HomeMy WebLinkAboutCSA-0004 047-640-018 CF Pump 7.2022 SDuurh m Pump&Irrigation WM.P.WILSON&SONS Invoice
CL#271327 Number: 0207478-IN
Main Office: Woodland Branch:
Durham Pump,Inc. Wm.P.Wilson&Sons Date: 7/26/2022
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order/Date: 0059573 7/20/2022
Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you! ICustomer#: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#128-WILDFLOWER EST.
7 COUNTY CENTER DR HERFORD DR
ATTN:MARGE CHICO,CA 95973
OROVILLE,CA 95965
Confirm To: JOHN GADDIE Job Name: CSA#128 Wildflower Estates
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
•
Item Code Description Unit WH Qty Ordered / Shipped / B.O. Price Amount
7/6/2022 COMPLETE BIANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
IPMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
CS Pr- aaa y O /7-GYn-of g
SPECIAL ORDER ITEMS: Special Orders(items not normally stocked)are non-returnable unless they can Taxable Amount: 0.00
be resold to others or are accepted for return by our vendor.Them will be a minimum restock fee of Non-Taxable Amount: 200.00
15%of the item value,or amount charged by vendor,whichever is higher,plus any applicable freight
incurred.All special sale/close-out item sales are final,no returns.Thank you Net Invoice: 200.00
Less Discount: 0.00
Sales Tax: 0.00
Signature N/q Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Durham ' '. Pimp PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891 .4821 CSA #128 - Wildflower Estates
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/6/2022
Motor Mfg: Sta-Rite HP: 1 Meter #: 14R432
RPM 3450 Volts 240 Phase 3 Rated Amps:
TM 80 Yes No Serial #
PG &E Acct. # Other:
Panel Mfg: NEMA Size:
Type: X/L P/W Other: Date Code: 10/90
Pump Mfg: Sta-Rite Serial#:
Non-Running Checks: Pump Model Type
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
na Fuses - Replace if Necessary Replaced Size: 20 Amp Breaker
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise ° Ok/see comments Pressure tank: Air-E-Tainer AT-266
Excessive or Unusual Vibration _" Ok/see comments Tank condition: Good
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other: PRESS. SWITCH
Amperage: Expected: 9.8 Pressure setting:
Actual: B 9 Y 9.1 R 0 Average: 8.25
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
GPS:
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's1128 Wildflower Est1128 Reports
Durham y'. now PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#128 -Wildflower Estates
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/6/2022
•
Motor Mfg: Franklin HP: 25 Meter#: 1006873268
RPM 3450 Volts 240 Phase 3 Rated Amps: 60
TM 80 Yes No Serial# N/A
PG &E Acct. # Other:
Panel Mfg: Furnas NEMA Size: 3
Type: X X/L P/W Other:
Pump Mfg: 25 HP Sub Serial#:
Non-Running Checks: Pump Model Manufacturer Franklin
na Lubricant Levels -Service and Change if Necessary Discharge
na Oiler Unit and/or Packing
Electrical Leads &Connections - Repair and Tighten as Necessary
• Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
• Fuses - Replace if Necessary Replaced Size: 100 Amp
• Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: U's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank: OK
Excessive or Unusual Vibration Ok/see comments Tank condition: Good
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 67 Pressure setting: PRESS SWITCH
Actual: L 1 65.8 L2 75.2 L3 68.8 Average: 69.93
Overload I I Underload I v' Even Load
Bowl Adiustment: N/A Yes No
Comments:
GPS:
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\128 Wildflower Est\128 Reports