Loading...
HomeMy WebLinkAboutB18-1780 CF PC August 8, 2018 FOOTHILL FIRE PROTECTION INC 4000 ALVIS CT ROCKLIN, CA 95677 APN: 047-040-003 Building Permit Number: B18-1780 Plan Check #1 Description: F/S NRES FOR B17-2907 Occupancy Classification: F-1 Fire Sprinklers: Yes Building Total Area: 34,920 SF Dear Applicant, The plans you recently submitted have been reviewed by the Fire Department referencing the 2016 edition of the California Fire Code (CFC). The numbered comments listed below in the body of this letter must be addressed prior to Fire Department Final Inspection of your project. Please contact us when you are ready for hydrostatic and acceptance testing. 1. Automatic Sprinkler System valves controlling water supply require supervision and monitoring. Submit Fire Alarm plans on a separate permit. 2. Sheet FP1, Hydraulic Calculations Placard, Remote Area 1, Change “Hose Stream Required” from 100 GPM to 250 GPM. The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. If you wish to discuss these plan check comments, please call during our business hours or e-mail us at the address below. Permit status can be tracked by logging on to http://www.buttecounty.net/dds and clicking Building Permits Status. Chris Boyd John Gaddie Deputy Fire Marshal Fire Protection Planning 530.538.6320 530.538.6320 Chris.boyd@fire.ca.gov john.gaddie@fire.ca.gov