HomeMy WebLinkAboutFAI20-0027 010141011 CF FA 2021 Fire Alarm and Life Safety System
Inspection Certificate
For
Esperanza High School
581 Jackson Street
Gridley, CA GRIDLEY
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages
of this report provide performance measurements, listed ranges of acceptable results, and complete
documentation of the inspection. Whenever discrepancies exist between acceptable performance
standards and actual test results, notes and/or recommended solutions have been proposed or provided
for immediate review and approval.
Annual Inspection
Inspection Date
Jul 19, 2021
Building: Esperanza High School Company: Hue&Cry,Inc.
Contact: Jordan Reeves Contact:johnathan jones
Title: Superintendent Title: inspector
Executive Summary
Generated by:BuildingReports.com
Building Information
Building: Esperanza High School Contact: Jordan Reeves
Address: 581 Jackson Street Phone: 1-530-846-4721
Address: Fax:
CitylStatelZip: Gridley, CA GRIDLEY Mobile:
Country: United States of America Email:jreeves@gusd.org
Inspection Performed By
Company: Hue&Cry, Inc. Inspector:johnathan jones
Address: 1751 Bruce Drive Phone: 916-956-0859
Address: Fax:
City/State/Zip:Anderson, California 96007 Mobile:
Country: United States of America Email: J.jones@hueandcry.com
System Control Unit
Manufacturer: Fire-Lite Inspection Date: 07/19/2021 IDC Style: B
Model Number: MS-5024UD Install Date: 01/30/2005 SLC Style:
Software Version: 43 Version Date: 02/04/2007 NAC Style: Y
Location: Water Heater/Staff Room Current Protection: Breaker
Disconnect Location:Water Heater/Staff Room Type: Breaker If
oni, cring x
Company: Hue&Cry, Inc. Phone: 800-800-ALARM Account#: 230018
Hue&Cry,Inc. Page 1 of 13 Download Date:05/25/2022
Executive Summary
Inspection Summary
f Total Items Serviced T Passed Failed/Other
Category:
i
Qty % Qty I °/n Qty % Qty %
Control 6 13.95% 6 100.00% 6 100.00% 0 0.00%
Indicating 17 39.53% 17 100.00% 16 94.12% 1 5.88%
Initiating 19 44.19% 19 100.00% 19 100.00% 0 0.00%
Supervisory 1 2.33% 1 100.00% 1 100.00% 0 0.00%
Totals I 43 1 100% 43 1100.00% I 42 97.67% 1 2.33%
Certification
l
Company: Hue&Cry, Inc. Building: Esperanza High School
Inspector:johnathan jones Contact: Jordan Reeves
I
Signed:Jul 20, 2021 Signed: Jul 19, 2021
Hue&Cry,Inc. Page 2 of 13 Download Date:05/25/2022
Executive Summary
Discrepancy Report
Generated by:BuildingReports.com
A High Esperanza Hi h School Control Panel: 1 - Fire-Lite MS-5O24UD �
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience.Any item that was inspected that is subject to a recall or part
of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanlD Location .Problem Address Reference
Indicating
Bell
1 13975309 Market Failed Operation 1 NFPA72 14.2.2.2.2
Code References
NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
Hue&Cry,Inc. Page 3 of 13 Download Date:05/25/2022
Discrepancy Report
Proposed Solutions Report
Generated by;BuildingReports.com
Building: Esperanza High School Control Panel: I - Fire-Lite MS-5024UD
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check
mark where indicated to approve repairs listed within the report.items listed as T/M are available for repair on a Time
and Materials basis.
Scanib Location Solution Model# Cost Fix
Indicating
Bell
13975309 Market Investigate SSV120-8 T/M ❑
PO#: (none) T/M
Hue&Cry,Inc. Page 4 of 13 Download Date:05/25/2022
Proposed Solutions Report
Notes & Recommendations
Generated by:BuildingReports.com
Building: Esperanza High School x`,:x.c" , k .
The Notes&Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection.Notes are grouped by Category.
General Note
Annual fire inspection
6/19/2021
Water flow bell failed to operate when water flow went into alarm needs to be investigated.
Hue&Cry,Inc. Page 5 of 13 Download Date:05/25/2022
Notes&Recommendations
Inspection & Testing
Generated by:BuildingReports.corn
Building: Esperanza High School Control Panel: i - Fire-Lite.MS-5024UD
The Inspection & Testing section lists all of the items inspected in your building.Items are grouped by Passed or
Failed/Other.Items are listed by Category. Each item includes the services performed, and the time&date at which testing
occurred.
°I ' 0c4F"]" Locatt0i I Service 'Ti I , tr[
e -.
Passed
Control
Battery FACP/Left Batt Annual 3:09:34 PM 07/19/2021
Battery FACP/Right Batt Annual 3:10:35 PM 07/19/2021
Control Panel Water Heater/Staff Room Annual 3:10:49 PM 07/19/2021
Disconnect S/E Whse Storage Area Annual 4:49:26 PM 07/19/2021
Phone Jack 530-846-2435 SEC Annual 3:09:22 PM 07/19/2021
Phone Jack 530-846-6721 PRI Annual 3:09:25 PM 07/19/2021
Indicating
Horn/Strobe Conference Room Annual 3:33:52 PM 07/19/2021
Horn/Strobe East Center Class Annual 3:01:00 PM 07/19/2021
Horn/Strobe East Outside Annual 3:33:55 PM 07/19/2021
Horn/Strobe
Lower LobbyCubicle Annual 3:33:58 PM 07/19/2021 i
Horn/Strobe N/W Classroom Annual 2:52:44 PM 07/19/2021
Horn/Strobe Office Annual 2:45:42 PM 07/19/2021
Horn/Strobe Principals Office Annual 2:58:36 PM 07/19/2021
Horn/Strobe S/E Classroom Annual 3:06:28 PM 07/19/2021
HornlStrobe West Ctr Classroom Annual 2:51:33 PM 07/19/2021
Strobe East Ctr Class Women's R/R Annual 3:02:53 PM 07/19/2021
Strobe S/E Class Men's R/R Annual 3:06:59 PM 07/19/2021
Strobe S/E Class Women's RJR Annual 3:07:09 PM 07/19/2021
Strobe S/W Class Men's R/R Annual 3:34:11 PM 07/19/2021
Strobe S/W Class Women's R/R Annual 3:07:43 PM 07/19/2021
Strobe Water Heater FACP R/R Annual 3:34:09 PM 07/19/2021
Strobe East center classroom mens restroom Annual 3:02:42 PM 07/19/2021
Initiating
Heat Detector Water Heater Room I FACP Annual 3:30:47 PM 07/19/2021
Pull Station N/W Exit Annual 2:51:59 PM 07/19/2021
Pull Station S/E Exit Annual 3:04:31 PM 07/19/2021
Pull Station S/W Exit Annual 2:50:19 PM 07/19/2021
Pull Station Front Entry Annual 2:59:04 PM 07/19/2021
Hue&Cry,Inc. Page 6 of 13 Download Date:05/25/2022
Inspection&Testing
....... .......
Device Type; ' , Location Service Time I Date
Passed
Smoke Detector Conference Room Annual 3:04:01 PM 07/19/2021
Smoke Detector East Ctr Class Annual 3:00:15 PM 07/19/2021
Smoke Detector East Ctr Class R/R Hall Annual 3:02:15 PM 07/19/2021
Smoke Detector N/E Office Annual 3:34:03 PM 07/19/2021
Smoke Detector NM Class Annual 2:53:11 PM 07/19/2021
Smoke Detector N/W Class Storage Annual 2:54:38 PM 07/19/2021
Smoke Detector Principals Office Annual 2:57:50 PM 07/19/2021
Smoke Detector SIE Class Annual 3:05:40 PM 07/19/2021
Smoke Detector SIE Class R/R Hall Annual 3:06:34 PM 07/19/2021
Smoke Detector S/W Class Annual 2:48:56 PM 07/19/2021
Smoke Detector S/W Class R/R Hall Annual 3:07:54 PM 07/19/2021
Smoke Detector Server Hall Annual 3:07:16 PM 07/19/2021
Smoke Detector West Ctr Class Annual 2:51:21 PM 07/19/2021
Waterflow Switch Market Riser Room in Front Annual 3:17:04 PM 07/19/2021
Supervisory
Tamper Switch Market Riser Room in Front Annual 3:16:54 PM 07/19/2021
Device T e. , ! Location
YP, ; I Service Time `I Date
Failed/Other
Indicating
1 Bell Market Annual 3:28:48 PM 07/19/2021
Hue&Cry,Inc. Page 7 of 13 Download Date:05/25/2022
Inspection&Testing
Service Summary
Generated by:BnildingReports.corn
Building: Esperanza High School
{
The Service Summary section provides an overview of the services performed in this report.
Device Type Service
Quantity.
Failed/Other
Bell Annual
1
Total ,l
Pas
Battery Annual 2
Control Panel Annual 1
Disconnect Annual 1
Heat Detector Annual 1
Horn/Strobe Annual 9
Phone Jack Annual 2
Pull Station Annual 4
Smoke Detector Annual 13
Strobe Annual
7
Tamper Switch Annual 1
Waterflow Switch Annual 1
Total
42
Grand Total 43
Hue&Cry,Inc. Page 8 of 13 Download Date: 05/25/2022
Service Summary
Auxiliary Functions Testing
Generated by:BuildingReports.com
Building: Esperanza High School Control Panel: I - Fire-Lite MS-5024UD
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are
controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type,
and a check box is provided to indicate if the test conducted was simulated.
'Type Location Comment ScanID Simulated
Passed
Heat Detector
Heat Compartment Water Heater Room/FACP Passed 11531319
Smoke Detector
Smoke Compartment Conference Room Passed 11531304
Smoke Compartment East Ctr Class Passed 11531310
Smoke Compartment East Ctr Class R/R Hall Passed 11531308
Smoke Compartment N/E Office Passed 11531301
Smoke Compartment NIW Class Passed 11531324
Smoke Compartment NIW Class Storage Passed 11531297
Smoke Compartment Principals Office Passed 11531303
Smoke Compartment SIE Class Passed 11531313
Smoke Compartment SIE Class R/R Half Passed 11531316
Smoke Compartment SIW Class Passed 11531333
Smoke Compartment S/W Class R/R Hall Passed 11531331
Smoke Compartment Server Hall Passed 11531317
Smoke Compartment West Ctr Class Passed 11531328
Hue&Cry,Inc. Page 9 of 13 Download Date:05/25/2022
Auxiliary Functions Testing
Time, Temperature & Level Testing
Generated by:BuildingReports.com
Building: Esperanza High School Control Panel: 1 - Fire-Lite MS-5024UD
The Time, Temperature, &Level Testing section details the measurements taken from various devices that are designed to
respond in a certain amount of time, respond at a certain temperature, or respond within the acceptable range of volume
or level.Items are grouped by Passed or Failed/Other.
I Type Location Comment Sec Deg LEI ScanlD
Passed
Waterflow Switch
Market Riser Room in Front Passed 9 n/a n/a 11531293
Hue&Cry,Inc_ Page 10 of 13 Download Date:05/25/2022
Time,Temperature Sc Level Testing
Battery & Power Supply Testing
Generated by:BuildingReports.corn
Building Esperanza High School Control Panel: 1 -Fire-Lite MS-5024UD
The Battery&Power Supply Testing section details the readings and measurements of batteries and power supplies used
to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Rated Rated Post
_,Type Location
j Ah Volts Pre Test Test Min Ah Tested Ah
Battery
II
I Passed Sealed Lead Acid FACP/Left Bail 7 12 12.72 4.55 8
Sealed Lead Acid FACP/Right Batt 7 12 12.65 4.55 11
Hue&Cry,Inc. Page 11 of 13 Download Date: 05/25/2022
Battery&Power Supply Testing
Inventory & Warranty Report
Generated by:BuildingReports.com
Building: Esperanza High School Control Panel: 1 - Fire-Lite MS-5024UD
The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report.A
complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
ti Category j olo of Invento �-
ry Qgan>rtjr:-
Battery Control 4.65% �
2
Bell Indicating 2,33% 1
Control Panel Control 2.33% 1
Disconnect Control o
2.33/o 1
Heat Detector Initiating 2.33% 1
Horn/Strobe Indicating 20.93% 9
Phone Jack Control o
4.65/0 2
Pull Station Initiating 9.30% 4
Smoke Detector Initiating 30.23% 13
Strobe Indicating 16.28% 7
Tamper Switch Supervisory 2.33% 1
Waterfrow Switch Initiating 2.33% 1
Type ,.
Qty Model# Description Install Date
In Service - 3 Years to 5 Years
Power-Sonic
Battery 2 PS-1270 F1 Sealed Lead Acid 11/19/2018
I In Service - 15 Years to 25 Years
Phone Jack 1 RJ-31 X l
01/30/2005
Phone Jack 1 RJ-31X 01/30/2005
Fire-Lite
Control Panel 1 MS-5024UD 01/30/2005
Pull Station 4 BG-12 Dual Action 01/30/2005
GE
Disconnect 1 20amp Breaker 01/30/2005
System Sensor
Bell 1 SSV120-8 01/30/2005
Heat Detector 1 5601P Combination 01/30/2005
Horn/Strobe 8 P2R 01/30/2005
Horn/Strobe 1 P2RK 01/30/2005
Smoke Detector 13 2W-B Photoelectric 01/30/2005
Strobe 7 SR 01/30/2005
Tamper Switch 1 OSY2 01/30/2005
Waterflow Switch 1 WFD60 01/30/2005
Hue&Cry,Inc. Page 12 of 13 Download Date:05/25/2022
Inventory&Warranty Report
Zone Address Report
Generated by:BuildingReports.com
Building: Esperanza High School y Control Panel: 1 -'Fire-Lite MS-5O24UD
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a
common zone. The device type, location, and description are included for your reference.
Address Device T e —. — —. _n --
yp loocation ` Type ScanlD v
Zone/Circuit: 1
Pull Station NIW Exit Dual Action 11531325
Pull Station S/E Exit Dual Action 11531312
Pull Station S/W Exit Dual Action 11531334
Pull Station Front Entry Dual Action 11531299
Zone/Circuit: 2
Smoke Detector NIW Class Photoelectric 11531324
Smoke Detector N/W Class Storage Photoelectric 11531297
Smoke Detector SM/Class Photoelectric 11531333
Heat Detector Water Heater Room/FACP Combination 11531319
Smoke Detector West Ctr Class Photoelectric 11531328
Zone/Circuit: 3
Smoke Detector Conference Room Photoelectric 11531304
Smoke Detector East Ctr Class Photoelectric 11531310
Smoke Detector East Ctr Class R/R Hall Photoelectric 11531308
Smoke Detector NIE Office Photoelectric 11531301
Smoke Detector Principals Office Photoelectric 11531303
Smoke Detector S/E Class Photoelectric 11531313
Smoke Detector S/E Class R/R Hall Photoelectric 11531316
Smoke Detector SIW Class R/R Hall Photoelectric 11531331
Smoke Detector Server Hall Photoelectric 11531317
ZonelCircuit: 4
Waterflow Switch Market Riser Room in Front 11531293
Zone/Circuit: 5
Tamper Switch Market Riser Room in Front 11531294
Hue&Cry,Inc. Page 13 of 13 Download Date:05/25/2022
Zone Address Report