HomeMy WebLinkAboutCSA-0005 040-570-015 CF Pump 7.2022 ?,6i;iu ham Pump&Irrigation WM.P.WILSON&SONS Invoice
CL#271327 Number: 0207480-IN
Main Office: Woodland Branch:
Durham Pump,Inc. Wm.P.Wilson&Sons Date: 7/26/2022
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order/Date: 0059575 7/20/2022
Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you! , Customer#: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT.MAIN Ship To: CSA#137 DURHAM DAYTON INDUST
7 COUNTY CENTER DR. PEPSI WAY
ATTN:MARGE DURHAM,CA 95938
OROVILLE,CA 95965
Confirm To: JOHN GADDIE Job Name: CSA#137 Durham Dayton Indust
•
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
Item Code Description Unit WH Qty Ordered I Shipped I B.O. Price Amount
7/7/2022 COMPLETE BIANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
/PMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
CSC -�uoS' CLjo 570—a5--
SPECIAL ORDER ITEMS: Special Orders(items not normally stocked)are non-retumable unless they can Taxable Amount: 0.00
be resold to others or are accepted for return by our vendor.There will be a minimum restock fee of Non-Taxable Amount: 200.00
15%of the item value,or amount charged by vendor,whichever is higher,plus any applicable freight
incurred.All special sale/close-out item sales are final,no returns.Thank you. Net Invoice: 200.00
Less Discount: 0.00
Sales Tax: 0.00
Signature N/A Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Durham ' '. Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891 .4821 CSA#137 Durham Dayton Industrial Partners
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/7/22
Motor Mfg: US motors HP: 100 Meter #: 1005520819
RPM 1775 Volts 460 Phase 3 Rated Amps: 120
TM 80 Yes No Serial # TO7T059ROOSR-12
PG &E Acct. # Other:
Panel Mfg: Delta NEMA Size: 3
Type: X/L P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Manufacturer
Lubricant Levels - Service and Change if Necessary
Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: 150A MCP
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise Ok
v Excessive or Unusual Vibration Ok
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other: Pressure Switch
Amperage: Expected: 120.5
Actual: Li: 120 L2: 114 L3: 125 Average: 119.7
Overload Underload Even Load
Bowl Adjustment: Yes X No
Comments:
Slightly uneven load, similar to previous inspection.
GPS: 39°38'41 .08"N 121 °43'18.99"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's\137 Durham Dayton Ind Partn\137 Reports
PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#137 Durham Dayton Industrial Partners
CUSTOMER NAME: Butte County fire Dept DATE: 7/7/22
Motor Mfg: Franklin HP: 3 Meter#:
RPM 3450 Volts 460 Phase 3 Rated Amps: 4.8
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: IEC NEMA Size: ?
Type: X/L P/W Other:
Pump Mfg: SUB Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels -Service and Change if Necessary Discharge
na Oiler Unit and/or Packing
• Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
• Fuses - Replace if Necessary Replaced Size: TSR10R
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: O's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank: OK
Excessive or Unusual Vibration Ok/see comments Tank condition: good
Control Devices: r H.O.A. / Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 4.8 Pressure setting:
Actual: L1: 6 L2: 5.2 L3: 5.4 Average: 5.533
Overload Underload / Even Load
Bowl Adjustment: N/A Yes No
Comments:
Voltage stabilizer on PG&E Panel is blown out
GPS:
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\137 Durham Dayton Ind Partn\137 Reports