HomeMy WebLinkAboutFAI19-0037 010041001 CF FA 2021 -6yc2morc, C(VAMz. Sc.h00 � aka
Training and Drill Schedule
Fire
Tues. Oct 5, 2021
2nd period
Code Red
Tues. Jan 25, 2021
4th period
Earthquake/Fire Drill
Thurs. Feb. 10,2022
6th period
Code Red
Tues. Mar. 3,2022
3rd period
Fire Alarm and Life Safety System
Inspection Certificate
For
Sycamore Middle School
1125 Sycamore Street
Gridley, CA 95948
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages
of this report provide performance measurements, listed ranges of acceptable results, and complete
documentation of the inspection. Whenever discrepancies exist between acceptable performance
standards and actual test results, notes and/or recommended solutions have been proposed or provided
for immediate review and approval.
Annual Inspection
Inspection Date
Jul 20, 2021
Building: Sycamore Middle School Company: Hue&Cry,Inc.
Contact:Jordan Reeves Contact:johnathan jones
Title: Superintendent Title: inspector
A
Executive Summary
Generated by:BuiddingReparts.cam
Building Information
Building: Sycamore Middle School Contact: Jordan Reeves
Address: 1125 Sycamore Street Phone: 1-530-846-34721
Address: Fax:
City/State/Zip: Gridley, CA 95948 Mobile:
Country: United States of America Email:jreeves@gusd.org
Inspection Performed By
Company: Hue &Cry, Inc. Inspector:johnathan jones
Address: 1751 Bruce Drive Phone: 916-956-0859
Address: Fax:
City/State/Zip:Anderson, California 96007 Mobile:
Country: United States of America Email: J.jones@hueandcry.com
System Control Unit 1
Manufacturer: Honeywell inspection Date: 07/20/2021 IDC Style: B
Model Number: 6820EVS Install Date: 10/17/1995 SLC Style: n/a
Software Version: Version Date: 10/17/1995 NAC Style:Y
Location: Office Current Protection: Breaker
Disconnect Location: Office Type: Breaker
Hue&Cry,Inc. Page 1 of 10 Download Date:05/25/2022
Executive Summary
Inspection Summary
Total Items I Serviced l Passed 1 Failed/Other
Category:
Qty % I Qty 1 % Qty % Qty %
Control 17 17.53% 17 100.00% 17 100.00% 0 0.00%
Indicating 53 54,64'Y 53 100.00% 53 100.00% 0 0.00%
Initiating 27 27,84% 27 100.00% 27 100.00% 0 0.00%
Totals 97 l 100% 97 100.00% 97 100.00% 0 I 0.00%
Certification
Company: Hue&Cry, Inc. Building: Sycamore Middle School
Inspector:johnathan jones Contact: Jordan Reeves
914( 1
Signed: Jul 20, 2021 Signed:
Hue&Cry,Inc. Page 2 of 10 Download Date:05/25/2022
Executive Summary
Inspection & Testing
Generated by;BuildingReports.com
Building: Sycamore Middle School Control Panel: l .- Honeywell 6820EVS, 1
The Inspection& Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other.Items are listed by Category.Each item includes the services performed, and the time&date at which testing
occurred.
' evice4TJpe F .. ... Location :_ I SerS+c .. Tithetle Date
Passed
Control
Battery Extender Panel Annual 12:22:47 PM 07/20/2021
Battery Extender Panel Annual 12:23:40 PM 07/20/2021
Battery FACP Annual 12:26:38 PM 07/20/2021
Battery FACP Annual 12:27:26 PM 07/20/2021
Battery Portable 21 Annual 12:34:01 PM 07/20/2021
Battery Portable 21 Annual 12:34:50 PM 07/20/2021
Battery Portable 21 Right Power supply Annual 12:31:14 PM 07/20/2021
Battery Portable 21 Right Power supply Annual 12:32:46 PM 07/20/2021
Communication Line Office Annual 12:28:42 PM 07/20/2021
Communication Line Office Annual 12:28:45 PM 07/20/2021
Control Panel
Office Annual 12:56:08 PM 07/20/2021
Disconnect Nurses Office Circuit Breaker#13 Annual 12:56:11 PM 07/20/2021
Disconnect Portable 21 Breaker 13 Annual 12:56:13 PM 07/20/2021
Expander Panel Office next to FACP Annual 12:56:16 PM 07/20/2021
Indicating
Horn Counselors Office Annual 12:56:28 PM 07/20/2021
Horn Gym East Annual 12:56:46 PM 07/20/2021
Horn Hall by Room 15 Annual 11:22:30 AM 07/20/2021
Horn Main Hall by Rooms 2-3 Annual 11:20:57 AM 07/20/2021
Horn Nurses Office Annual 12:56:20 PM 07/20/2021
Horn Office Conference Room Annual 12:56:25 PM 07/20/2021
Horn Offices for Counselors Annual 12:17:42 PM 07/20/2021
Horn
Outside by Room 23 Annual 12:56:37 PM 07/20/2021
Horn Outside by Rooms 19 Annual 12:56:44 PM 07/20/2021
Horn Outside by Rooms 21 Annual 12:56:40 PM 07/20/2021
Horn Staff Lounge Annual 12:56:34 PM 07/20/2021
Horn Library Annual 12:56:31 PM 07/20/2021
Hue&Cry,Inc. Page 3 of 10 Download Date:05/25/2022
Inspection&Testing
-Device '0e 1.uA Lticat on I Service , . Time Date
----- Passed
Horn Office Annual 12:56:23 PM 07/20/2021
Horn/Strobe Band Room Annual 12:55:41 PM 07/20/2021
Horn/Strobe Boys R/R Outside Main Bldg Annual 12:55:46 PM 07/20/2021
Horn/Strobe Boys R/R by Media Room Annual 12:57:14 PM 07/20/2021
Horn/Strobe Girls R/R by Media Room Annual 12:57:17 PM 07/20/2021
Horn/Strobe Hall by Girls RIR by Main Bldg Annual 12:57:02 PM 07/20/2021
Horn/Strobe Main Hall West near Storage Annual 11:18:13 AM 07/20/2021
Horn/Strobe Main Hall by Rooms 5-6 Annual 11:18:35 AM 07/20/2021
Horn/Strobe Office Lobby Annual 12:56:55 PM 07/20/2021
Horn/Strobe Outside Main Bldg West Annual 12:56:59 PM 07/20/2021
Horn/Strobe Storage by Rooms 15-16 Annual 12:57:07 PM 07/20/2021
Horn/Strobe Portables 17 Annual 11:24:20 AM 07/20/2021
Horn/Strobe Portables 17 Annual 11:26:12 AM 07/20/2021
i
Horn/Strobe Portables 18 Annual 11:27:31 AM 07/20/2021
Horn/Strobe Portables 18 Annual 11:28:32 AM 07/20/2021
Horn/Strobe Portables 19 Annual 11:40:35 AM 07/20/2021
Horn/Strobe Portables 19 Annual 11:40:55 AM 07/20/2021
Horn/Strobe Portables 20 Annual 11:41:58 AM 07/20/2021
Horn/Strobe Portables 20 Annual 11:42:44 AM 07/20/2021
Horn/Strobe Portables 21 Annual 11:32:38 AM 07/20/2021
Horn/Strobe Portables 21 Annual 11:33:34 AM 07/20/2021
Horn/Strobe Room 1 Annual 12:57:27 PM 07/20/2021
Horn/Strobe Room 10 Annual 12:55:56 PM 07/20/2021
Horn/Strobe Room 11 Annual 12:57:55 PM 07/20/2021
Horn/Strobe Room 12 Annual 12:57:45 PM 07/20/2021
Horn/Strobe Room 13 Annual 12:57:34 PM 07/20/2021
Horn/Strobe Room 14 Annual 12:57:31 PM 07/20/2021
Horn/Strobe Room 15 Annual 12:57:11 PM 07/20/2021
Horn/Strobe Room 16 Annual 12:57:05 PM 07/20/2021
Horn/Strobe Room 2 Annual 12:57:40 PM 07/20/2021
Horn/Strobe Room 23 Annual 11:12:14 AM 07/20/2021
Horn/Strobe Room 23 Restroom Annual 12:56:50 PM 07/20/2021
Horn/Strobe Room 3 Annual 12:57:49 PM 07/20/2021
Horn/Strobe Room 4 Annual 12:57:51 PM 07/20/2021
Horn/Strobe Room 5 Annual 12:57:57 PM 07/20/2021
Horn/Strobe Room 6 Annual 12:55:58 PM 07/20/2021
Horn/Strobe Room 7 Annual 12:55:49 PM 07/20/2021
Hue&Cry,Inc. Page 4 of 10 Download Date:05/25/2022
Inspection&Testing
Device,Typie ° Location I Service Time Date
Passed
Horn/Strobe Room 8 Annual 12:56;53 PM 07/20/2021
Horn/Strobe Room 9 Annual 12:55:53 PM 07/20/2021
Strobe Counselors R/R Annual 12:55:31 PM 07/20/2021
Strobe Nurses R/R Annual 12:55:28 PM 07/20/2021
Initiating
Heat Detector Portable 17 Annual 12:16:04 PM 07/20/2021
Heat Detector Portable 18 Annual 12:13:55 PM 07/20/2021
Heat Detector Portable 19 Annual 11:53:09 AM 07/20/2021
Heat Detector Portable 20 Annual 12:09:16 PM 07/20/2021
Heat Detector Portable 20 Annual 12:11:22 PM 07/20/2021
Pull Station Band Room Annual 11:09:12 AM 07/20/2021
Pull Station Gym East Annual 11:02:34 AM 07/20/2021
Pull Station Gym North Annual 11:05:16 AM 07/20/2021
Pull Station Gym West Exit Annual 11:04:00 AM 07/20/2021
Pull Station Hall by Room 15 Annual 11:22:27 AM 07/20/2021
Pull Station Main Hall between Rooms 5-6 Annual 11:18:43 AM 07/20/2021
Pull Station Cafeteria Annual 11:46:12 AM 07/20/2021
Pull Station Kitchen Annual 11:47:14 AM 07/20/2021
Pull Station Main hall betwen rms 2&3 Annual 11:21:06 AM 07/20/2021
Pull Station Room 22 Annual 11:13:50 AM 07/20/2021
Pull Station Room 23 Annual 11:11:30 AM 07/20/2021
Smoke Detector Office Above FACP Annual 10:59:48 AM 07/20/2021
Smoke Detector Portable 17 Annual 11:24:08 AM 07/20/2021
Smoke Detector Portable 17 Annual 11:26:05 AM 07/20/2021
Smoke Detector Portable 18 Annual 11:27:38 AM 07/20/2021
Smoke Detector Portable 18 Annual 11:28:36 AM 07/20/2021
Smoke Detector Portable 19 Annual 11:40:30 AM 07/20/2021
Smoke Detector Portable 19 Annual 11:40:51 AM 07/20/2021
Smoke Detector Portable 20 Annual 11:42:09 AM 07/20/2021
Smoke Detector Portable 20 Annual 11:42:21 AM 07/20/2021
Smoke Detector Portable 21 Annual 11:32:31 AM 07/20/2021
Smoke Detector Portable 21 Annual 11:33:51 AM 07/20/2021
Hue&Cry,Inc. Page 5 of 10 Download Date:05/25/2022
Inspection&Testing
Building: Sycamore Middle School Control Panel: 2
The Inspection& Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other.Items are listed by Category.Each item includes the services performed, and the time&date at which testing
occurred.
Device Type Location Service Time I Date - '
Passed
Control
Power Supply Office Annual 12:28:33 PM 07/20/2021
Power Supply Portable 21 Annual 12:55:35 PM 07/20/2021
Power Supply Portable 21 Annual 12:55:38 PM 07/20/2021
Hue&Cry,Inc. Page 6 of 10 Download Date:05/25/2022
Inspection&Testing
Service Summary
Generated by:BuildingReports.cone
Building: Sycamore Middle School
The Service Summary section provides an overview of the services performed in this report.
svice "service ,
Quarts
I Passed
Battery Annual
8
Communication Line Annual 2
Control Panel Annual 1
Disconnect Annual 2
Expander Panel Annual 1
Heat Detector Annual 5
Horn/Strobe Annual 38
Horn Annual 13
Power Supply Annual 3
Pull Station Annual 11
Smoke Detector Annual 11
Strobe Annual 2
Total 97
Grand Total 97
Hue&Cry,Inc. Page 7 of 10 Download Date:05/25/2022
Service Summary
Battery & Power Supply Testing
r� &r Generated by:BuildrngReports.com
ld' Sys Vliddl,� School Control Panel: 1 - Honeywell 6820EVS
The Battery&Power Supply Testing section details the readings and measurements of batteries and power supplies used
to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Rated [ Rated { Post I
Type Location Ah f Volts Pre Test Test Min Ah j Tested Ah
Battery
Passed
Sealed Lead Acid Extender Panel 7 12 12.96 4.55 8
Sealed Lead Acid Extender Panel 7 12 12.76 4.55 11
Sealed Lead Acid FACP 7 12 12.94 4.55 7.8
Sealed Lead Acid FACP 7 12 12.91 4.55 7.8
Sealed Lead Acid Portable 21 7 12 12.94 4.55 7.9
Sealed Lead Acid Portable 21 7 12 12.90 4.55 8
Sealed Lead Acid Portable 21 Right Power 7 12 12.88 4.55 8
supply
Sealed Lead Acid Portable 21 Right Power 7 12 12.84 4.55 11
supply
Hue&Cry,Inc. Page 8 of 10 Download Date:05/25/2022
Battery&Power Supply Testing
Inventory & Warranty Report
Generated by:BuildingReports.con:
Building: Sycamore Middle School Control Panel: 1 - Honeywell 6820EVS
The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report. A
complete inventory count by device type and category is provided.Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category i %of Inventory I Quantity
Battery Control 8.25% 8
Communication Line Control 2.06% 2
Control Panel Control 1.03% 1
Disconnect Control 2.06% 2
Expander Panel Control 1.03% 1
Heat Detector Initiating 5.15% 5
Horn Indicating 13.40% 13
Horn/Strobe Indicating 39.18% 38
Power Supply Control 3.09% 3
Pull Station Initiating 11.34% 11
Smoke Detector Initiating 11.34% 11
Strobe Indicating 2.06% 2
Type Qty Model# !Description Install Date
In Service - 2 Years to 3 Years
Duracell
Battery 1 DURAA12 Sealed Lead Acid 01/21/2020
Battery 4 DURA12 Sealed Lead Acid 08/22/2019
In Service - 3 Years to 5 Years
Duracell
Battery 2 DURA12 Sealed Lead Acid 01/21/2019
In Service- 5 rears to 10 Years
Fire-Lite
Heat Detector 5 H365 Rate-of-Rise 10/22/2014
Honeywell
Smoke Detector 11 SK-PHOTO Photoelectric 10/22/2014
Duracell
Battery 1 DURA12 Sealed Lead Acid 09/24/2013
I
In Service - 15 Years to 25 Years
Gentex
Horn 5 MHR 10/06/2003
Horn/Strobe 2 GXS-4-15/75WR 10/06/2003
Silent Knight
Horn/Strobe 1 10/06/2003
Pull Station 4 PS-SATK Single Action 10/06/2003
Hue&Cry,Inc. Page 9 of 10 Download Date:05/25/2022
Inventory&Warranty Report
SimplexGrinnell
Horn 6 2901-9838 10/06/2003
Horn 1 4901-9817 10/06/2003
Horn 1 GX90-4 10/06/2003
Horn/Strobe 23 2901-9838 10/06/2003
Pull Station 6 596B Single Action 10/06/2003
Pull Station 1 BG60 Single Action 10/06/2003
Strobe 2 unknown 10/06/2003
Squre D
Disconnect 2 20amp Breaker 10/06/2003
System sensor
Horn/Strobe 10 SPScRI 10/06/2003
Wheelock
Horn/Strobe 1 10/06/2003
Horn/Strobe 1 MT12/24 10/06/2003
SimplexGrinnell
Expander Panel 1 4009 08/20/2001
In Service - 25 Years or Older
Honeywell
Control Panel 1 6820EVS 10/17/1995
Phone line 1
Communication Line 1 846-2370 10/17/1995
Phone line 2
Communication Line 1 846-1275 10/17/1995
Building: Sycamore Middle School Control Panel 2
The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report. A
complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Mode!# Description lat'air Date.
In Service - 25 Years or Older
Honeywell
Power Supply 2 5496 05/20/1975
Power Supply 1 EVS-50W 05/20/1975
Hue&Cry,Inc. Page 10 of 10 Download Date:05/25/2022
Inventory&Warranty Report