Loading...
HomeMy WebLinkAboutFAI21-0014 CF FA Inspection 2021 ALARM AND DETECTION REPORT Page 1 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 VOLTAGE' SPECIALIsTs 530-624-4514 C101C16 License#880862 www.VoltageSpecialists.com Inspection # ALARM & DETECTION EQUIPMENT TEST REPORT Type of Inspection: Annual i.e.Quarterly,Annual Date: 10/14/21 Site Name: Las Plumas High School Customer Name: Oroville Union High School District Street: 2380 Plumas Drive Contact: Jim LaGrone City&State: Oroville, CA Phone: 530-682-0444 1. Before Test Notify Proper Authorities: Name Phone # A. Owner or Owner's Rep Jim LaGrone 530-682-0444 B. Fire Department OROVILLE POLICE DEPARTMENT 530-538-2444 C. Central Station Central Station Monitoring 1-800-722-0364 D. Central Station Acct# #40-3750 2. Control Panel Status YES NO NOTE# A. Is the system monitored by Central Station? On Test Time: 3:30 Return to Service Time: 9:30 ❑✓ 0 0 B. Is the Power Light on? I ✓ I I I I C. Does the Panel indicate Normal conditions? n D. Are all indicating Lamp Bulbs in Operator order? E. Does the Trouble Light operate? _ F. Does the Silence Switch Operate? I ✓1 I I G. Battery A.H. 8 Date Batteries Installed: 01/24/18 I ✓ I U U H. Does the Panel have non operational zones? f I ✓ I. Does the Panel have Battery Backup? J. Do the batteries indicate they are Properly Charged? Condition of Batteries: Good Battery Voltage with AC Power: 27.36 Battery Voltage without AC Power: 27.24 K. List any trouble conditions on panel before test: Comments: 3. FACP Manufacturer: SILENT KNIGHT Model#: 5820 Type of System: ADDRESSABLE Location of Annunciators: Location of Primary Power Source: Panel#: Brk# Comments: SEE PAGE 1A FOR ADDITIONAL PANEL INFORMATION Owner/Rep: Phone#: Date: Printed Name Inspector: Mat Machado Phone#: 530-362-2609 Date: 10/14/21 C)SOwners Rep Sign: Date: 10/14/21 Inspector Sign: Panel Report Page 1A to Fire Alarm Report VOLTAGE SPECIALISTS 530-624-4514 #880862 VObTAGE\SPEcIAusTs 530-624.459 4 C10/C16 License#880862 www.VoltageSpeciaiists.com Type of Inspection: Annual i.e.Quarterly,Annual Date: 10/14/21 Property Name: Las Plumas High School Customer Name: Street: 2380 Plumas Drive Contact: Jim LaGrone City & State: Oroville, CA Phone: 530-682-0444 FCPS: FCPS #1 Manufacturer: Silent Knight Model#: 5495 Panel/Breaker#: Port/5 Location: inside the FACP Battery Voltage with A/C Power: 27.43 without A/C Power 27.39 Date: 1/24/18 FCPS: FCPS #2 Manufacturer: Silent Knight Model#: 5495 Panel/Breaker#: Port/5 Location: Room 629 Battery Voltage with A/C Power: 27.30 without A/C Power 27.22 Date: 12/09/19 FCPS: FCPS #3 Manufacturer: Silent Knight Model#: 5895 Panel/Breaker#: LB/33 Location: Old Gym Battery Voltage with A/C Power: 27.06 without A/C Power 26.99 Date: 1/24/18 FCPS: FCPS #4 Manufacturer: Silent Knight Model#: 5495 Panel/Breaker#: Location: ABOVE FACP Battery Voltage with A/C Power: 27.27 without A/C Power 27.20 Date: 1/24/18 FCPS: FCPS #5 Manufacturer: Silent Knight Model#: 5495 Panel/Breaker#: Location: ABOVE FACP Battery Voltage with A/C Power: 27.37 without A/C Power 27.34 Date: 12/9/20 FCPS: FCPS #6 Manufacturer: Silent Knight Model#: 5495 Panel/Breaker#: Location: ABOVE FACP Battery Voltage with A/C Power: 27.36 without A/C Power 27.32 Date: 12/9/20 FCPS: FCPS#7 Manufacturer: Silent Knight Model#: 5495 Panel/Breaker#: Location: ABOVE FACP Battery Voltage with A/C Power: 27.37 without A/C Power 27.30 Date: 12/9/20 FCPS: FCPS #8 Manufacturer: Silent Knight Model#: 5895 Panel/Breaker#: L19/5 Location: NEW GYM ELECTRICAL Battery Voltage with A/C Power: 26.98 without A/C Power 26.89 Date: 1/24/18 FCPS: FCPS #9 Manufacturer: Silent Knight Model#:5495 Panel/Breaker#:614/10 Location: Music Wing Electrical Battery Voltage with A/C Power: 27.30 without A/C Power27.27 Date:7/15/19 4S . Owners Rep Sin: Date: 10/14/21 Inspector 9 pSign: ALARM AND DETECTION REPORT Page2 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumes High School Operational #Tested This Equipment Total# Report Yes N/A Note# 4. Remote Annunciators 1 1 X 5. Zones 6. Manual Stations(Pull) Hardware Addressable 47 47 X 7. Detectors Photoelectric 175 175 X Ionization Heats/Fixed or R of R 172 172 X Flame Duct(See#15) 7 7 X 8. Horn/Strobe 83 83 X Strobe Only 61 61 X Bell Speakers Horn 21 21 X Beam Detectors 11 11 X 9. 10. Automatic Door Release 5 5 X 11. Water Flow switches X Did W/F Ring Outside Bell? X Did W/F Activate Alarm Panel? X 12. Tamper Switches X 13. PIV X OS&Y X 14. 15. Did test of Duct Detectors shut down air handling units? I X 16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line)receive signal? I X I 17. Is system reset for normal conditions? I X I 18. Is system restored to operational service? I X I 19. Have Proper Authorities (see#1) been notified system is back in service? I X I List Proper Authorities: Central Station 20. Indicate%of equipment tested this report 25 50 75 X 100 21. Indicate%of equipment tested YTD 25 50 75 X 100 Comments for any"no"answers or explanations (Note#): C/'S Owners Rep Sign: Date: 10/14/21 Ins ector Si9n: p ALARM AND DETECTION REPORT Page 3 of_17 _ VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE zone or DEVICE SLC # TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL HT Bldg 100 Girls RR X 3 1 HT Bldg 100 Girls RR X 3 2 HT Bldg 100 Janitors Rm X 3 21 HT Bldg 100 Boys RR X 3 23 HT Bldg 100 Boys RR X 3 24 HT Bldg 500 RR X 3 59 HT Bldg 500 Storage X 3 60 HT Bldg 500 Storage X 3 61 HT Bldg 500 Janitors X 3 62 HT Gym Girls RR X 3 105 HT Gym Girls RR X 3 106 HT Gym Girls RR X 3 107 HT Gym Janitors Rm X 3 108 HT Gym Storage Rm X 3 113 HT Gym Storage Rm X 3 114 HT Gym Boys RR X 3 115 HT Gym Boys RR X 3 116 HT Gym Boys RR X 3 117 HT Gym Storage Rm X 3 118 HT Bldg 900 OS Girls Rm X 3 42 HT Bldg 900 Girls RR X 3 44 HT Bldg 900 Girls Equipment X 3 45 HT Bldg 900 Girls Janitors X 3 49 HT Bldg 900 Girls Locker Rm X 3 53 HT Bldg 900 Girls Locker Rm X 3 57 HT Bldg 900 Girls Locker Rm X 3 58 HT Bldg 900 Girls Storage X 3 62 HT Bldg 900 Girls Storage X 3 63 HT Bldg 900 Girls Locker Rm X 3 64 HT Bldg 900 Girls Locker Rm X 3 65 HT Bldg 900 Girls Locker Rm X 3 66 HT Bldg 900 Girls Locker Rm X 3 68 HT Bldg 900 Girls Locker Rm X 3 71 4S Owners Rep Sign: Date: 10/14/21 Inspector Sign: p J ALARM AND DETECTION REPORT Page 4 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas Hiah School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# HT Locker Rm X 5 34 HT Girls Locker Rm X 5 74 HT Girls Locker Rm X 5 55 HT Girls Locker Rm X 5 67 HT 400 Server Closet X 5 11 HT Girls Locker RR X 5 43 HT Bldg 900 Girls Locker Rm X 5 72 HT Bldg 900 Girls Locker Rm X 5 73 HT Bldg 900 Girls Locker Rm Shower X 5 75 HT Bldg 800 Boys Locker Rm AC X 5 79 HT Bldg 800 Boys Locker Rm AC X 5 79 HT Bldg 800 Boys Locker Rm AC X 5 79 HT Bldg 800 Boys RR X 5 80 HT Bldg 800 Boys Hall X 5 81 HT Bldg 800 Boys Hall X 5 86 HT Bldg 800 Boys Coaches RR X 5 87 HT Bldg 800 Boys Locker Rm X 5 89 HT Bldg 800 Boys Locker Rm X 5 90 HT Bldg 800 Boys Locker Rm X 5 91 HT Bldg 800 Boys Locker Rm X 5 94 HT Bldg 800 Boys Locker Rm X 5 95 HT Bldg 800 Boys Locker Rm X 5 96 HT Bldg 800 Boys Hall X 5 101 HT Bldg 800 Boys Locker Rm Shower X 5 102 HT Bldg 800 Boys Locker Rm Shower X 5 102 HT Bldg 800 Boys Locker Rm Shower X 5 102 HT Bldg 800 Boys RR Hall X 5 103 HT Bldg 800 Boys Locker Rm X 5 104 HT Bldg 800 Boys Boiler Rm X 5 106 HT Bldg 400 Storage X 5 113 HT Bldg 400 RR X 5 116 Date: 10/14/21 4 ) Owners Rep Sign: Inspector Sign: ALARM AND DETECTION REPORT Page 5 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# HT Weight Rm X 8 3 HT Weight Rm X 8 5 HT Weight Rm X 8 6 HT Weight Rm X 8 7 HT Kitchen Heat X 8 15 HT Kitchen Heat X 8 16 HT Bldg 700 Kitchen X 8 17 HT Bldg 700 Kitchen X 8 18 HT Bldg 700 Firefly X 8 19 HT Bldg 700 Cashiers X 8 20 HT Bldg 700 Kitchen X 8 21 HT Bldg 700 Kitchen X 8 22 HT Bldg 700 Workroom X 8 23 HT Bldg 700 Mens RR X 8 24 HT Bldg 700 Mens RR X 8 25 HT Bldg 700 Workroom X 8 27 HT Bldg 700 Food Storage X 8 30 HT Bldg 700 Janitors X 8 31 HT Bldg 700 Kitchen AC X 8 34 HT Bldg 700 Kitchen AC X 8 34 HT Bldg 700 Kitchen AC X 8 34 HT Bldg 700 Kitchen AC X 8 34 HT Bldg 1500 Electrical X 33 16 HT Bldg 1500 Staff RR X 33 17 HT Bldg 1500 Staff RR X 33 18 HT Bldg 1500 Boys RR X 33 32 HT Bldg 1500 Girls RR X 33 33 HT Bldg 200 Womens RR X 33 43 HT Bldg 200 Womens RR X 33 44 HT Bldg 200 Womens RR X 33 45 HT Bldg 600 Storage 605 X 33 67 4 Date: 10/14/21 ) Owners Rep Sign: Inspector Sign: ALARM AND DETECTION REPORT Page of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# HT Bldg 600 Toilet 604 X 33 68 HT Bldg 600 Rm 601 X 33 76 HT Bldg 600 Rm 601 X 33 77 HT Bldg 600 Rm 601 X 33 78 HT Bldg 300 Project Rm 303 X 33 96 HT Bldg 300 Project Rm 303 X 33 97 HT Bldg 300 Finish Rm 304 X 33 98 HT Bldg 300 Work Rm 305 X 33 99 HT Bldg 300 Shop 306 X 33 100 HT Bldg 300 Shop 306 X 33 101 HT Bldg 300 Shop 306 X 33 102 HT Bldg 300 Shop 306 X 33 103 HT Bldg 300 Toilet 309 X 33 104 HT Bldg 300 Work Rm 310 X 33 105 HT Bldg 300 308 Mezz X 33 107 HT Bldg 300 Shop 311 X 33 109 HT Bldg 200 Mens RR X 33 113 HT Bldg 200 Mens RR X 33 114 HT Bldg 200 Mens RR X 33 115 HT Bldg 300 Shop 311 X 33 117 HT Bldg 300 Shop 311 X 33 118 HT Bldg 300 Shop 311 X 33 119 HT Bldg 300 Shop 311 X 33 120 HT Bldg 300 Shop 311 X 33 122 HT Bldg 1500 Staff Rm X 33 4-1 HT Bldg 1500 Staff Rm X 33 4-2 HT Bldg 1500 Staff Rm X 33 4-3 HT Bldg 1500 Staff Rm X 33 4-4 HT Bldg 1500 Staff Rm X 33 4-5 HT Bldg 1500 Staff Rm X 33 4-6 HT Bldg 1500 Rm 1502 AC X 33 4-7 Owners Rep Sign: Date: 10/14/21 Inspector Sign: ALARM AND DETECTION REPORT Page 6 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# HT Bldg 1500 Rm 1502 AC X 33 4-8 HT Bldg 1500 Rm 1502 AC X 33 4-9 HT Bldg 1500 Rm 1502 AC X 33 4-10 HT Bldg 1500 Rm 1502 AC X 33 4-11 HT Bldg 1500 Rm 1502 AC X 33 4-12 HT Bldg 1500 Rm 1501 AC X 33 3-1 HT Bldg 1500 Rm 1501 AC X 33 3-2 HT Bldg 1500 Rm 1501 AC X 33 3-3 HT Bldg 1500 Rm 1501 AC X 33 3-4 HT Bldg 1500 Rm 1501 AC X 33 3-5 HT Bldg 1500 Rm 1500 AC X 33 3-6 HT Bldg 1500 Rm 1500 AC X 33 3-7 HT Bldg 1500 Rm 1500 AC X 33 3-8 HT Bldg 1500 Rm 1500 AC X 33 3-9 HT Bldg 1500 Rm 1500 AC X 33 3-10 HT Bldg 1500 Rm 1500 AC X 33 3-11 HT Bldg 1500 Rm 1500 AC X 33 3-12 HT Bldg 1500 Rm 1500 AC X 33 3-12 HT Bldg 1500 Rm 1500 AC X 33 3-12 HT Bldg 1500 N. Breezeway X 33 1 HT Bldg 1500 N. Breezeway X 33 1 HT Bldg 1500 N. Breezeway X 33 1 HT Bldg 1500 N. Breezeway X 33 1 HT Bldg 1500 N. Breezeway X 33 1 HT Bldg 1500 N. Breezeway X 33 1 HT Bldg 1500 N. Breezeway X 33 1 HT Bldg 1500 N. Breezeway X 33 1 HT Bldg 1500 Rm 1503 AC X 33 6-1 HT Bldg 1500 Rm 1503 AC X 33 6-2 HT Bldg 1500 Rm 1503 AC X 33 6-3 HTO Bldg 1500 Rm 1503 AC X 33 6-4 Date: 10/14/21 ' ) Owners Rep Sign: Inspector Sign: ALARM AND DETECTION REPORT Page 7 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# HT Bldg 1500 Rm 1503 AC X 33 6-5 HT Bldg 1500 Rm 1503 AC X 33 6-6 HT Bldg 1500 Rm 1503 AC X 33 6-7 HT Bldg 1500 Rm 1503 AC X 33 6-8 HT Bldg 1500 Rm 1503 AC X 33 6-9 HT Bldg 1500 Rm 1504 AC X 33 6-10 HT Bldg 1500 Rm 1504 AC X 33 6-11 HT Bldg 1500 Rm 1504 AC X 33 6-12 HT Bldg 1500 Rm 1504 AC X 33 6-13 HT Bldg 1500 Rm 1504 AC X 33 6-14 HT Bldg 1500 Rm 1504 AC X 33 6-15 HT Bldg 1500 Rm 1504 AC X 33 6-16 HT Bldg 1500 Rm 1505 AC X 33 7-1 HT Bldg 1500 Rm 1505 AC X 73s 7-2 HT Bldg 1500 Rm 1505 AC X 33 7-3 HT Bldg 1500 RR AC X 33 7-8 HT Bldg 1500 RR AC X 33 7-9 HT Bldg 1500 RR AC X 33 7-10 HT Bldg 1500 RR AC X 33 7-11 HT Bldg 1500 RR AC X 33 7-12 HT Bldg 1500 RR AC X 33 7-12 HT Port 629 X 33 75 HT Bldg 300 Janitor 302 X 33 95 HT Bldg 1200 Toilet 1260 X 3 79 HT Bldg 1200 Toilet 1250 X 3 95 HT Bldg 1200 Boys 1248 X 3 92 Date: 10/14/21 Owners Rep Sign: Inspector Sign: ALARM AND DETECTION REPORT Page 8 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PSD Bldg 100 Rm 102 X 3 3 PSD Bldg 100 Rm 102 X 3 4 PSD Bldg 100 Rm 103 X 3 5 PSD Bldg 100 Rm 103 X 3 6 PSD Bldg 100 Rm 104 X 3 7 PSD Bldg 100 Rm 104 X 3 8 PSD Bldg 100 Rm 105 X 3 9 PSD Bldg 100 Rm 105 X 3 10 PSD Bldg 100 Rm 106 X 3 11 PSD Bldg 100 Rm 106 X 3 12 PSD Bldg 100 Corridor X 3 14 PSD Bldg 100 Corridor X 3 15 PSD Bldg 100 Corridor X 3 16 PSD Bldg 100 Corridor X 3 17 PSD Bldg 100 Corridor X 3 18 PSD Bldg 100 Corridor X 3 19 PSD Bldg 100 Corridor X 3 20 PSD Bldg 100 Rm 110 X 3 25 PSD Bldg 100 Rm 110 X 3 26 PSD Bldg 100 Rm 111 X 3 27 PSD Bldg 100 Rm 111 X 3 28 PSD Bldg 100 Rm 112 X 3 29 PSD Bldg 100 Rm 112 X 3 30 PSD Bldg 100 Rm 113 X 3 31 PSD Bldg 100 Rm 113 X 3 32 PSD Bldg 100 Rm 114 X 3 33 PSD Bldg 100 Rm 114 X 3 34 PSD Bldg 500 Rm 501 X 3 42 PSD Bldg 500 Rm 501 X 3 43 PSD Bldg 500 Rm 50 X 3 45 PSD Rm 501 Office X 3 46 ./ Date: 10/14/21 C Owners Rep Sign: Inspector Sign: ALARM AND DETECTION REPORT Page 9 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas Hiah School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PSD Bldg 500 Rm 502 X 3 47 PSD Bldg 500 Rm 502 X 3 48 PSD Bldg 500 Rm 502 X 3 51 PSD Bldg 500 Rm 502 X 3 52 PSD Bldg 500 Rm 503 X 3 53 PSD Library Office X 3 54 PSD Bldg 500 Rm 507 X 3 55 PSD Bldg 500 Rm 507 X 3 56 PSD Bldg 500 Rm 507A X 3 57 PSD Bldg 500 Rm 507 X 3 58 PSD Library Staff X 3 59 PSD Bldg 1200 Band X 3 63 PSD Bldg 1200 Band X 3 64 PSD Bldg 1200 Band X 3 65 PSD Bldg 1200 Band X 3 67 PSD Bldg 1200 Band X 3 68 PSD Bldg 1200 Band X 3 69 PSD Bldg 1200 Band X 3 70 PSD Bldg 1200 Band X 3 72 PSD Bldg 1200 Band X 3 73 PSD Bldg 1200 Practice X 3 76 PSD Bldg 1200 Entry X 3 77 PSD Bldg 1200 Office X 3 85 PSD Bldg 1200 Hall X 3 86 PSD Bldg 1200 Drum Room X 3 87 PSD Bldg 1200 Hall X 3 88 PSD Bldg 1200 Band X 3 91 PSD Bldg 1200 Uniform Rm X 3 93 PSD Bldg 1200 Hall X 3 94 PSD Gym Ticket Booth X 3 111 PSD Bldg 400 Lobby 427 X 5 3 Owners Rep Sign: Date: 10/14/21 Inspector Sign: S ALARM AND DETECTION REPORT Page 10 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas Hiah School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PSD Bldg 400 Office X 5 4 PSD Principal's Office X 5 5 PSD Vice Principal's Office X 5 6 PSD Bldg 400 Office X 5 7 PSD Bldg 400 Office 422 X 5 8 PSD Bldg 400 Work Rm X 5 9 PSD Bldg 400 Work Rm X 5 10 PSD Bldg 400 Conference Rm X 5 12 PSD Bldg 400 Hallway X 5 13 PSD Bldg 400 Office 422B X 5 14 PSD Bldg 400 Attendance X 5 15 PSD Bldg 400 Hallway X 5 16 PSD Bldg 400 Counselors X 5 17 PSD Bldg 400 Counselors X 5 18 PSD Bldg 400 Counselors X 5 19 PSD Bldg 400 Deans Office X 5 20 PSD Bldg 400 Deans 404 X 5 21 PSD Bldg 400 Hallway X 5 22 PSD Bldg 400 Counselors 420A X 5 23 PSD Bldg 400 Nurses X 5 24 PSD Old Gym SW Foyer X 5 26 PSD Old Gym NW Foyer X 5 27 PSD Girls Locker Rm Entry X 5 28 PSD 900 Girls Locker Team Rm X 5 37 PSD 900 Girls Locker Team Rm X 5 38 PSD 900 Girls Locker Coaches Dress X 5 46 PSD 900 Girls Locker Coaches Dress X 5 47 PSD 900 Girls Locker Team Rm X 5 69 PSD 900 Girls Locker Team Rm X 5 70 PSD Old Gym Front Foyer X 5 76 PSD 800 Boys Locker Entry X 5 78 4 Date: 10/14/21 ) Owners Rep Sign: InspectorSign: ALARM AND DETECTION REPORT Page 11 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PSD 800 Boys Locker Team Rm X 5 82 PSD 800 Boys Locker Team Rm X 5 83 PSD 800 Boys Locker Team Rm X 5 84 PSD 800 Boys Locker Team Rm X 5 85 PSD 800 Boys Locker Coaches Office X 5 88 PSD Boys Locker RM X 5 93 PSD 800 Boys Locker Storage X 5 99 PSD 800 Boys Locker Storage X 5 100 PSD 800 Boys Locker Storage X 5 107 PSD Bldg 400 Office 418 X 5 108 PSD Bldg 400 RR 403 X 5 109 PSD Bldg 400 Hallway X 5 110 PSD Bldg 400 Audion 417 X 5 111 PSD Bldg 400 Nurses 416 X 5 112 PSD Bldg 400 RR 402 X 5 114 PSD Bldg 400 Lounge 401 X 5 115 PSD Bldg 400 Work Rm 412 X 5 119 PSD Bldg 400 Faculty X 5 121 PSD Bldg 400 Faculty X 5 122 PSD Bldg 700 Dining 701 X 8 26 PSD Bldg 700 Kitchen Entrance X 8 32 PSD Bldg 700 RR X 8 33 PSD Bldg 1500 Staff Rm X 33 19 PSD Bldg 1500 Rm 1502 X 33 20 PSD Bldg 1500 Rm 1502 X 33 21 PSD Bldg 1500 Rm 1501 X 33 22 PSD Bldg 1500 Rm 1501 X 33 23 PSD Bldg 1500 Rm 1501A X 33 24 PSD Bldg 1500 Rm 1501A X 33 25 PSD Bldg 1500 Rm 1503 X 33 26 PSD Bldg 1500 Rm 1503 X 33 27 °PSOwners Rep Sign: Date: 10/14/21 Inspector Sign: ALARM AND DETECTION REPORT Page 12 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PSD Bldg 1500 Rm 1504 X 33 28 PSD Bldg 1500 Rm 1504 X 33 29 PSD Bldg 1500 Rm 1505 X 33 30 PSD Bldg 1500 Rm 1505 X 33 31 PSD Bldg 200 Corridor X 33 35 PSD Bldg 200 Corridor X 33 36 PSD Bldg 200 Corridor X 33 37 PSD Bldg 200 Corridor X 33 38 PSD Bldg 200 Corridor X 33 39 PSD Bldg 200 Corridor X 33 40 PSD Bldg 200 Corridor X 33 41 PSD Bldg 200 Rm 203 X 33 46 PSD Bldg 200 Rm 203 X 33 47 PSD Bldg 200 Rm 203 Projects X 33 48 PSD Bldg 200 Rm 203 Storage X 33 49 PSD Bldg 200 Rm 206 X 33 50 PSD Bldg 200 Rm 206 X 33 51 PSD Bldg 200 Rm 206 Storage X 33 52 PSD Bldg 200 Rm 206 Projects X 33 54 PSD Bldg 200 Rm 211 X 33 55 PSD Bldg 200 Rm 211 X 33 56 PSD Bldg 200 Rm 220 X 33 57 PSD Bldg 200 Rm 220 X 33 58 PSD Bldg 200 Rm 219 X 33 59 PSD Bldg 200 Rm 219 X 33 60 PSD Bldg 200 Rm 218 X 33 61 PSD Bldg 200 Rm 218 X 33 62 PSD Bldg 200 Rm 218 Projects X 33 63 PSD Bldg 600 Rm 606 X 33 65 PSD Bldg 600 Rm 606 X 33 66 PSD Bldg 600 Rm 602 X 33 69 4S Owners Rep Sign: Date: 10/14/21 Inspector Sign: p ALARM AND DETECTION REPORT Page 13 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PSD Bldg 600 Rm 602 X 33 70 PSD Bldg 600 Storage X 33 71 PSD Bldg 600 Rm 602 X 33 72 PSD Bldg 600 West Hall X 33 81 PSD Bldg 600 West Hall X 33 82 PSD Bldg 600 Center Hall X 33 83 PSD Bldg 600 East Hall X 33 84 PSD Bldg 600 East Hall X 33 85 PSD Bldg 600 Rm 612 X 33 87 PSD Bldg 600 Rm 612 X 33 88 PSD Bldg 600 Rm 611 X 33 89 PSD Bldg 600 Rm 611 X 33 90 PSD Bldg 600 Rm 610 X 33 91 PSD Bldg 600 Rm 610 X 33 92 PSD Bldg 600 Rm 609 X 33 93 PSD Bldg 600 Rm 609 X 33 94 PSD Bldg 300 Rm 308 X 33 94 PSD Bldg 300 Rm 308 X 33 106 PSD Bldg 300 Rm 307 X 33 108 PSD Bldg 200 Storage X 33 110 PSD Bldg 200 Rm 215 X 33 111 PSD Bldg 200 Rm 215 X 33 112 PSD Bldg 200 Corridor X 33 116 PSD Bldg 300 Rm 307 X 33 123 PSD Bldg 300 Rm 313 X 33 124 PSD Bldg 700 Office 701 B X 8 28 PSD Gym Ticket Booth X 3 111 q,'S Owners Rep Sign: Date: 10/14/21 Inspector Sign: ALARM AND DETECTION REPORT Page 14 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas Hiah School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PS Gym N. Exit X 3 120 PS Bldg 400 Lobby X 5 1 PS Bldg 400 Lobby X 5 2 PS Old Gym Girls Exit X 5 29 PS Old Gym West Exit X 5 30 PS Old Gym West Exit X 5 31 PS Bldg 900 Girls Exit X 5 59 PS Old Gym Front Entrance X 5 77 PS Bldg 800 Boys Exit X 5 98 PS Bldg 400 Facility Rm X 5 120 PS Bldg 700 SW Entry X 8 1 PS Bldg 700 Weight Rm X 8 4 PS Bldg 700 MP SE X 8 8 PS Bldg 700 MP NE X 8 9 PS Rm 613 X 8 51 PS Rm 614 X 8 52 PS Rm 615 X 8 53 PS Rm 616 X 8 54 PS Rm 618 X 8 55 PS Rm 619 X 8 56 PS Rm 621 X 8 58 PS Rm 622 X 8 59 PS Rm 623 X 8 60 PS Rm 624 X 8 61 PS Rm 620 X 8 57 PS Bldg 1500 Staff Rm X 33 9 PS Bldg 1500 Rm 1502 X 33 10 PS Bldg 1500 Rm 1501 X 33 11 PS Bldg 1500 Rm 1501A X 33 12 PS Bldg 1500 Rm 1505 X 33 13 PS Bldg 1500 Rm 1504 X 33 14 4 Date: 10/14/21 ) Owners Rep Sign: Inspector Sign: ALARM AND DETECTION REPORT Page 15 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumes High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PS Bldg 1500 Rm 1504 X 33 15 PS Bldg 1500 Rm 1503 X 33 34 PS Bldg 200 E Exit X 33 42 PS Bldg 200 W Exit X 33 73 PS Portable 1201 X 33 73 PS Portable 1202 X 33 73 PS Portable 1203 X 33 73 PS Portable 1204 X 33 74 PS Aerobics Portable X 33 74 PS Aerobics Portable X 33 74 PS Aerobics Portable X 33 75 PS South Portables X 33 75 PS South Portables X 33 75 PS South Portables X 33 75 PS South Portables X 33 75 PS South Portables X 33 75 PS South Portables X 33 75 PS South Portables X 33 75 PS South Portables X 33 75 PS South Portables X 33 75 PS Bldg 600 E Exit X 33 86 PS Gym Rear Exit X 3 19 PS Gym Ticket Booth X 3 112 4 Date: 10/14/21 ) Owners Rep Sign: Inspector Sign: ALARM AND DETECTION REPORT Page 16 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumas High School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PDD Gym Duct Girls Locker X 3 5 PDD Gym Duct Girls Locker X 3 5 PDD Gym Duct Boys Locker X 3 6 PDD Gym Duct Boys Locker X 3 6 PDD Shop Classroom 313 X 3 121 PDD New Gym X 3 127-1 PDD New Gym X 3 127-2 BD 700 Bldg MP X 8 10 BD 700 Bldg MP X 8 11 BD 700 Bldg MP X 8 12 BD 700 Bldg MP X 8 13 BD 700 Bldg MP X 8 14 BD Gym Beam North X 3 100 BD Gym Beam North Mid X 3 101 BD Gym Beam South Mid X 3 102 BD Gym Beam South X 3 103 BD Gym Beam North X 5 32 BD Gym Beam South X 5 33 TS Room 601 Ansul X 33 79 q,'S Date: 10/14/21 Ins ector Owners Rep Sign: pSign: ALARM AND DETECTION REPORT Page 17 of 17 VOLTAGE SPECIALISTS 530-624-4514 #880862 Property Site: Las Plumes Hiah School DEVICE ZONE OR SLC TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL DEVICE# PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve SSD—Signal Station Scnoke Detector B—Bell AV—Audible Visual PIV—Post Indicator Valve NOTES Yes jj See Discrepancy Rep Yes ✓ )S Date: 10/14/21 C Owners Rep Sign: Inspector Sign: