HomeMy WebLinkAboutCSA-0011 047-740-019 CF Pump 7.2022 .ii
",'Dui Pump&Irrigation WI&P.WILSON&SONS Invoice
CL#271327 Number: 0207482-IN
Main Office: Woodland Branch:
Durham Pump,Inc. Wm.P.Wilson&Sons Date: 7/26/2022
2313 Durham-Dayton Hwy,Durham,CA 95938 202 Kentucky Ave,Woodland,CA 95695
530.891.4821 530-891.0613 Fax 530.662.8654 530.662.5797 Fax Page: 1
Order/Date: 0059577 7/20/2022
Please Remit All Payments to: Durham Pump,PO Box 60,Durham,CA 95938 Thank you! Customer#: 01-0005315
Salesperson: JOHN RHEIN
Sold To: BUTTE COUNTY FIRE DEPT-MAIN Ship To: CSA#176 PHEASANT LANDING PH3
7 COUNTY CENTER DR. GUNTREN RD.
ATTN:MARGE CHICO,CA 95973
OROVILLE,CA 95965
Confirm To: JOHN GADDIE Job Name: CSA#176 Pheasant Landing Ph3
•
Customer P.O. Ship VIA: F.O.B. Terms: NET 10TH
Item Code Description Unit WH Qty Ordered / Shipped / B.O. Price Amount
7/6/2022 COMPLETE BIANNUAL SERVICE AND MAINTENANCE CHECKS.REPORTS ENCLOSED.
/PMAINT PUMP SERVICE CONTRACT LABOR 0.00 200.00
•
GS/k —no\1 7-7`ft CIC1
SPECIAL ORDER ITEMS: Special Orders(items not normally stocked)are non-returnable unless they can Taxable Amount: 0.00
be resold to others or are accepted for return by our vendor.There will be a minimum restock fee of Non-Taxable Amount: 200.00
15%of the item value,or amount charged by vendor,whichever is higher,plus any applicable freight
incurred.All special sale/close-out item sales are final,no returns. Thank you. Net Invoice: 200.00
Less Discount: 0.00
Sales
Signature
N/A Invoice Total: 200.00
Less Deposit: 0.00
Invoice Balance: 200.00
Durham3Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891 .4821 CSA #176 - Pheasant Landing Ph. 3
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/6/2022
Motor Mfg: Franklin HP: 1 .5 Meter #:
RPM 3450 Volts 460 Phase 3 Rated Amps: 2.5
TM 80 Yes No Serial #
PG &E Acct. # Other:
Panel Mfg: NEMA Size:
Type: X X/L l P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Type
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: CMR-6
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: Q's to ground
Excessive or Unusual Noise / Ok/see comments Pressure tank: AP-80
Excessive or Unusual Vibration Ok/see comments Tank condition: ok
Control Devices: H.O.A. Start Switch Time Clock
Frost Start ,Time Delay Other: PRESS. SWITCH
Amperage: Expected: 2.5 Pressure setting:
Actual: R 3.3 Y 3.3 B 3.3 Average: 3.3
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
GPS: 39° 48' 49.58"N 121 ° 47' 40.91"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:1Pump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's1176 Pheasant Landing 3\176 Reports
Dwhain : Pip PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#176 - Pheasant Landing Ph. 3
CUSTOMER NAME: Butte County Fire Dept. DATE: 7/6/2022
Motor Mfg: Franklin HP: 15 Meter#: 1006782900
RPM Volts 460 Phase 3 Rated Amps: 37.5
TM 80fYes fNo Serial#
PG &E Acct. # Other: Pump Date Code: 07/01
Panel Mfg: Myers NEMA Size:
Type: X/L P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels -Service and Change if Necessary Discharge
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: 60 Amp
piPerform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: O's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank: Bad
Excessive or Unusual Vibration Ok/see comments Tank condition:
Control Devices: n H.O.A. Start Switch Time Clock
TiFrost Start Time Delay Other:
Amperage: Expected: 37.5 Pressure setting:
Actual: L1 34.3 L2 38.8 L3 36.3 Average: 36.47
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
Incoming voltage is 490V,492V&490V
GPS: 39°48' 49.58"N 121°47'40.91"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS& INSPECTIONS\Cal Fire CSA's\176 Pheasant Landing 3\176 Reports