HomeMy WebLinkAboutCSA-0006 047-750-061 CF Pump 7.2022 c", Durham Pump&Irrigation WM.P.WILSON&SONS Invoice
www.do,hampomp..om
CL#271327 Number: 0207476-IN
Main Office: Woodland Branch:
Durham Pump,Inc. Wm.P.Wilson&Sons Date: 7/26/2022
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order/Date: 0059571 7/20/2022
Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you! I
Customer#: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#158-ISHI VALLEY
7 COUNTY CENTER DR TULIYANI DRIVE
ATTN:MARGE CHICO,CA 95973
OROVILLE,CA 95965
Confirm To: JOHN GADDIE Job Name: CSA#158 Ishi Valley
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
Item Code Description Unit WH Qty Ordered / Shipped I B.O. Price Amount
07/06/2022 COMPLETE BIANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
/PMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
L5A -000b 697_7co-orel
SPECIAL ORDER ITEMS: Special Orders(items not normally stocked)are non-returnable unless they can Taxable Amount: 0.00
be resold to others or are accepted for return by our vendor.There will be a minimum restock fee of Non-Taxable Amount: 200.00
15%of the item value,or amount charged by vendor,whichever is higher,plus any applicable freight
incurred.All special sale/close-out item sales are final,no returns.Thank you. Net Invoice: 200.00
Less Discount: 0.00
Sales Tax: 0.00
Signature N/A Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Durham3 ')Punip PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891 .4821 CSA#158 Ishi Valley
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/6/22
Motor Mfg: Franklin HP: 25 Meter #: 1006908237
RPM 3450 Volts 240 Phase 3 Rated Amps: 75
TM 80 Yes No Serial #
PG &E Acct. # Other:
Panel Mfg: Furnas NEMA Size: 3
Type: X/L P/W Other:
Discharge Mfg: Steel 6°' Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: TR9OR
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
° Excessive or Unusual Noise Ok
1 Excessive or Unusual Vibration Ok
Control Devices: X H.O.A. X Start Switch Time Clock
Frost Start Time Delay Other: Pressure Switch
Amperage: Expected: 65
Actual: L 9: 68.3 L2: 76.9 L3: 62.4 Average: 69.2
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
Slightly overloaded with uneven load but within service factor
Gate is falling apart, needs to be repaired or replaced.
NO CHANGE
GPS: 39°48'32.57"N 121 °53'38.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's\158 Ishi Valley1158 Reports
'�fallt PIS PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#158 Ishi Valley
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/6/22
Motor Mfg: Franklin HP: 1 Meter#: 1006908237
RPM 3450 Volts 240 Phase 1 Rated Amps: 9.8
TM 80fYes v No Serial#
PG &E Acct. # Other:
Panel Mfg: Franklin control box NEMA Size:
Type: v X/L P/W Date code
Discharge Mfg: 1 1/4 Serial#:
Non-Running Checks: Tank Model WX-302 Manufacturer Well-X-Trol
na Lubricant Levels -Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections- Repair and Tighten as Necessary
Incoming Idle Voltage: nW/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: N/A
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: Less than 1 Meg O's to ground
Excessive or Unusual Noise Ok
Excessive or Unusual Vibration ' Ok
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other: Pres. Sw. 30-50
Amperage: Expected:
Actual:Red: 4.1 Yellow: 13.3 Black: 12.9 Average: 10.1
Overload Underload Even Load
Bowl Adiustment: N/A Yes No
Comments:
Fence enclosure falling in on all 4 sides, needs repair- NO CHANGE
GPS: 39°48'32.57"N 121°53'38.30"W
•
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.