HomeMy WebLinkAboutFAI20-0025 010210026 CF FA 2021 Fire Alarm and Life Safety System
Inspection Certificate
For
Gridley High School
300 East Spruce Street
Gridley, CA 95948
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages
of this report provide performance measurements, listed ranges of acceptable results, and complete
documentation of the inspection. Whenever discrepancies exist between acceptable performance
standards and actual test results, notes and/or recommended solutions have been proposed or provided
for immediate review and approval.
Annual Inspection
Inspection Date
JuI20, 2021
Building: Gridley High School Company: Hue&Cry,Inc.
Contact:Jordan Reeves Contact:johnathan jones
Title: Superintendent Title: inspector
Executive Summary
Generated by:BuildingReports.com
Building Infoiiiiation
Building: Gridley High School Contact: Jordan Reeves
Address: 300 East Spruce Street Phone: 1-530-846-4721
Address: Fax:
City/State/Zip: Gridley, CA 95948 Mobile:
Country: United States of America Email:jreeves@gusd.org
Inspection Performed By
Company: Hue &Cry, Inc. Inspector:johnathan jones
Address: 1751 Bruce Drive Phone: 916-956-0859
Address: Fax:
City/State/Zip:Anderson, California 96007 Mobile:
Country: United States of America Email: J.jones@hueandcry.com
System Control Unit
Manufacturer: Fire-Lite Inspection Date: 07/19/2021 IDC Style: B
Model Number: Sensiscan 1000 Install Date: 07/21/2010 SLC Style:
Software Version: Version Date: 07/21/2010 NAC Style:Y
Location: Office Conference Room Current Protection: Breaker
Disconnect Location: Office Conference Room Type: Breaker
Hue&Cry,Inc. Page 1 of 13 Download Date:05/25/2022
Executive Summary
Inspection Summary
Total Items Serviced I Passed Failed/Other
Category: IQty
%
Qty pia Qty Rio Qty % Qty Rio
Control 8 15.38°/ 8 100.00% 6 75.00% 2 25.00%
Indicating 20 38.46% 20 100.00°/ 1 5.00% 19 95.00%
Initiating 24 46.15% 24 100.00% 1 4.17% 23 95.63%
Totals I 52 1 100% 52 100.00% I 8 15.38% 44 84.62% j
Certification
Company: Hue&Cry, inc. Building: Gridley High School
Inspector:johnathan Jones Contact: Jordan Reeves
F/IF-/
Signed: Signed: Jul 19, 2021
Hue&Cry,Inc. Page 2 of 13 Download Date:05/25/2022
Executive Summary
Discrepancy Report
Generated by:Bui ldingReports.com
Building; Gridley High School Control Panel: l Fire Lite Sensiscan
1000 .
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience.Any item that was inspected that is subject to a recall or part
of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade
Pull Station Fire-Lite BG-10 04/01/2013 1
ScaniD I Location Problem Address Reference
Control
Battery
118891963 FACP Requires 1
Maintenance
1 18891964 FACP Left Batt Requires 1
Maintenance
Indicating
Horn
13975300 200 Wing East 1
13975298 200 Wing West 1
13975296 300 Wing 1
13975289 400 Wing North Side 1
13975291 400 Wing West Side 1
13975285 Auto Shop 1
13975997 Boys Locker Room 1
13975993 Girls Locker Room 1
41245625 Leadership Bldg 1
13975295 Library Hall 1
13975995 Outside Locker Room North 1
13975280 Room 209 Outside 1
13975991 Team Room 1
13975281 Welding Bldg 1
13975283 Wood Shop 1
13975272 portable 603 1
Horn/Strobe
13975287 N/E Portable 1
41245650 Room 209 1
Hue&Cry,Inc. Page 3 of 13 Download Date:05/25/2022
Discrepancy Report
Location Problem I Address Reference
41245677 Room 211 1
Initiating
Pull Station
1 41245676 200 Wing East Failed Operation 1 NFPA72 14.2.2.2.2
13975299 200 Wing West 1
13975297 300 Wing 1
1 13975290 400 Wing East Failed Operation 1 NFPA72 14.2.2.2.2
1 13975292 400 Wing West Failed Operation 1 NFPA72 14.2.2.2.2
1 13975286 Auto Shop Failed Operation 1 NFPA72 14.2.2.2.2
1 13975996 Boys Locker Room Failed Operation 1 NFPA72 14.2.2.2.2
1 13975994 Girls Locker Room Failed Operation 1 NFPA72 14.2.2.2.2
1 13975990 Leadership Bldg Failed Operation 1 NFPA72 14.2.2.2.2
1 13975294 Library Hall East Failed Operation 1 NFPA72 14.2.2.2.2
1 13975293 Library Hall West Failed Operation 1 NFPA72 14.2.2.2.2
1 13975288 NIE Portable Room 603 Failed Operation 1 NFPA72 14.2.2.2.2
1 13975273 Office Failed Operation 1 NFPA72 14.2.2.2.2
1 13975275 Office Hall Failed Operation 1 NFPA72 14.2.2.2.2
1 13975279 Room 209 Failed Operation 1 NFPA72 14.2.2.2.2
13975277 Room 211 1
1 13975992 Team Room Failed Operation 1 NFPA72 14.2.2.2.2
1 13975282 Welding Bldg Failed Operation 1 NFPA72 14.2.2.2.2
1 13975284 Wood Shop Failed Operation 1 NFPA72 14.2.2.2.2
Smoke Detector
13975983 Room 209 1
13975984 Room 209 1
13975987 Room 211 1
13975988 Room 211 1
- Code References
p.
NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
Hue&Cry,Inc. Page 4 of 13 Download Date:05/25/2022
Discrepancy Report
Proposed Solutions Report
Generated by:BuildingReports.com
Building: Gridley High School Control Panel: 1 - Fire-Lite Sensiscan 1000 I
The Proposed Solution Report provides a solution Jra each discrepancy listed on the Discrepancy Report. Provide a check
mark where indicated to approve repairs listed within the report.Items listed as T/M are available for repair on a Time
and Materials basis.
ScanlD Location 'Solution Modei ' .1' ""Cost ; [ E7 I
Control
Battery
18891963 FACP Investigate PS-12180NB T/M 0
18891964 FACP Left Batt Investigate PS-12180NB T/M 0
Indicating
Horn
13975300 200 Wing East SC806A1004 T/M 0
13975298 200 Wing West 34-24 T/M 0
13975296 300 Wing SC806A1004 T/M 0
13975289 400 Wing North Side SC806A1004 T/M 0
13975291 400 Wing West Side 5C806A1004 T/M 0
13975285 Auto Shop SC806A1004 T/M 0
13975997 Boys Locker Room 4040 T/M 0
13975993 Girls Locker Room 4040 T/M ❑
41245625 Leadership Bldg SC806A1004 T/M 0
13975295 Library Hall SC806A1004 T/M 0
13975995 Outside Locker Room North 31T-115 T/M 0
13975280 Room 209 Outside H12/24K T/M El
13975991 Team Room 4040 T/M ❑
13975281 Welding Bldg SC806A1004 T/M ❑
13975283 Wood Shop SC806A1004 T/M ❑
13975272 portable 603 MT-24R T/M 0
Horn/Strobe
13975287 N/E Portable NS-24MCW TIM 0
41245650 Room 209 P2R T/M ❑
41245677 Room 211 P2R T/M 0
Initiating
Pull Station
41245676 200 Wing East Investigate BG-12 T/M 0
13975299 200 Wing West S464A1045 T/M ❑
13975297 300 Wing S464A1045 T/M 0
13975290 400 Wing East Investigate S464A1045 T/M 0
13975292 400 Wing West Investigate S464A1045 T/M 0
Hue&Cry,Inc. Page 5 of 13 Download Date:05/25/2022
Proposed Solutions Report
1 Building: Gridley High School Control Panel: 1 - Fire-Lite Sensiscan 1000
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check
mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time
and Materials basis.
ScanlD ,i `t I Location Solution Model#- .'Cost 1iX
Initiating
Pull Station
13975286 Auto Shop Investigate S46A1045 T/M 0
13975996 Boys Locker Room Investigate 4251-1 125v T/M 0
13975994 Girls Locker Room Investigate 4251-1 125v T/M 0
13975990 Leadership Bldg Investigate S464A1045 T/M 0
13975294 Library Hall East Investigate S464A1045 T/M 0
13975293 Library Hall West Investigate S464A1045 T/M 0
13975288 N/E Portable Room 603 Investigate 2099-9101 T/M 0
13975273 Office Investigate S464A1045 T/M 0
13975275 Office Hall Investigate S46A1045 T/M 0
13975279 Room 209 Investigate BG-12 T/M ❑
13975277 Room 211 BG-12 T/M ❑
13975992 Team Room Investigate 4251-1 125v T/M ❑
13975282 Welding Bldg Investigate S46A1045 T/M ❑
13975284 Wood Shop Investigate S46A1045 T/M
Smoke Detector
13975983 Room 209 DS282 T/M ❑
13975984 Room 209 DS282 T/M 0 .
13975987 Room 211 DS282 T/M ❑
13975988 Room 211 DS282 T/M 0
PO#: (none) T/M l
Hue&Cry,Inc. Page 6 of 13 Download Date:05/25/2022
Proposed Solutions Report
Notes & Recommendations
Generated by:BuildingReports.corn
Building: Gridley High School
The Notes&Recommendations Report details additional inspection notes made by the inspectors during the course of the
building inspection. Notes are grouped by Category.
General Note
Annual fire inspection
G/19/2021
19 of the 20 fire pole stations failed to operate
Battery in booster panel are dead and have short circuited and panel may be dead needs to be investigated
Hue&Cry,Inc. Page 7 of 13 Download Date:05/25/2022
Notes&Recommendations
Inspection & Testing
Generated by:BuildingReports.com
Control Panel: 1 - Fire-Lite Sensiscan
Building: Gridley High School
1000
The Inspection& Testing section lists all of the items inspected in your building.Items are grouped by Passed or
Failed/Other.Items are listed by Category. Each item includes the services performed, and the time&date at which testing
occurred.
Device Type 1 Location. 1 Service Time i Date
Passed
Control
Battery 10th Below Connector Cell Room 211 Annual 9:52:21 AM 07/19/2021
Power Supply
Battery Room 211 Power Supply Annual 9:52:18 AM 07/19/2021
Control Panel Office Conference Room Annual 12:14:20 PM 07/19/2021
Disconnect Room 211 #14A Annual 12:14:26 PM 07/19/2021
Disconnect Staff Break Room Hall -C/B A2#2 Annual 12:14:23 PM 07/19/2021
Power Supply Room 211 above Ceiling Tile Annual 9:52:07 AM 07/19/2021
Indicating
Bell Office Hall Annual 10:02:17 AM 07/19/2021
Initiating
Pull Station 100 Wing Outside Annual 4:14:27 PM 07/20/2021
Device Type Location I Service Time,,, i bite
Failed/Other
Control
1 Battery FACP Tested 8:29:22 AM 07/20/2021
1 Battery FACP Left Batt Tested 8:29:07 AM 07/20/2021
Indicating
Horn 200 Wing East Annual 12:15:18 PM 07/19/2021
Horn 200 Wing West Tested 12:15:13 PM 07/19/2021
Horn 300 Wing Tested 12:14:41 PM 07/19/2021
Horn 400 Wing North Side Annual 12:15:01 PM 07/19/2021
Horn 400 Wing West Side Annual 12:15:05 PM 07/19/2021
Horn Auto Shop Annual 12:14:57 PM 07/19/2021
Horn Boys Locker Room Tested 12:15:30 PM 07/19/2021
Horn Girls Locker Room Tested 12:15:24 PM 07/19/2021
Horn Leadership Bldg Tested 12:15:34 PM 07/19/2021
Horn Library Hall Annual 12:15:08 PM 07/19/2021
Horn Outside Locker Room North Tested 12:15:27 PM 07/19/2021
Hue&Cry,Inc. Page 8 of 13 Download Date: 05/25/2022
Inspection&Testing
Device Type 1 Location Service Time Date
Failed/Other
Horn Room 209 Outside Annual 12:14:49 PM 07/19/2021
Horn Team Room Tested 12:15:21 PM 07/19/2021
Horn Welding Bldg Annual 12:14:51 PM 07/19/2021
Horn Wood Shop Annual 12:14:54 PM 07/19/2021
Horn portable 603 Annual 12:14:46 PM 07/19/2021
Horn/Strobe N/E Portable Tested 12:15:37 PM 07/19/2021
Horn/Strobe Room 209 Tested 12:15:39 PM 07/19/2021
Horn/Strobe Room 211 Tested 12:15:43 PM 07/19/2021
Initiating
1 Pull Station 200 Wing East Annual 10:06:57 AM 07/19/2021
Pull Station 200 Wing West Tested 4:14:11 PM 07/20/2021
Pull Station 300 Wing Tested 4:14:08 PM 07/20/2021
1 Pull Station 400 Wing East Annual 10:18:45 AM 07/19/2021
1 Pull Station 400 Wing West Tested 12:16:12 PM 07/19/2021
1 Pull Station Auto Shop Tested 10:45:30 AM 07/19/2021
1 Pull Station Boys Locker Room Tested 10:29:06 AM 07/19/2021
1 Pull Station Girls Locker Room Tested 10:29:29 AM 07/19/2021
1 Pull Station Leadership Bldg Annual 10:39:48 AM 07/19/2021
1 Pull Station Library Hall East Annual 10:17:17 AM 07/19/2021
1 Pull Station Library Hall West Annual 10:16:09 AM 07/19/2021
1 Pull Station N/E Portable Room 603 Annual 10:48:14 AM 07/19/2021
1 Pull Station Office Annual 10:01:49 AM 07/19/2021
1 Pull Station Office Hall Annual 12:15:59 PM 07/19/2021
1 Pull Station Room 209 Annual 10:38:32 AM 07/19/2021
Pull Station Room 211 Tested 12:15:50 PM 07/19/2021 E
1 Pull Station Team Room Tested 10:45:54 AM 07/19/2021
1 Pull Station Welding Bldg Annual 10:41:20 AM 07/19/2021
1 Pull Station Wood Shop Annual 10:43:40 AM 07/19/2021
Smoke Detector Room 209 Tested/Cleaned 3:34:34 PM 07/19/2021
Smoke Detector Room 209 Tested/Cleaned 3:34:37 PM 07/19/2021
Smoke Detector Room 211 Tested/Cleaned 3:34:41 PM 07/19/2021
Smoke Detector Room 211 Tested/Cleaned 3:34:46 PM 07/19/2021
Hue&Cry,Inc. Page 9 of 13 Download Date:05/25/2022
Inspection&Testing
Service Summary
Generated by:BuildingReports.com
Building: Gridley High School
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other
Battery Tested 2
Horn/Strobe Tested 3
Horn Annual 9
Horn Tested 7
Pull Station Annual 11
Pull Station Tested 8
Smoke Detector Tested/Cleaned 4
Total 44
Passed
Battery Annual 2
Bell Annual 1
Control Panel Annual 1
Disconnect Annual 2
Power Supply Annual 1
Pull Station Annual 1
Total 8
Grand Total 52
Hue&Cry,Inc. Page 10 of 13 Download Date: 05/25/2022
Service Summary
Battery & Power Supply Testing
Generated by.BuildingReports.com
Building: Gridley High School
Control Panel: I - Fire-Lite Sensiscan
laao
The.Battery&Power Supply Testing section details the readings and measurements of batteries and power supplies used
to provide power to the fire alarm and life safety systems.Items are grouped by Passed or Failed/Other.
Rated Rated Post
Type Location Ah Volts I Pre Test Test Min Ah Tested Ah
Battery
Passed
Sealed Lead Acid 10th Below Connector Cell 7 12
Room 211 Power Supply
Sealed Lead Acid Room 211 Power Supply 7 12
Failed/Other
Sealed Lead Acid FACP 18 12
Sealed Lead Acid FACP Left Batt 18 12
Hue&Cry,Inc. Page 11 of 13 Download Date:05/25/2022
Battery&Power Supply Testing
Inventory & Warranty Report
Generated by:BuildingReports.conz
Building: Gridley High School Control Panel: 1 - Fire-Lite Sensiscan 1000
The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report. A
complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
i Device or Type Category % of Inventory l Quantity
Battery Control 7.69% 4
Bell Indicating 1.92% 1
Control Panel Control 1.92% 1
Disconnect Control 3.85% 2
Horn Indicating 30.77% 16
Horn/Strobe Indicating 5.77% 3
Power Supply Control 1.92% 1
Pull Station Initiating 38.46% 20
Smoke Detector Initiating 7.69% 4
Type oty Mode!# !Description . Install Date
In Service - 5 Years to 10 Years
Power-Sonic
Battery 1 PS-1270F1 Sealed Lead Acid 10/21/2014
Ultra Tech
Battery 1 PS-1270F1 Sealed Lead Acid 10/21/2014
Power-Sonic
Battery 2 PS-12180NB Sealed Lead Acid 09/24/2013
In Service -- 10 Years to 15. Years
Altronix
Power Supply 1 AL300ULXR 07/21/2010
Detection Systems
Smoke Detector 4 DS282 Photoelectric 07/21/2010
Fire-Lite
Control Panel 1 Sensiscan 1000 07/21/2010
Pull Station 1 BG-10 Dual Action 07/21/2010
Pull Station 3 BG-12 Dual Action 07/21/2010
Honeywell
Horn 9 5C806A1004 07/21/2010
Pull Station 8 S464A1045 Single Action 07/21/2010
Pull Station 4 S46A1045 Single Action 07/21/2010
Modtech
Disconnect 1 15amp Breaker 07/21/2010
SimplexGrinnell
Horn 3 4040 07/21/2010
Hue&Cry,Inc. Page 12 of 13 Download Date:05/25/2022
Inventory&Warranty Report
Pull Station 1 2099-9101 Single Action 07/21/2010
(Pull Station 3 4251-1 125v Single Action 07/21/2010
Square D
Disconnect 1 20amp Breaker 07/21/2010
System Sensor
Horn 1 H12/24K 07/21/2010
Horn/Strobe
2 P2R 07/21/2010
Unknown
Bell 1 12" 07/21/2010
Wheelock
Horn 1 31 T-115 07/21/2010
Horn 1 34-24 07/21/2010
Horn 1 MT-24R 07/21/2010
Horn/Strobe 1 NS-24MCW 07/21/2010
Hue&Cry,Inc. Page 13 of 13 Download Date:05/25/2022
Inventory&Warranty Report