HomeMy WebLinkAboutB17-1283 CALFIRE UNDERGROUND LPG TANKUnderground LPG Tank Inspection Form
California Department of Forestry and Fire Protection
Butte County Fire Department
76 Nelson Avenue, Oroville, CA 95965 ■530) 538-7888
Property Location: / 3 i ,..kA.Cilpt.u. , ity:
Inspection Date: 1 -i -1 15 Permit #: 4611-49E.3 APN:
Property Owner
Inspector: ry
Qy'Qv\
ASME Tank Information: NFPA 58: 2001 edition
❑ Approved underground tank installed with no vehicle traffic shall be at least 6 inches below grade. NFPA 58: 3.2.9.1(a).
❑ Approved interchangeable aboveground/underground installation, maximum depth. 12 inches below grade NFPA 58:3.2.9.1(d)
❑ Approved non -interchangeable underground installation shall have a minimum depth of 18 inches or provide adequate vehicle
protection for all appurtenances. NFPA 58:3.2.9.1(b)
7L cation of Tank: NFPA 58: 2001 edition
YYES ❑ NO
["YES ❑ NO
F YES 0 NO
Tanks of 125 -gallon water capacity and under at least 10 feet from all buildings and property lines. NFPA 58:
3.2.2.2
Capacity from 125 - 2000 gallons is at least 10 feet away from all buildings and property lines?
NFPA Table 58:3.2.2.2
Capacity from 2001 gallons and larger shall be 50 ft from buildings / property lines.
NFPA Table 58:3.2.2.2
All sources of ignition at least 10 feet away from tank appurtenances. NFPA 58: appendix figure I: 1(c)
Tan Installation: NFPA 58: 2001 edition
S ❑ NO
AS tNO
0 N
S NO
Underground tank installed upon a level surface. NFPA 58: 3.2.9.1. (i).
Adequate vehicle protection of tank appurtenances. NFPA 58 :3.2.9.1(b), (c) & NFPA 58:A-5.4.2.2.
Minimum 14 AWG corrosion resistant tracer wire (entrenched) being visible at riser or building.
NFPA 58: 3.2.16.9.
Tanks shall be coated to protect against corrosion. NFPA 58 3.2.9.2(h), NFPA 58: 3.2.4, NFPA 58:A-
3.2.9.3(c)(d).
Pre%ure Relief Devices: NFPA 58: 2001 edition
S ❑ NO
Uiserground
YES ❑ NO
❑YES 0 N
Underground
❑ YES ❑ NO
Adequate protection provided to prevent water or debris from entering the relief valve or discharge
piping. NFPA 58:3.2.11.4.
tanks with less than 2000 gal. Capacity:
If relief device discharges into manhole or protective shroud, the manhole shall be equipped with
ventilated louvers or passive system to provide ventilation. NFPA 58: 3.2.11.6 (See exceptions for
dispensing stations)
If discharge piping has been installed has the relief valve capacity been verified as
adequately meeting its discharge capacity. NFPA 58:3.2.11.8, 2.3.2.4. (a).
tanks with more than 2000 gal. Capacity:
Discharge from pressure relief is piped vertically and directly upward to a point at least 7 feet above the ground
level. NFPA 58:3.2.11.7 (See exceptions for dispensing stations)
Corrosion (Cathodic) Protection: NFPA 588: A 3.2.9.3(d), 58: A 3.2.2.4
Specify Type of Backfill Material: .5' Backfill Material: 0 Dry ['Damp
OYES 0 NO Additional coating materials applied to surface areas disturbed during installation or shipment of tank
5v ES 0 NO After installation of anode and prior to backfilling the anode bag(s) was pre-soaked with water.
D'YES 0 NO Installation site, anode bag, and backfill naturally wet due to weather or other conditions:
/YES 0 NO Anode bag lead wire accessible inside dome for testing.
Comments:
0 Wet
OK to Enter in Trakit p� Date: / -r Initials:
Underground LPG Tank Inspection Form — Master 6/2/07