HomeMy WebLinkAboutCSA21-0001 047-320-062 CF Pump 7.2022 c)Durham Pump&Irrigation WM.P.WILSON&SONS Invoice
a www.durhampump.mm ,
CL#271327 Number: 0207485-IN
Main Office: Woodland Branch:
Durham Pump,Inc. Wm.P.Wilson&Sons Date: 7/26/2022
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order/Date: 0059580 7/20/2022
Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you! 1
Customer#: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#165-JUSTIN MANOR
7 COUNTY CENTER DR. FELICIDAD LANE
ATTN:MARGE CHICO,CA 95973
OROVILLE,CA 95965
Confirm To: JOHN GADDIE Job Name: CSA#165 Justin Manor
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
Item Code Description Unit WH Qty Ordered I Shipped I B.O. Price Amount
7/7/2022 COMPLETE BIANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
/PMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
c $ Z1--000I 697-3Zo-062_
SPECIAL ORDER ITEMS: Special Orders(items not normally stocked)am non-returnable unless they can Taxable Amount: 0.00
be resold to others or are accepted for return by our vendor.There will be a minimum restock fee of Non-Taxable Amount: 200.00
15%of the item value,or amount charged by vendor,whichever is higher,plus any applicable freight
incurred.All special sale/close-out item sales are final,no returns.Thank you. Net Invoice: 200.00
Less Discount: 0.00
Sales Tax: 0.00
Signature N/q Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
DurhainC6PignP PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#165 -Justin Manor
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/7/2022
Motor Mfg: Franklin HP: 1/2 Meter#:
RPM 3450 Volts 240 Phase 1 Rated Amps: 6
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: Franklin 1/2 HP Control Box NEMA Size: n/a
Type:FIX/L nP/W Other: 119 gal. Champion bladder tank
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Type Submersible
na Lubricant Levels-Service and Change if Necessary
na Oiler Unit and/or Packing
•
Electrical Leads & Connections- Repair and Tighten as Necessary
Incoming Idle Voltage: nW/I Acceptable Limits []Unacceptable
riFuses- Replace if Necessary Replaced Size:
• Perform General Clean-Up of Electrical Panel and Motor
Runnina Checks: Motor winding resistance: O's to ground
• Excessive or Unusual Noise nOk/see comments Pressure tank: 119 gal Champion
Excessive or Unusual Vibration Ok/see comments Tank condition: ok
• Control Devices: H.O.A. Start Switch []Time Clock
[]Frost Start Time Delay Other: PRESS. SWITCH
Amperage: Expected: 6 Pressure setting:
Actual: R 1.3 Y 5.2 B 4.6 Average: 3.7
Overload Underload • Even Load
Bowl Adiustment: N/A Yes nNo
Comments:
Pump is now running. Needs pressure switches.
GPS: 39°48'49.56"N 121° 54'40.91"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:1Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's1165 Justin Manor1165 Reports
•
Diiftant )PUmp PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891 .4821 CSA #165 - Justin Manor
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/7/2022
Motor Mfg: Franklin HP: 25 Meter #: 1006873938
RPM 3450 Volts 480 Phase 3 Rated Amps:
TM 80 Yes No Serial #
PG &E Acct. # Other:
Panel Mfg: Furnas NEMA Size: 3
Type: X X/L P/W Other:
Pump Mfg: 25 HP Sub Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels - Service and Change if Necessary Discharge 6" Fab
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: 200 Amp
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: O's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank:
Excessive or Unusual Vibration Ok/see comments Tank condition: Good, 34 psi
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 65 Pressure setting: PRESS SWITCH
Actual: L l 58.3 L2 66.7 L3 59.4 Average: 61 .47
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
Pump is now running
GPS: 39°48' 49.56"N 121 ° 54' 40.91 "W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's\165 Justin Manor\165 Reports