ANNUAL FIRE ALARM TEST & INSPECTION
FEATHER FALLS CASINO
3 ALVERDA DR
OROVILLE, CA. 95966
11/25/2015
SimplexGrinnell
4650 Beloit Drive
Sacramento, CA 95838
916-283-0300
•
ISIMPleXGrinnell BE SAFE
4650 Beloit Drive, Sacramento CA 95838— (916) 283-0300 — (916) 920-2241
ALARM & DETECTION EQUIPMENT TEST REPORT
Technician #1 CHRIS JAMES Technician #2 0
Cell Phone# 530-207-7582 Cell Phone# 0
November 25, 2015
Customer Name: Property address: (if different)
FEATHER FALLS CASINO 3 ALVERDA DR
3 ALVERDA DR OROVILLE, CA. 95966
OROVILLE, CA. 95966 SR# 33263094
Contact Information: Monitoring Information:
Name: TROY Central Station: CERTIFIED SYSTEf
Phone: 530-533-3885 Acct#: 8099046
Fax: - Phone: 800-473-5244
Time of Test
Operator#& Name:
Control Panel Status Before Test:
Panel Type: FIRELITE Model: MS-9200
Yes No Notes:
Is Power Light On? X
Does the Panel Indicate Normal Condition? X
Is the panel in a Trouble Condition?
Are all Indicating Lamp Bulbs in Operating Order? X
Does the Silence Switch Operate? X
Do the Batteries indicate they are Properly Charged? X
Type Pass Fail Amp/VIt Date
Battery#1 SEALED X 7AH 12V Jan-11
Battery#2 SEALED X 7AH 12V Jan-11
Comments:
Page 2 of 6
•
SimplexGrinnell BE SAFE.
4650 Beloit Drive,Sacramento CA 95838— (916)283-0300 —(916)920-2241
25-Nov-15
FEATHER FALLS CASINO
3 ALVERDA DR
OROVILLE, CA. 95966
Device Floor Zone Alarm Trouble Location Note:
MAIN CASINO
TAMPER 2 M-24 Pass NA 2ND FLR TAMPER
SMOKE DETECT. 2 D-07 Pass NA SURVEILLANCE ROOM
WATER FLOW 2 M-19 Pass NA DRY RISER
LOW PRESSURE 2 M-20 Pass NA AIR REGULATOR
SMOKE DETECT. 2 D-08 Pass NA ELEV. LOBBY 2ND. FLR
SMOKE DETECT. 2 D-09 Pass NA ELEV. SERV.2ND FLR
PULL STATION 1 M-01 Pass NA MAIN LOBBY ENTRY
PULL STATION 1 M-02 Pass NA MAIN LOBBY ENTRY
PULL STATION 1 M-03 Pass NA NORTH ENTRY
PULL STATION 1 M-04 Pass NA NORTH ENTRY
PULL STATION 1 M-05 Pass NA WEST EXIT
PULL STATION 1 M-06 Pass NA NORTH STAIRWAY
PULL STATION 1 M-33 Pass NA SECURITY BOOTH
SMOKE DETECT. 1 D-10 Pass NA LOBBY ELEC. RM. (ELEV.)
SMOKE DETECT. 1 D-11 Pass NA ELEV. LOBBY 1ST FLR
SMOKE DETECT. 1 D-12 Pass NA ELEV. SERV. 1ST FLR
ANSUL 1 M-21 Pass NA KITCHEN ANSUL STOVES
ANSUL 1 M-22 Pass NA KITCHEN ANSUL FRYERS
ANSUL 1 M-23 Pass NA KITCHEN ANSUL OVENS
HEAT 1 M-15 Pass NA LOBBY ELEC. RM.
SMOKE DETECT. LL D-14 Pass NA SERVICE ELEC. RM
SMOKE DETECT. LL D-13 Pass NA ELEV. SERV. L.L.
PULL STATION LL M-35 Pass NA S.W. BASEMENT
HEAT LL M-16 Pass NA BASEMENT S.W.ELEC.
SMOKE DETECT. LL D-03 Pass NA MAIN ELEC. RM.
SMOKE DETECT. LL D-02 Pass NA MAIN ELEC. RM.
SMOKE DETECT. LL D-01 Pass NA MAIN ELEC. RM.
TAMPER NA M-18 Pass NA PIV TAMPER
TAMPER NA M-18 Pass NA BASEMENT WET SYSTEM BUTTERFLY
WATER FLOW NA M-17 Pass NA WET SYSTEM
TAMPER NA M-38 Pass NA OLD CASINO
WATER FLOW NA M-37 Pass NA OLD CASINO
SMOKE DETECT. 1 D-16 Pass NA 1ST BREWERY ELEVATOR LOBBY Note 1
SMOKE DETECT. 2 D-17 Pass NA 2ND BREWERY ELEVATOR LOBBY Note 5
SMOKE DETECT. 1 D-19 Pass NA BREWERY ELEV ROOM
HEAT DETECT, 1 M-54 Pass NA BREWERY ELEV ROOM
ANSUL 1 M-43 Pass NA BREWERY PIZZA
ANSUL 1 M-44 Pass NA STOVE GRILL
ANSUL 1 M-45 Pass NA BREW SMOKER ANSUL
TROUBLE B2 M-08 Pass NA TRBL GARAGE
ALARM B2 M-07 Pass NA SUPERVISORY GARAGE
SimplexGrinnell BE SAFE.
4650 Beloit Drive,Sacramento CA 95838— (916)283-0300 —(916)920-2241
25-Nov-15
FEATHER FALLS CASINO
3 ALVERDA DR
OROVILLE, CA. 95966
Device Floor Zone Alarm Trouble Location Note:
PWR SPLY 2 1 M-52 Pass NA HOUSEKPG CLOSET BY LUCKY ZONE
PWR SPLY 1 1 M-53 Pass NA HOUSEKPG CLOSET BY LUCKY ZONE
SMOKE DETECT. 1 D-15 Pass NA HOUSEKPG CLOSET BY LUCKY ZONE
SMOKE DETECT. 1 D-21 Pass NA PED LINK DOOR
SMOKE DETECT. 1 D 20 Pass NA PED LINK DOOR
PARKING GARAGE SIMPLEX PANEL (2) 12 ah batteries
PULL STATION P3 Pass NA GARAGE P3 LEVEL S. STAIRWELL
PULL STATION P2 Pass NA GARAGE P2 LEVEL S. STAIRWELL
PULL STATION P1 Pass NA GARAGE P1 LEVEL S. STAIRWELL
PULL STATION B1 Pass NA GARAGE B1 LEVEL S. STAIRWELL
PULL STATION B2 Pass NA GARAGE B2 LEVEL S. STAIRWELL
HEAT DETECTOR P2 ID NET1' Pass NA GARAGE P2 LEVEL ELEV. LOBBY
HEAT DETECTOR P1 ID NET1( Pass NA GARAGE P1 LEVEL ELEV. LOBBY
HEAT DETECTOR B2 ID NET8 Pass NA B2 GARAGE LOBBY HEAT
SMOKE DETECTR B2 ID NET 3 Pass NA B2 CONTROL ROOM SMOKE
HEAT DETECTOR B1 ID NET 9 Pass NA GARAGE B1 ELEV LOBBY
HEAT DETECTOR P3 ID NET1 Pass NA GARAGE P3 LEVEL ELEV. LOBBY
SMOKE DETECTR B2 Pass NA ABOVE FACP
PULL STATION P3 Pass NA P3 NORTH STAIRWELL
PULL STATION P2 Pass NA P2 NORTH STAIRWELL
PULL STATION P1 Pass NA P1 NORTH STAIRWELL
PULL STATION B1 Pass NA B1 NORTH STAIRWELL
PULL STATION B2 Pass NA B2 NORTH STAIRWELL
PIV Pass NA PIV
•
SIMPleXerinnell BE SAFE
4650 Beloit Drive, Sacramento CA 95838— (916) 283-0300 — (916)920-2241
Deficiency Report
Date: 11/25/2015
Customer: FEATHER FALLS CASINO
Address 3 ALVERDA DR
City, State OROVILLE, CA. 95966
SR # 33263094
Contact TROY 530-533-3885
Were Do Repairs
Repairs need to be
Made Quoted
Yes/No Yes/No
Panel discription needs to changed: D-16 needs to read 1st floor brewry
Note 1 elevator landing.
Note 2 MAIN FIRE CONTROL PANEL DID NOT SILIENCE ALARM. PANEL HAS TO
RESET TO SILIENCE
Note 3 Batteries in main fire panel and extender panel need to be replaced (6) 7ah
Note 4 Recommend zone map for parking garage fire panel. Zoned fire panel discription
does not specify location.
Note 5 Panel discription needs to be changed: D-17 needs to read as 2nd floor brewry
elevator landing
SimplexOrinnell
BE SAFE.
4650 Beloit Drive, Sacramento CA 95838 — (916) 283-0300 — (916) 920-2241
FEATHER FALLS CASINO SR# 33263094
3 ALVERDA DR IS THERE A DEFICIENCY?
OROVILLE, CA. 95966 YES X NO
TROY
Equipment Test Report
Yes No Qty Notes:
Were Tested Detectors Cleaned? II NA I I
If"No" answer, explain under comments
Were Tested Detectors Sensitivity Tested? II NA I
If"No" answer, explain under comments
Did test of Duct Detectors shut down air handling units: NA
Did the monitoring center receive signals? X
Central Station, Fire Department, Lease Line?
Is system reset for normal conditions? X
Is system restored to operational service? X
Operator and Time system put back on line? Operator: Time:
Have proper authorities been notified system is back in service? X
Indicate % of Equipment tested this report 25 50 75 100
Indicate % of equipment tested YTD 25 50 75 100
Comments for any"No" answers or explanations:
Did you receive a copy of your inspection report? YES X NO
If no how would you prefer to receive your report:
Email: 0 FAX 0
We appreciate your business. Thank you!
Customer Date
ChrOjCAMI., 11/25/15
Inspector Date
IF YOU HAVE ANY QUESTIONS REGARDING THIS INSPECTION AND/OR REPORT PLEASE CONTACT:
Our office at 916-283-0300