Durham Pump,Inc. Wm. P.Wilson&Sons Date: 7/26/2022
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order/Date: 0059578 7/20/2022
Please Remit All Payments to: Durham Pump, PO Box 60,Durham, CA 95938 Thank you!
Customer#: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#172-AUTUMN PARK
7 COUNTY CENTER DR. OFF GARNER LANE
ATTN: MARGE CHICO,CA 95973
OROVILLE,CA 95965
Confirm To: JOHN GADDIE Job Name: CSA#172 Autumn Park
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
Item Code Description Unit WH Qty Ordered / Shipped / B.O. Price Amount
7/7/2022 COMPLETE BI-ANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
/PMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
654 -06/ 0 4%°—"ZI
Gy��
SPECIAL ORDER ITEMS: Special Orders(items not normally stocked)are non-returnable unless they can Taxable Amount: 0.00
be resold to others or are accepted for return by our vendor.There will be a minimum restock fee of Non-Taxable Amount: 200.00
15%of the item value,or amount charged by vendor,whichever is higher,plus any applicable freight
incurred. All special sale/close-out item sales are final,no returns. Thank you. Net Invoice: 200.00
Less Discount: 0.00
Sales Tax: 0.00
Signature N /A Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Di// n �''. Pow PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#172 Autumn Park Subdivision
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/7/22
Motor Mfg: Franklin HP: 2 Meter#:
RPM Volts 240 Phase 1 Rated Amps:
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: Franklin control box NEMA Size:
Type: << X/L P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
✓ Fuses- Replace if Necessary Replaced Size: 15 amp
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise / Ok
• Excessive or Unusual Vibration Ok
• Control Devices: X H.O.A. Start Switch Time Clock
n Frost Start Time Delay Other: Press. Sw. 40-60
Amperage: Expected: 9.8
Actual:Red: 2.6 Yellow: 11.3 Black: 11.3 Average: 8.4
Overload Underload -' Even Load
Bowl Adjustment: N/A Yes No
Comments:
GPS: 39°48'7.51"N 121°53'40.31"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions,nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\172 Autumn Park\172 Reports
. Aim PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#172 Autumn Park Subdivision
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/7/22
Motor Mfg: Franklin HP: 25 Meter#: X11162
RPM 3450 Volts 460 Phase 3 Rated Amps: 75max
TM 801-7Yes nNo Serial#
PG &E Acct. # Other:
Panel Mfg: Furnas NEMA Size: 3
Type: X/L n P/W Other:
Discharge Mfg: Fabricated steel 6" Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
- Electrical Leads & Connections- Repair and Tighten as Necessary
Incoming Idle Voltage: nW/I Acceptable Limits Unacceptable
Fuses- Replace if Necessary Replaced Size: 100 amp MCP
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: 1.2 Megs to ground
Excessive or Unusual Noise nOk
Excessive or Unusual Vibration Ok
(Control Devices: X H.O.A. X Start Switch Time Clock
Frost Start nTime Delay Other: Pres. Sw.
Amperage: Expected: 75.0 max
Actual: L1: 75 L2: 74.5 L3: 75.6 Average: 75.03
Overload Underload Even Load
Bowl Adjustment: N/A Yes nNo
Comments:
Idle voltage back down to around 485-487V
Gate broken. Fence broken, hard to open.
Lock changed, but left unlocked
GPS: 39°48'7.51"N 121°53'40.31"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions,nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\172 Autumn Park\172 Reports