HomeMy WebLinkAboutB18-0150 CF PC
May 30, 2018
SEAN EARLEY
PO BOX 147
RICHVALE, CA 95974
APN: 029-100-068
Building Permit Number: B18-0150 Plan Check
Description: T.I TO EXISTING BLDG OFFICE(3000)STOR(3000)
Occupancy Classification: B / U
Building Total Area: B @ 3000 sf / U @ 3000 sf
Dear Applicant,
The plans you recently submitted have been reviewed by the Fire Department referencing the 2016 edition of the California Fire Code (CFC). Please complete and return the Statement of
Intended Use form that provided to you at permit intake so we can determine if there may be additional requirements. The numbered comments listed below in the body of this letter must
be addressed prior to Fire Department Final Inspection of your project.
Access: Prior to building construction, provide an all-weather access of at least 10 feet wide for residential, and 20 feet wide for commercial, and 15 feet vertical clearance that will
allow for ingress and egress and accommodate a 40,000-pound fire apparatus to within 150 feet of all structures.
Storage: Storage shall be maintained 2 feet or more below the ceiling in non-sprinkled areas of buildings or a minimum of 18 inches below sprinkler deflectors in sprinkled areas of building.
The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. If you wish to discuss these plan check comments, please call during our business hours or e-mail
us at the address below. Permit status can be tracked by logging on to http://www.buttecounty.net/dds and clicking Building Permits Status.
Chris Boyd John Gaddie
Deputy Fire Marshal Fire Protection Planning
530.538.6320 530.538.6320
Chris.boyd@fire.ca.gov john.gaddie@fire.ca.gov