March 12, 2018
MICHAEL FELKINS
PO BOX 242
RICHVALE, CA 95974
APN: 029-100-064
Building Permit Number: B18-0397 Plan Check #1
Description: AG STORAGE/SHOP /W PLUMB, NO ELEC(2400)
Occupancy Classification: U / U
Building Total Area: U @ 2400 sf / U @ 0 sf
Dear Applicant,
The plans you recently submitted have been reviewed by the Fire Department referencing the 2016 edition of the California Fire Code (CFC). The numbered comments listed below in the body
of this letter must be addressed prior to Fire Department Final Inspection of your project.
1. Address and Building Identification: Ensure structure has appropriate building identification, minimum 4" high and 0.5" stroke. Ensure the street address is posted at the street main
entrance and on the main or first building encountered. All other buildings on site are identified with same standard as address. Buildings can be numbered, lettered or named, but must
be same label as staff on site uses.
3. Fire Extinguishers: Extinguishers must be mounted on a bracket or in a cabinet with the top not more than five feet above the floor. Extinguishers may be required to have a sign mounted
above in order to be visible from a distance. Ordinary Hazard occupancy: Provide a minimum of (2) 2A20BC rated fire extinguisher mounted in an accessible conspicuous area. One extinguisher
is required for every 1500 square feet and the travel distance to a fire extinguisher shall not exceed 75 feet from any point.
The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. Please contact us when you are ready for a final inspection. Permit status can be tracked by logging
on to ttp://www.buttecounty.net/dds and clicking Building Permits Status.
Chris Boyd John Gaddie
Deputy Fire Marshal Fire Protection Planning