HomeMy WebLinkAboutFAI20-0026 010180008 CF FA 2021 Fire Alarm and Life Safety System Inspection Certificate For Wilson Elementary School 429 Magnolia Street Gridley, CA 95948 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Annual Inspection Inspection Date Jul 19, 2021 Building:Wilson Elementary School Company: Hue&Cry,Inc, Contact:Jordan Reeves Contact:Nick Kuykendall Title: Superintendent Title:INSPECTOR/TECHNICIAN 1 Executive Summary Generated by:BuildingReparts.corn Building Information Building: Wilson Elementary School Contact: Jordan Reeves Address:429 Magnolia Street Phone: 1-530-846-4721 Address: Fax: City/State/Zip: Gridley, CA 95948 Mobile: Country: United States of America Email:jreeves@gusd.org Inspection Performed By Company: Hue&Cry, Inc. Inspector: Nick Kuykendall Address: 1751 Bruce Drive Phone: 800-800-alarm Address: Fax: City/State/Zip:Anderson, California 96007 Mobile: Country: United States of America Email: n.kuykendall@hueandcry.com System Control Unit Manufacturer: Honeywell Inspection Date: 07/19/2021 IDC Style: Model Number: 6820 EVS Install Date: 01/30/2005 SLC Style: Software Version: Version Date: 11/20/2018 NAG Style: Location: Custodian Room Current Protection: Breaker Disconnect Location: Custodian Room Type: Breaker Hue&Cry,Inc. Page 1 of 11 Download Date:05/25/2022 Executive Summary Inspection Summary Total Items Serviced Passed Failed/Other Category: �---.....__ Qty % 1 Qty °i° Qty % Qty % Control 15 15.00% 15 100.00% 15 100.00% 0 0.00% Indicating 40 40.00% 40 100.00% 40 100.00% 0 0.00% Initiating 45 45.00% 45 100.00% 45 100.00% 0 0.00% Totals I 100 I 100% 100 100.00% I 100 100.00% 0 0.00% Certification Company: Hue&Cry, Inc. Building: Wilson Elementary School Inspector: Nick Kuykendall Contact: Jordan Reeves Signed: Jul 19, 2021 Signed: Jul 19, 2021 Hue&Cry,Inc. Page 2 of 11 Download Date:05/25/2022 Executive Summary Inspection & Testing Generated by:BuildingReports.com Building; Wilson Elementary School Control Panel 1 The Inspection& Testing section lists all of the items inspected in your building.Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time&date at which testing occurred. Device:Type Location I Service Time Date I Passed Control Annunciator Office Tested 12:53:12 PM 07/19/2021 Battery Custodian Room Tested 2:12:18 PM 07/19/2021 Battery Custodian Room Tested 2:12:21 PM 07/19/2021 Battery Power Supply kitchen Tested 1:20:15 PM 07/19/2021 Battery Room 22 Tested 1:44:47 PM 07/19/2021 Battery Room 22 Tested 1:44:51 PM 07/19/2021 Battery Room 22 Tested 1:45:58 PM 07/19/2021 Battery Room 22 Tested 1:46:03 PM 07/19/2021 Disconnect Janitors Room Main Hall Tested 2:04:57 PM 07/19/2021 Disconnect Kitchen Circuit Panel B#12 Tested 1:22:36 PM 07/19/2021 Disconnect Room 22 Tested 1:44:37 PM 07/19/2021 Power Supply Kitchen Tested 1:20:03 PM 07/19/2021 Power Supply Room 22 Tested 1:44:43 PM 07/19/2021 Power Supply Room 22 Tested 1:48:00 PM 07/19/2021 indicating Horn Library Outside Tested 1:57:10 PM 07/19/2021 Horn Main Hall Room 16 Tested 1:26:17 PM 07/19/2021 Horn Main Hall Rooms 11-12 Tested 1:26:10 PM 07/19/2021 Horn Main Hall at Janitors Room Tested 1:26:14 PM 07/19/2021 Horn Outside Room 21 Tested 1:44:09 PM 07/19/2021 Horn Outside Room 25 Tested 1:49:41 PM 07/19/2021 Horn Outside Room 32 Tested 1:09:15 PM 07/19/2021 Horn Outside Room 35 Tested 1:09:11 PM 07/19/2021 Horn Outside Rooms 19-20 Tested 1:44:04 PM 07/19/2021 Horn Room 36. EOL 3.9k 27v Tested 12:59:02 PM 07/19/2021 Horn Room 25 Tested 1:57:16 PM 07/19/2021 Horn Room 26 Tested 1:57:04 PM 07/19/2021 Horn Room 30 Tested 1:14:03 PM 07/19/2021 Horn Room 31 Tested 1:12:29 PM 07/19/2021 Hue&Cry,Inc. Page 3 of 11 Download Date:05/25/2022 Inspection&Testing Device Type Location Service Time Date Passed 1 Horn Room 32 Tested 1:11:11 PM 07/19/2021 Horn Room 33 Tested 1:09:34 PM 07/19/2021 Horn Room 34 Tested 1:06:01 PM 07/19/2021 Horn Room 35 Tested 1:06:17 PM 07/19/2021 Horn/Strobe Cafe North EOL 3.9k 27v Annual 1:19:24 PM 07/19/2021 Horn/Strobe Cafe South Annual 1:17:05 PM 07/19/2021 Speaker Outside Room 17 Tested 1:30:27 PM 07/19/2021 Speaker Outside Room 19 Tested 1:42:31 PM 07/19/2021 Speaker/Strobe Boys Restroom Tested 1:57:25 PM 07/19/2021 Speaker/Strobe Girls Restroom Tested 1:58:36 PM 07/19/2021 Speaker/Strobe Room 17 Tested 1:30:13 PM 07/19/2021 Speaker/Strobe Room 17 Tested 1:30:17 PM 07/19/2021 Speaker/Strobe Room 18 Tested 1:36:15 PM 07/19/2021 Speaker/Strobe Room 19 Tested 1:38:55 PM 07/19/2021 Speaker/Strobe Room 20 Tested 1:40:11 PM 07/19/2021 Speaker/Strobe Room 21 Tested 1:43:28 PM 07/19/2021 Speaker/Strobe Room 22 Tested 1:46:40 PM 07/19/2021 Speaker/Strobe Staff Restroom Tested 1:32:52 PM 07/19/2021 Speaker/Strobe Staff Restroom Tested 1:33:40 PM 07/19/2021 Speaker/Strobe Storage Tested 1:35:17 PM 07/19/2021 Speaker/Strobe Office Room 17 Tested 1:29:55 PM 07/19/2021 Speaker/Strobe Restroom Room 17 Tested 1:30:06 PM 07/19/2021 Strobe Boys R/R by Room 33 Tested 2:01:55 PM 07/19/2021 Strobe Girls R/R by Room 33 Tested 2:01:40 PM 07/19/2021 Strobe Handicap R/R by Room 33 Tested 2:02:23 PM 07/19/2021 Strobe Kitchen Tested 1:49:13 PM 07/19/2021 Initiating Heat Detector Room 17 Tested 1:39:23 PM 07/19/2021 Heat Detector Room 18 Tested 1:39:27 PM 07/19/2021 Heat Detector Room 18 Tested 1:42:08 PM 07/19/2021 Heat Detector Room 19 Tested 1:42:05 PM 07/19/2021 Heat Detector Room 20 Tested 1:42:00 PM 07/19/2021 Heat Detector Room 21 Tested 1:44:16 PM 07/19/2021 9 Heat Detector Room 22 Tested 1:46:58 PM 07/19/2021 Heat Detector Restroom Room 17 Tested 1:39:20 PM 07/19/2021 Pull Station Cafe North Tested 1:19:28 PM 07/19/2021 Pull Station Cafe South Tested 1:17:01 PM 07/19/2021 Hue&Cry,Inc. Page 4 of 11 Download Date:05/25/2022 Inspection&Testing Device Type [ Location Service Time 1 Date Passed Pull Station Main Hall North Doors Tested 12:33:28 PM 07/19/2021 Pull Station Main Hall Office Tested 12:34:51 PM 07/19/2021 Pull Station Main Hall Room 14B Tested 1:27:10 PM 07/19/2021 Pull Station Main Hall South End Tested 1:27:05 PM 07/19/2021 Pull Station Office Tested 1:27:00 PM 07/19/2021 Pull Station Room 24 Tested 1:50:56 PM 07/19/2021 Pull Station Room 25 Tested 1:53:06 PM 07/19/2021 Pull Station Room 26 Tested 1:55:02 PM 07/19/2021 Pull Station Room 30 Tested 1:13:58 PM 07/19/2021 Pull Station Room 31 Tested 1:12:34 PM 07/19/2021 Pull Station Room 32 Tested 1:11:19 PM 07/19/2021 Pull Station Room 33 Tested 1:09:38 PM 07/19/2021 Pull Station Room 34 Tested 1:06:08 PM 07/19/2021 Pull Station Room 35 Tested 1:27:17 PM 07/19/2021 Pull Station Room 36 Tested 12:55:51 PM 07/19/2021 Smoke Detector Boys Restroom Tested 1:58:15 PM 07/19/2021 Smoke Detector Girls Restroom Tested 1:58:42 PM 07/19/2021 Smoke Detector Room 17 Tested 1:28:36 PM 07/19/2021 Smoke Detector Room 17 Tested 1:30:34 PM 07/19/2021 Smoke Detector Room 17 Tested 1:30:37 PM 07/19/2021 Smoke Detector Room 18 Tested 1:37:54 PM 07/19/2021 Smoke Detector Room 19 Tested 1:39:41 PM 07/19/2021 Smoke Detector Room 19 Tested 1:39:46 PM 07/19/2021 Smoke Detector Room 20 Tested 1:41:45 PM 07/19/2021 Smoke Detector Room 20 Tested 1:41:48 PM 07/19/2021 Smoke Detector Room 21 Tested 1:42:20 PM 07/19/2021 Smoke Detector Room 21 Tested 1:42:25 PM 07/19/2021 Smoke Detector Room 22 Tested 1:49:22 PM 07/19/2021 Smoke Detector Room22 Tested 1:48:52 PM 07/19/2021 Smoke Detector Staff Restroom Tested 1:34:59 PM 07/19/2021 Smoke Detector Staff Restroom Tested 1:35:03 PM 07/19/2021 Smoke Detector Storage Tested 1:43:48 PM 07/19/2021 Smoke Detector Storage room Tested 1:43:52 PM 07/19/2021 Smoke Detector Custodian Room Tested 12:29:01 PM 07/19/2021 Smoke Detector Office Room 17 Tested 1:30:41 PM 07/19/2021 Hue&Cry,Inc. Page 5 of 11 Download Date:05/25/2022 Inspection&Testing Building: Wilson Elementary School Control Panel: 2 - Honeywell 6820 EVS The Inspection& Testing section lists all of the items inspected in your building.Items are grouped by Passed or Failed/Other.Items are listed by Category.Each item includes the services performed, and the time&date at which testing occurred. Device Type I Location Service. I Time Date °e'. :y Passed Control Control Panel Custodian Room Tested 12:29.56 PM 07/19/2021 Hue&Cry,Inc. Page 6 of 11 Download Date:05/25/2022 Inspection&Testing Service Summary Generated by:BuildingReports.cont Building: Wilson Elementary School The Service Summary section provides an overview of the services performed in this report. Devices Type 1Service _ 1. y .. Passed Annunciator Tested 1 Battery Tested 7 Control Panel Tested 1 Disconnect Tested 3 Heat Detector Tested g Horn/Strobe Annual 2 Horn Tested 18 Power Supply Tested 3 Pull Station Tested 17 Smoke Detector Tested 20 Speaker/Strobe Tested 14 Speaker Tested 2 Strobe Tested 4 Total 100 Grand Total 100 Hue&Cry,Inc. Page 7 of 11 Download Date:05/25/2022 Service Summary Auxiliary Functions Testing Generated by:BuildingReports.com dY® ® liternbiltaW40,001 Control Panel` ;14] The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated. Type 'Location Comment Scan1D Simulated J Passed Smoke Detector Smoke Compartment Boys Restroom Passed 44834527 Smoke Compartment Girls Restroom Passed 44834526 Smoke Compartment Room 17 Passed 44834499 Smoke Compartment Room 17 Passed 44834500 Smoke Compartment Room 17 Passed 44834501 Smoke Compartment Room 18 Passed 44834510 Smoke Compartment Room 19 Passed 448314 Smoke Compartment Room 19 Passed 44834515 Smoke Compartment Room 20 Passed 44834520 Smoke Compartment Room 20 Passed 44834518 Smoke Compartment Room 21 Passed 44834521 Smoke Compartment Room 21 Passed 4623 Smoke Compartment Room 22 Passed 44834539 Smoke Compartment Room22 Passed 44834538 Smoke Compartment Staff Restroom Passed 44834486 Smoke Compartment Staff Restroom Passed 44834488 Smoke Compartment Storage Passed 44834491 Smoke Compartment Storage room Passed 44834481 • Smoke Compartment Custodian Room Passed 60675142 Smoke Compartment Office Room 17 Passed 44834506 Hue&Cry,Inc. Page 8 of 11 Download Date:05/25/2022 Auxiliary Functions Testing Battery & Power Supply Testing Generated by:BuildingReports.coin Building: Wilson Elementary School Control Panel: 1 The Battery&Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other. Rated Rated Post Type Location , Ah Volts Pre Test Test 1 Min Ah , Tested Ah;. Battery Passed Lead Acid Custodian Room 8 12 Lead Acid Custodian Room 8 12 Sealed Lead Acid Power Supply kitchen 7 12 Lead Acid Room 22 8 12 12.78 4.55 12ah Lead Acid Room 22 8 12 12.87 4.55 12ah Lead Acid Room 22 8 12 12.79 4.55 l l ah Lead Acid Room 22 8 12 12.87 4.55 7.9 Hue&Cry,Inc. Page 9 of 11 Download Date:05/25/2022 Battery&Power Supply Testing Inventory & Warranty Report Generated by:BuildingReports.corr Building: Wilson Elementary School Control Panel: 1 j The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report.A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. 1pevice:rType Category 1 %of Inventory 1 Quantity Annunciator Control 1.00% 1 Battery Control 7.00% 7 Control Panel Control 1.00% 1 Disconnect Control 3.00% 3 Heat Detector Initiating 8.00% 8 Horn Indicating 18.00% 18 Horn/Strobe Indicating 2.00% 2 Power Supply Control 3.00% 3 Pull Station Initiating 17.00% 17 Smoke Detector Initiating 20.00% 20 Speaker Indicating 2.00% 2 Speaker/Strobe Indicating 14.00% 14 Strobe Indicating 4.00% 4 Type Qty 1 Model# Description Install Date In Service - 1 Year to 2 Years Power-Sonic Battery 1 PS-1270 F1 Sealed Lead Acid 11/24/2020 In Service - 2 Years to 3 Years Duracell Battery 1 DURA12-8F2 Lead Acid 01/30/2020 • In Service - 15 Years to 25 Years GE Disconnect 1 20amp Breaker 01/31/2005 Disconnect 1 Breaker 01/30/2005 Duracell Battery 5 DURA12-8F2 Lead Acid 01/30/2005 FCI Horn 9 130-3117c 01/30/2005 Pull Station 10 MS-2 Dual Action 01/30/2005 Faraday Horn 1 01/30/2005 Fire-Lite Pull Station 2 BG10 Dual Action 01/30/2005 Hue&Cry,Inc. Page 10 of 11 Download Date:05/25/2022 inventory&Warranty Report Gentex Horn/Strobe 2 GX90s-4-15/75WR 01/30/2005 Strobe 1 GXS-4-15/75WR 01/30/2005 Honeywell Power Supply 1 EVS-50W 01/30/2005 Smoke Detector 1 SK- Fire-Co Combination 01/30/2005 Smoke Detector 19 SK- Photo Photoelectric 01/30/2005 Silent Knight Annunciator 1 01/30/2005 Heat Detector 8 SK-HEAT-HT Fixed Temperature 01/30/2005 Power Supply 1 5496 01/30/2005 Standard Horn 5 14 01/30/2005 Power Supply 1 Fire Lite Box Only 01/30/2005 Pull Station 1 11531258 Single Action 01/30/2005 Pull Station 4 750 Single Action 01/30/2005 System Sensor Speaker 2 SPWK 01/30/2005 Speaker/Strobe 2 SPSCRL 01/30/2005 Speaker/Strobe 12 SPSRL 01/30/2005 Wheelock Horn 3 MT 12/24 01/30/2005 Strobe 3 RS-241575 01/30/2005 Zinsco Disconnect 1 20amp Breaker 01/30/2005 Building; Wilson Elementary School Control Panel: 2 - Honeywell 6820 EVSJ The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report.A complete inventory count by device type and category is provided.Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. Type Qty ,i Model# ,Description Install Date In Service - 15 Years to 25 Years Honeywell Control Panel 1 6820 EVS 01/30/2005 Hue&Cry,Inc. Page 11 of 11 Download Date:05/25/2022 Inventory&Warranty Report