March 12, 2018
ANNELLE REED
P O BOX 3193
CHICO, CA 95927
APN: 047-300-126
Building Permit Number: B18-0421
Description: ADDN LUMBER STORAGE (3191)
Occupancy Classification: S-1 / U
Building Total Area: S-1 @ 3191 sf / U @ 0 sf
Dear Applicant,
The plans you recently submitted have been reviewed by the Fire Department referencing the 2016 edition of the California Fire Code (CFC). The numbered comments listed below in the body
of this letter must be addressed prior to Fire Department Final Inspection of your project.
1. Ensure that building is identified with same standard address. Buildings can be numbered, lettered, or named, but must be same label as staff on site uses. Minimum 4" height with
1/2" stroke.
2. Fire extinguishers are required. (Ordinary/Moderate Hazard.) Provide one 2A:20B-C Extinguisher for every 3000 sqft. Travel distance to any extinguisher shall not exceed 75'. Extinguishers
shall be mounted no higher than 5 feet from finished floor, be located along normal paths of travel and readily available and easily accessible.
3. No high pile storage (over 12' high) shall be permitted.
The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. If you wish to discuss these plan check comments, please call during our business hours or contact
us by e-mail at the address below. Permit status can be tracked by logging on to http://www.buttecounty.net/dds and clicking Building Permits Status. Please contact us when you are
ready for a final inspection.