7/7/2022 COMPLETE BI-ANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
IPMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
csA--vavi °HI-(.7o-ac
SPECIAL ORDER ITEMS: Special Orders(items not normally stocked)are non-returnable unless they can Taxable Amount: 0.00
be resold to others or are accepted for return by our vendor.There will be a minimum restock fee of Non-Taxable Amount: 200.00
15%of the item value,or amount charged by vendor,whichever is higher,plus any applicable freight
incurred.All special sale/close-out item sales are final,no returns.Thank you Net Invoice: 200.00
Less Discount: 0.00
Sales Tax: 0.00
Signature N/q Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Dwiam )Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891 .4821 CSA#169 Pheasant Landing
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/7/22
Motor Mfg: Newman HP: 40 Meter #: 1005576060
RPM 1770 Volts 460 Phase 3 Rated Amps: 59
TM 80 Yes No Serial # 326TPH/DD27K2PM
PG &E Acct. # Other:
Panel Mfg: Cuttler Hammer NEMA Size: 21/2
Type: ® X/L P/W Other:
Pump Mfg: Peerless 6" Serial#:
Non-Running Checks: Pump Model Manufacturer Newman
Lubricant Levels - Service and Change if Necessary
Oiler Unit and/or Packing
V Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: 100A MCP
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise ' Ok/see comments Pressure tank: n/a
Excessive or Unusual Vibration ✓ Ok/see comments Tank condition: n/a
Control Devices: v H.O.A. Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 59 Pressure setting: PRESS SWITCH
Actual: R 51 .3 Y 50.3 B 44.8 Average: 48.8
Overload Underload' Even Load
Bowl Adjustment: N/A Yes No
Comments:
NO JOCKY PUMP
No Backspin protection, needs to be addressed
Idle voltage is a little high at around 495V. System holding 40 psi pressure.
Gate is broken, Fence Broken, hard to access
GPS: 39°47'57.43"N 121 °53'5.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:1Pump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's1169 Pheasant Landing1169 Reports
Dhan . PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#169 Pheasant Landing •
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/7/2022
Motor Mfg: Franklin Motor HP: 1.5hp Meter#: 34422R
RPM 3450 Volts 460 Phase 3 Rated Amps: 3
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: NEMA Size:
Type: X/L P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Type: Submersible
Lubricant Levels- Service and Change if Necessary
Oiler Unit and/or Packing
Electrical Leads & Connections- Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: 15 amp
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: 120,000 D's to ground
Excessive or Unusual Noise Ok Pressure tank: Clayton Mark 86 gal
Excessive or Unusual Vibration Ok Condition:
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other: Pres. Sw.
Amperage: Expected: 3
Actual: L1: L2: L3: Average: 0
Overload Underload Even Load
Bowl Adjustment: Yes No
Comments:
i Is n er in well
GPS:
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\169 Pheasant Landing\169 Reports