Loading...
HomeMy WebLinkAboutCSA-0009 047-670-058 CF Pump 7.2022 6DurhPump&Irrigation WM.P.WILSON&SONS Invoice CL#271327 Number: 0207484-I N Main Office: Woodland Branch: Durham Pump,Inc. Wm.P.Wilson&Sons Date: 7/26/2022 2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695 530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1 Order I Date: 0059579 7/20/2022 Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you! ICustomer#: 01-0005315 Salesperson: JOHN RHEIN Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#169-PHEASANT LANDING 7 COUNTY CENTER DR. AGUSTA WAY ATTN:MARGE CHICO,CA 95973 OROVILLE,CA 95965 Confirm To: JOHN GADDIE Job Name: CSA#169 Pheasant Landing Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH Item Code Description Unit WH Qty Ordered / Shipped / B.O. Price Amount 7/7/2022 COMPLETE BI-ANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED. IPMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00 csA--vavi °HI-(.7o-ac SPECIAL ORDER ITEMS: Special Orders(items not normally stocked)are non-returnable unless they can Taxable Amount: 0.00 be resold to others or are accepted for return by our vendor.There will be a minimum restock fee of Non-Taxable Amount: 200.00 15%of the item value,or amount charged by vendor,whichever is higher,plus any applicable freight incurred.All special sale/close-out item sales are final,no returns.Thank you Net Invoice: 200.00 Less Discount: 0.00 Sales Tax: 0.00 Signature N/q Invoice Total: 200.00 Less Deposit: 0.00 Invoice Balance: 200.00 Dwiam )Pump PUMP CHECK REPORT 2313 Durham-Dayton Hwy. Durham, CA 95938 530.891 .4821 CSA#169 Pheasant Landing CUSTOMER NAME: Butte County Fire Dept. DATE: 7/7/22 Motor Mfg: Newman HP: 40 Meter #: 1005576060 RPM 1770 Volts 460 Phase 3 Rated Amps: 59 TM 80 Yes No Serial # 326TPH/DD27K2PM PG &E Acct. # Other: Panel Mfg: Cuttler Hammer NEMA Size: 21/2 Type: ® X/L P/W Other: Pump Mfg: Peerless 6" Serial#: Non-Running Checks: Pump Model Manufacturer Newman Lubricant Levels - Service and Change if Necessary Oiler Unit and/or Packing V Electrical Leads & Connections - Repair and Tighten as Necessary Incoming Idle Voltage: W/I Acceptable Limits Unacceptable Fuses - Replace if Necessary Replaced Size: 100A MCP Perform General Clean-Up of Electrical Panel and Motor Running Checks: Motor winding resistance: Excessive or Unusual Noise ' Ok/see comments Pressure tank: n/a Excessive or Unusual Vibration ✓ Ok/see comments Tank condition: n/a Control Devices: v H.O.A. Start Switch Time Clock Frost Start Time Delay Other: Amperage: Expected: 59 Pressure setting: PRESS SWITCH Actual: R 51 .3 Y 50.3 B 44.8 Average: 48.8 Overload Underload' Even Load Bowl Adjustment: N/A Yes No Comments: NO JOCKY PUMP No Backspin protection, needs to be addressed Idle voltage is a little high at around 495V. System holding 40 psi pressure. Gate is broken, Fence Broken, hard to access GPS: 39°47'57.43"N 121 °53'5.30"W The above readings reflect the site and pump conditions at the time of inspection. This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system. S:1Pump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's1169 Pheasant Landing1169 Reports Dhan . PUMP CHECK REPORT 2313 Durham-Dayton Hwy. Durham, CA 95938 530.891.4821 CSA#169 Pheasant Landing • CUSTOMER NAME: Butte County Fire Dept. DATE: 7/7/2022 Motor Mfg: Franklin Motor HP: 1.5hp Meter#: 34422R RPM 3450 Volts 460 Phase 3 Rated Amps: 3 TM 80 Yes No Serial# PG &E Acct. # Other: Panel Mfg: NEMA Size: Type: X/L P/W Other: Pump Mfg: Serial#: Non-Running Checks: Pump Model Type: Submersible Lubricant Levels- Service and Change if Necessary Oiler Unit and/or Packing Electrical Leads & Connections- Repair and Tighten as Necessary Incoming Idle Voltage: W/I Acceptable Limits Unacceptable Fuses - Replace if Necessary Replaced Size: 15 amp Perform General Clean-Up of Electrical Panel and Motor Running Checks: Motor winding resistance: 120,000 D's to ground Excessive or Unusual Noise Ok Pressure tank: Clayton Mark 86 gal Excessive or Unusual Vibration Ok Condition: Control Devices: H.O.A. Start Switch Time Clock Frost Start Time Delay Other: Pres. Sw. Amperage: Expected: 3 Actual: L1: L2: L3: Average: 0 Overload Underload Even Load Bowl Adjustment: Yes No Comments: i Is n er in well GPS: The above readings reflect the site and pump conditions at the time of inspection. This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system. S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\169 Pheasant Landing\169 Reports