HomeMy WebLinkAboutFAI20-0025 010210026 CF FA 2021 Fire Alarm and Life Safety System Inspection Certificate For Gridley High School 300 East Spruce Street Gridley, CA 95948 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Annual Inspection Inspection Date JuI20, 2021 Building: Gridley High School Company: Hue&Cry,Inc. Contact:Jordan Reeves Contact:johnathan jones Title: Superintendent Title: inspector Executive Summary Generated by:BuildingReports.com Building Infoiiiiation Building: Gridley High School Contact: Jordan Reeves Address: 300 East Spruce Street Phone: 1-530-846-4721 Address: Fax: City/State/Zip: Gridley, CA 95948 Mobile: Country: United States of America Email:jreeves@gusd.org Inspection Performed By Company: Hue &Cry, Inc. Inspector:johnathan jones Address: 1751 Bruce Drive Phone: 916-956-0859 Address: Fax: City/State/Zip:Anderson, California 96007 Mobile: Country: United States of America Email: J.jones@hueandcry.com System Control Unit Manufacturer: Fire-Lite Inspection Date: 07/19/2021 IDC Style: B Model Number: Sensiscan 1000 Install Date: 07/21/2010 SLC Style: Software Version: Version Date: 07/21/2010 NAC Style:Y Location: Office Conference Room Current Protection: Breaker Disconnect Location: Office Conference Room Type: Breaker Hue&Cry,Inc. Page 1 of 13 Download Date:05/25/2022 Executive Summary Inspection Summary Total Items Serviced I Passed Failed/Other Category: IQty % Qty pia Qty Rio Qty % Qty Rio Control 8 15.38°/ 8 100.00% 6 75.00% 2 25.00% Indicating 20 38.46% 20 100.00°/ 1 5.00% 19 95.00% Initiating 24 46.15% 24 100.00% 1 4.17% 23 95.63% Totals I 52 1 100% 52 100.00% I 8 15.38% 44 84.62% j Certification Company: Hue&Cry, inc. Building: Gridley High School Inspector:johnathan Jones Contact: Jordan Reeves F/IF-/ Signed: Signed: Jul 19, 2021 Hue&Cry,Inc. Page 2 of 13 Download Date:05/25/2022 Executive Summary Discrepancy Report Generated by:Bui ldingReports.com Building; Gridley High School Control Panel: l Fire Lite Sensiscan 1000 . The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience.Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 1 ScaniD I Location Problem Address Reference Control Battery 118891963 FACP Requires 1 Maintenance 1 18891964 FACP Left Batt Requires 1 Maintenance Indicating Horn 13975300 200 Wing East 1 13975298 200 Wing West 1 13975296 300 Wing 1 13975289 400 Wing North Side 1 13975291 400 Wing West Side 1 13975285 Auto Shop 1 13975997 Boys Locker Room 1 13975993 Girls Locker Room 1 41245625 Leadership Bldg 1 13975295 Library Hall 1 13975995 Outside Locker Room North 1 13975280 Room 209 Outside 1 13975991 Team Room 1 13975281 Welding Bldg 1 13975283 Wood Shop 1 13975272 portable 603 1 Horn/Strobe 13975287 N/E Portable 1 41245650 Room 209 1 Hue&Cry,Inc. Page 3 of 13 Download Date:05/25/2022 Discrepancy Report Location Problem I Address Reference 41245677 Room 211 1 Initiating Pull Station 1 41245676 200 Wing East Failed Operation 1 NFPA72 14.2.2.2.2 13975299 200 Wing West 1 13975297 300 Wing 1 1 13975290 400 Wing East Failed Operation 1 NFPA72 14.2.2.2.2 1 13975292 400 Wing West Failed Operation 1 NFPA72 14.2.2.2.2 1 13975286 Auto Shop Failed Operation 1 NFPA72 14.2.2.2.2 1 13975996 Boys Locker Room Failed Operation 1 NFPA72 14.2.2.2.2 1 13975994 Girls Locker Room Failed Operation 1 NFPA72 14.2.2.2.2 1 13975990 Leadership Bldg Failed Operation 1 NFPA72 14.2.2.2.2 1 13975294 Library Hall East Failed Operation 1 NFPA72 14.2.2.2.2 1 13975293 Library Hall West Failed Operation 1 NFPA72 14.2.2.2.2 1 13975288 NIE Portable Room 603 Failed Operation 1 NFPA72 14.2.2.2.2 1 13975273 Office Failed Operation 1 NFPA72 14.2.2.2.2 1 13975275 Office Hall Failed Operation 1 NFPA72 14.2.2.2.2 1 13975279 Room 209 Failed Operation 1 NFPA72 14.2.2.2.2 13975277 Room 211 1 1 13975992 Team Room Failed Operation 1 NFPA72 14.2.2.2.2 1 13975282 Welding Bldg Failed Operation 1 NFPA72 14.2.2.2.2 1 13975284 Wood Shop Failed Operation 1 NFPA72 14.2.2.2.2 Smoke Detector 13975983 Room 209 1 13975984 Room 209 1 13975987 Room 211 1 13975988 Room 211 1 - Code References p. NFPA72 14.2.2.2.2 System deficiencies shall be corrected. Hue&Cry,Inc. Page 4 of 13 Download Date:05/25/2022 Discrepancy Report Proposed Solutions Report Generated by:BuildingReports.com Building: Gridley High School Control Panel: 1 - Fire-Lite Sensiscan 1000 I The Proposed Solution Report provides a solution Jra each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report.Items listed as T/M are available for repair on a Time and Materials basis. ScanlD Location 'Solution Modei ' .1' ""Cost ; [ E7 I Control Battery 18891963 FACP Investigate PS-12180NB T/M 0 18891964 FACP Left Batt Investigate PS-12180NB T/M 0 Indicating Horn 13975300 200 Wing East SC806A1004 T/M 0 13975298 200 Wing West 34-24 T/M 0 13975296 300 Wing SC806A1004 T/M 0 13975289 400 Wing North Side SC806A1004 T/M 0 13975291 400 Wing West Side 5C806A1004 T/M 0 13975285 Auto Shop SC806A1004 T/M 0 13975997 Boys Locker Room 4040 T/M 0 13975993 Girls Locker Room 4040 T/M ❑ 41245625 Leadership Bldg SC806A1004 T/M 0 13975295 Library Hall SC806A1004 T/M 0 13975995 Outside Locker Room North 31T-115 T/M 0 13975280 Room 209 Outside H12/24K T/M El 13975991 Team Room 4040 T/M ❑ 13975281 Welding Bldg SC806A1004 T/M ❑ 13975283 Wood Shop SC806A1004 T/M ❑ 13975272 portable 603 MT-24R T/M 0 Horn/Strobe 13975287 N/E Portable NS-24MCW TIM 0 41245650 Room 209 P2R T/M ❑ 41245677 Room 211 P2R T/M 0 Initiating Pull Station 41245676 200 Wing East Investigate BG-12 T/M 0 13975299 200 Wing West S464A1045 T/M ❑ 13975297 300 Wing S464A1045 T/M 0 13975290 400 Wing East Investigate S464A1045 T/M 0 13975292 400 Wing West Investigate S464A1045 T/M 0 Hue&Cry,Inc. Page 5 of 13 Download Date:05/25/2022 Proposed Solutions Report 1 Building: Gridley High School Control Panel: 1 - Fire-Lite Sensiscan 1000 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis. ScanlD ,i `t I Location Solution Model#- .'Cost 1iX Initiating Pull Station 13975286 Auto Shop Investigate S46A1045 T/M 0 13975996 Boys Locker Room Investigate 4251-1 125v T/M 0 13975994 Girls Locker Room Investigate 4251-1 125v T/M 0 13975990 Leadership Bldg Investigate S464A1045 T/M 0 13975294 Library Hall East Investigate S464A1045 T/M 0 13975293 Library Hall West Investigate S464A1045 T/M 0 13975288 N/E Portable Room 603 Investigate 2099-9101 T/M 0 13975273 Office Investigate S464A1045 T/M 0 13975275 Office Hall Investigate S46A1045 T/M 0 13975279 Room 209 Investigate BG-12 T/M ❑ 13975277 Room 211 BG-12 T/M ❑ 13975992 Team Room Investigate 4251-1 125v T/M ❑ 13975282 Welding Bldg Investigate S46A1045 T/M ❑ 13975284 Wood Shop Investigate S46A1045 T/M Smoke Detector 13975983 Room 209 DS282 T/M ❑ 13975984 Room 209 DS282 T/M 0 . 13975987 Room 211 DS282 T/M ❑ 13975988 Room 211 DS282 T/M 0 PO#: (none) T/M l Hue&Cry,Inc. Page 6 of 13 Download Date:05/25/2022 Proposed Solutions Report Notes & Recommendations Generated by:BuildingReports.corn Building: Gridley High School The Notes&Recommendations Report details additional inspection notes made by the inspectors during the course of the building inspection. Notes are grouped by Category. General Note Annual fire inspection G/19/2021 19 of the 20 fire pole stations failed to operate Battery in booster panel are dead and have short circuited and panel may be dead needs to be investigated Hue&Cry,Inc. Page 7 of 13 Download Date:05/25/2022 Notes&Recommendations Inspection & Testing Generated by:BuildingReports.com Control Panel: 1 - Fire-Lite Sensiscan Building: Gridley High School 1000 The Inspection& Testing section lists all of the items inspected in your building.Items are grouped by Passed or Failed/Other.Items are listed by Category. Each item includes the services performed, and the time&date at which testing occurred. Device Type 1 Location. 1 Service Time i Date Passed Control Battery 10th Below Connector Cell Room 211 Annual 9:52:21 AM 07/19/2021 Power Supply Battery Room 211 Power Supply Annual 9:52:18 AM 07/19/2021 Control Panel Office Conference Room Annual 12:14:20 PM 07/19/2021 Disconnect Room 211 #14A Annual 12:14:26 PM 07/19/2021 Disconnect Staff Break Room Hall -C/B A2#2 Annual 12:14:23 PM 07/19/2021 Power Supply Room 211 above Ceiling Tile Annual 9:52:07 AM 07/19/2021 Indicating Bell Office Hall Annual 10:02:17 AM 07/19/2021 Initiating Pull Station 100 Wing Outside Annual 4:14:27 PM 07/20/2021 Device Type Location I Service Time,,, i bite Failed/Other Control 1 Battery FACP Tested 8:29:22 AM 07/20/2021 1 Battery FACP Left Batt Tested 8:29:07 AM 07/20/2021 Indicating Horn 200 Wing East Annual 12:15:18 PM 07/19/2021 Horn 200 Wing West Tested 12:15:13 PM 07/19/2021 Horn 300 Wing Tested 12:14:41 PM 07/19/2021 Horn 400 Wing North Side Annual 12:15:01 PM 07/19/2021 Horn 400 Wing West Side Annual 12:15:05 PM 07/19/2021 Horn Auto Shop Annual 12:14:57 PM 07/19/2021 Horn Boys Locker Room Tested 12:15:30 PM 07/19/2021 Horn Girls Locker Room Tested 12:15:24 PM 07/19/2021 Horn Leadership Bldg Tested 12:15:34 PM 07/19/2021 Horn Library Hall Annual 12:15:08 PM 07/19/2021 Horn Outside Locker Room North Tested 12:15:27 PM 07/19/2021 Hue&Cry,Inc. Page 8 of 13 Download Date: 05/25/2022 Inspection&Testing Device Type 1 Location Service Time Date Failed/Other Horn Room 209 Outside Annual 12:14:49 PM 07/19/2021 Horn Team Room Tested 12:15:21 PM 07/19/2021 Horn Welding Bldg Annual 12:14:51 PM 07/19/2021 Horn Wood Shop Annual 12:14:54 PM 07/19/2021 Horn portable 603 Annual 12:14:46 PM 07/19/2021 Horn/Strobe N/E Portable Tested 12:15:37 PM 07/19/2021 Horn/Strobe Room 209 Tested 12:15:39 PM 07/19/2021 Horn/Strobe Room 211 Tested 12:15:43 PM 07/19/2021 Initiating 1 Pull Station 200 Wing East Annual 10:06:57 AM 07/19/2021 Pull Station 200 Wing West Tested 4:14:11 PM 07/20/2021 Pull Station 300 Wing Tested 4:14:08 PM 07/20/2021 1 Pull Station 400 Wing East Annual 10:18:45 AM 07/19/2021 1 Pull Station 400 Wing West Tested 12:16:12 PM 07/19/2021 1 Pull Station Auto Shop Tested 10:45:30 AM 07/19/2021 1 Pull Station Boys Locker Room Tested 10:29:06 AM 07/19/2021 1 Pull Station Girls Locker Room Tested 10:29:29 AM 07/19/2021 1 Pull Station Leadership Bldg Annual 10:39:48 AM 07/19/2021 1 Pull Station Library Hall East Annual 10:17:17 AM 07/19/2021 1 Pull Station Library Hall West Annual 10:16:09 AM 07/19/2021 1 Pull Station N/E Portable Room 603 Annual 10:48:14 AM 07/19/2021 1 Pull Station Office Annual 10:01:49 AM 07/19/2021 1 Pull Station Office Hall Annual 12:15:59 PM 07/19/2021 1 Pull Station Room 209 Annual 10:38:32 AM 07/19/2021 Pull Station Room 211 Tested 12:15:50 PM 07/19/2021 E 1 Pull Station Team Room Tested 10:45:54 AM 07/19/2021 1 Pull Station Welding Bldg Annual 10:41:20 AM 07/19/2021 1 Pull Station Wood Shop Annual 10:43:40 AM 07/19/2021 Smoke Detector Room 209 Tested/Cleaned 3:34:34 PM 07/19/2021 Smoke Detector Room 209 Tested/Cleaned 3:34:37 PM 07/19/2021 Smoke Detector Room 211 Tested/Cleaned 3:34:41 PM 07/19/2021 Smoke Detector Room 211 Tested/Cleaned 3:34:46 PM 07/19/2021 Hue&Cry,Inc. Page 9 of 13 Download Date:05/25/2022 Inspection&Testing Service Summary Generated by:BuildingReports.com Building: Gridley High School The Service Summary section provides an overview of the services performed in this report. Device Type Service Quantity Failed/Other Battery Tested 2 Horn/Strobe Tested 3 Horn Annual 9 Horn Tested 7 Pull Station Annual 11 Pull Station Tested 8 Smoke Detector Tested/Cleaned 4 Total 44 Passed Battery Annual 2 Bell Annual 1 Control Panel Annual 1 Disconnect Annual 2 Power Supply Annual 1 Pull Station Annual 1 Total 8 Grand Total 52 Hue&Cry,Inc. Page 10 of 13 Download Date: 05/25/2022 Service Summary Battery & Power Supply Testing Generated by.BuildingReports.com Building: Gridley High School Control Panel: I - Fire-Lite Sensiscan laao The.Battery&Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems.Items are grouped by Passed or Failed/Other. Rated Rated Post Type Location Ah Volts I Pre Test Test Min Ah Tested Ah Battery Passed Sealed Lead Acid 10th Below Connector Cell 7 12 Room 211 Power Supply Sealed Lead Acid Room 211 Power Supply 7 12 Failed/Other Sealed Lead Acid FACP 18 12 Sealed Lead Acid FACP Left Batt 18 12 Hue&Cry,Inc. Page 11 of 13 Download Date:05/25/2022 Battery&Power Supply Testing Inventory & Warranty Report Generated by:BuildingReports.conz Building: Gridley High School Control Panel: 1 - Fire-Lite Sensiscan 1000 The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. i Device or Type Category % of Inventory l Quantity Battery Control 7.69% 4 Bell Indicating 1.92% 1 Control Panel Control 1.92% 1 Disconnect Control 3.85% 2 Horn Indicating 30.77% 16 Horn/Strobe Indicating 5.77% 3 Power Supply Control 1.92% 1 Pull Station Initiating 38.46% 20 Smoke Detector Initiating 7.69% 4 Type oty Mode!# !Description . Install Date In Service - 5 Years to 10 Years Power-Sonic Battery 1 PS-1270F1 Sealed Lead Acid 10/21/2014 Ultra Tech Battery 1 PS-1270F1 Sealed Lead Acid 10/21/2014 Power-Sonic Battery 2 PS-12180NB Sealed Lead Acid 09/24/2013 In Service -- 10 Years to 15. Years Altronix Power Supply 1 AL300ULXR 07/21/2010 Detection Systems Smoke Detector 4 DS282 Photoelectric 07/21/2010 Fire-Lite Control Panel 1 Sensiscan 1000 07/21/2010 Pull Station 1 BG-10 Dual Action 07/21/2010 Pull Station 3 BG-12 Dual Action 07/21/2010 Honeywell Horn 9 5C806A1004 07/21/2010 Pull Station 8 S464A1045 Single Action 07/21/2010 Pull Station 4 S46A1045 Single Action 07/21/2010 Modtech Disconnect 1 15amp Breaker 07/21/2010 SimplexGrinnell Horn 3 4040 07/21/2010 Hue&Cry,Inc. Page 12 of 13 Download Date:05/25/2022 Inventory&Warranty Report Pull Station 1 2099-9101 Single Action 07/21/2010 (Pull Station 3 4251-1 125v Single Action 07/21/2010 Square D Disconnect 1 20amp Breaker 07/21/2010 System Sensor Horn 1 H12/24K 07/21/2010 Horn/Strobe 2 P2R 07/21/2010 Unknown Bell 1 12" 07/21/2010 Wheelock Horn 1 31 T-115 07/21/2010 Horn 1 34-24 07/21/2010 Horn 1 MT-24R 07/21/2010 Horn/Strobe 1 NS-24MCW 07/21/2010 Hue&Cry,Inc. Page 13 of 13 Download Date:05/25/2022 Inventory&Warranty Report