HomeMy WebLinkAboutB18-1780 CF PC
August 8, 2018
FOOTHILL FIRE PROTECTION INC
4000 ALVIS CT
ROCKLIN, CA 95677
APN: 047-040-003
Building Permit Number: B18-1780 Plan Check #1
Description: F/S NRES FOR B17-2907
Occupancy Classification: F-1
Fire Sprinklers: Yes
Building Total Area: 34,920 SF
Dear Applicant,
The plans you recently submitted have been reviewed by the Fire Department referencing the 2016 edition of the California Fire Code (CFC). The numbered comments listed below in the body
of this letter must be addressed prior to Fire Department Final Inspection of your project. Please contact us when you are ready for hydrostatic and acceptance testing.
1. Automatic Sprinkler System valves controlling water supply require supervision and monitoring. Submit Fire Alarm plans on a separate permit.
2. Sheet FP1, Hydraulic Calculations Placard, Remote Area 1, Change “Hose Stream Required” from 100 GPM to 250 GPM.
The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. If you wish to discuss these plan check comments, please call during our business hours or e-mail
us at the address below. Permit status can be tracked by logging on to http://www.buttecounty.net/dds and clicking Building Permits Status.
Chris Boyd John Gaddie
Deputy Fire Marshal Fire Protection Planning
530.538.6320 530.538.6320
Chris.boyd@fire.ca.gov john.gaddie@fire.ca.gov