HomeMy WebLinkAboutB19-0428 CF PCMarch 5, 2019
BETTER BUILDERS CONSTRUCTION INC
5263 ROYAL OAKS DRIVE
OROVILLE, CA 95966
APN: 028-240-063
Building Permit Number: B19-0428 Plan Check #1
Description: SHOP/STORAGE (1984) FOR WINERY
Occupancy Classification: S-2
Dear Applicant,
The plans you recently submitted have been reviewed by the Fire Department referencing the 2016 edition of the California Fire Code (CFC). The numbered comments listed below in the body
of this letter must be addressed prior to Fire Department Approval of your project.
This parcel is located within the State Responsibility Area (SRA) and a Moderate Fire Hazard Severity Zone. Maintain 100' of Defensible Space around all structures in accordance with
Public Resource Code 4291.
Provide a turnaround within 50' of building that complies with the Fire Safe Regulations. (1273.10(c) and 1273.05)
Provide a turnout near the midpoint of the driveway that complies with the Fire Safe Regulations. (1273.10 and 1273.06.)
Fire Extinguishers shall be 2A10B:C. Provide one Fire Extinguisher for every 3000 square feet with a travel distance of less than 75' from any point. Extinguishers shall be mounted in
a conspicuous place, easily accessible and readily available, and shall be along normal paths of travel. Extinguishers shall be mounted so that the top of the extinguisher is no higher
than 5' above finished floor. Where extinguishers may be subject to physical damage they shall be adequately protected.
Address and Building Identification: Ensure building and suites have appropriate building identification. Identification shall be placed in a position that is plainly
visible from the street or road fronting property. Minimum 4" high and 0.5" stroke. Post address at the street main entrance and on the main or first building encountered. Ensure that
other buildings on site are identified with same standard as address. Buildings can be numbered, lettered or named, but must be same label as staff on site uses.
All flammable vegetation and fuels caused by site development and construction, road and driveway construction and/or fuel modification must be removed, chipped, buried or burned prior
to completion of building permit.
The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. If you wish to discuss these plan check comments, please call during our business hours or contact
us by e-mail at the address below. Permit status can be tracked by logging on to http://www.buttecounty.net/dds and clicking Building Permits Status.
Chris Boyd John Gaddie
Deputy Fire Marshal Fire Protection Planning
530.538.6320 530.538.6320
Chris.boyd@fire.ca.gov john.gaddie@fire.ca.gov