HomeMy WebLinkAboutB18-0298 CALFIRE UNDERGROUND LPG INSPECTIONProperty Owned:
Inspector:
Underground LPG Tank Inspection Form
California Department of Forestry and Fire Protection
Butte County Fire Department
176 Nelson Avenue, Oroville, CA 95965 ■ (530) 538-7888
o erty Location: r j 3 / 3 ,) La.�
Inspection Date: z? -9j `g Permit #:4j it --04;/
APN: 069— 06/5 --ter),,
ASME Tank Information: NFPA 58: 2001 edition
❑ Approved underground tank installed with no vehicle traffic shall be at least 6 inches below grade. NFPA 58: 3.2.9.1(a).
❑ Aroved interchangeable aboveground/underground installation, maximum depth. 12 inches below grade NFPA 58:3.2.9.1(d)
Approved non -interchangeable underground installation shall have a minimum depth of 18 inches or provide adequate vehicle
protection for all appurtenances. NFPA 58:3.2.9.1(b)
Location of Tank: NFPA 58: 2001 edition
❑ YES 0 NO Tanks of 125 -gallon water capacity and under at least 10 feet from all buildings and property lines. NFPA 58:
3.2.2.2
g YES 0 NO Capacity from 125 - 2000 gallons is at least 10 feet away from all buildings and property lines?
NFPA Table 58:3.2.2.2
Capacity from 2001 gallons and larger shall be 50 ft from buildings / property lines.
NFPA Table 58:3.2.2.2
S ❑ NO All sources of ignition at least 10 feet away from tank appurtenances. NFPA 58: appendix figure I: 1(c)
tallation: NFPA 58: 2001 edition
S ❑ NO
S ❑ NO
YES 0 NO
:❑YES 0 NO
Underground tank installed upon a level surface. NFPA 58: 3.2.9.1. (i).
Adequate vehicle protection of tank appurtenances. NFPA 58 :3.2.9.1(b), (c) & NFPA 58:A-5.4.2.2.
Minimum 14 AWG corrosion resistant tracer wire (entrenched) being visible at riser or building.
NFPA 58: 3.2.16.9.
Tanks shall be coated to protect against corrosion. NFPA 58 3.2.9.2(h), NFPA 58: 3.2.4, NFPA 58:A-
3.2.9.3(c)(d).
Pre re Relief Devices: NFPA 58: 2001 edition
YES ❑ NO
Un jOrgtound
I_WYES ❑ NO
❑YES 0 N
Underground
❑YES 0 N
Adequate protection provided to prevent water or debris from entering the relief valve or discharge
piping. NFPA 58:3.2.11.4.
tanks with less than 2000 gal. Capacity:
If relief device discharges into manhole or protective shroud, the manhole shall be equipped with
ventilated louvers or passive system to provide ventilation. NFPA 58: 3.2.11.6 (See exceptions for
dispensing stations)
If discharge piping has been installed has the relief valve capacity been verified as
adequately meeting its discharge capacity. NFPA 58:3.2.11.8, 2.3.2.4. (a).
tanks with more than 2000 gal. Capacity:
Discharge from pressure relief is piped vertically and directly upward to a point at least 7 feet above the ground
level. NFPA 58:3.2.11.7 (See exceptions for dispensing stations)
Corrosion (Cathodic) Protection: NFPA 58: 3-2.24. 58: A 3.2.9.3(d), 58: A 3.2.2.4
Speci Type of Backfill Material:Sc-A.ntQ Backfill Material: e'Dry 0 Damp
YES 0 NO Additional coating materials applied to surface areas disturbed during installation or shipment of tank
1 0 NO After installation of anode and prior to backfilling the anode bag(s) was pre-soaked with water.
LYES 0 NO Installation site, anode bag, and backfill naturally wet due to weather or other conditions:
'YES 0 NO Anode bag lead wire accessible inside dome for testing.
Comments:
0 Wet
OK to Enter in Trakit pe"Date: i` -g !
Underground LPG Tank Inspection Form — Master 6/2/07
Initials: