U @ 0 sf Dear Applicant, The plans you recently submitted have been reviewed and approved by the Fire Department referencing the 2016 edition of the California Fire Code (CFC). The numbered comments listed below in the body of this letter must be addressed prior to Fire Department Final Inspection of your project. Provide illuminated exit signs for the new exits with a backup power source that will allow the continuation of the illumination for 90 minutes in case of power failure. Extinguishers shall be 2A10BC. One extinguisher is required for every 3000 square feet with a travel distance of less than 75'. Extinguishers shall be mounted in a conspicuous place, easily accessible and readily available, and shall be along normal paths of travel. Extinguishers shall be mounted so that the top of the extinguisher is no higher than 5' above finished floor. Where extinguishers may be subject to physical damage they shall be adequately protected. The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. If you wish to discuss these plan check comments, please call during our business hours or contact us by e-mail at the address below. Permit status can be tracked by logging on to http://www.buttecounty.net/dds and clicking Building Permits Status. Chris Boyd John Gaddie Deputy Fire Marshal Fire Protection Planning 530.538.6320 530.538.6320 Chris.boyd@fire.ca.gov john.gaddie@fire.ca.gov