HomeMy WebLinkAboutFAI15-0072 CF FA Durham High 3.1.22 ALARM AND DETECTION REPORT Page 1 of 6
VOLTAG PECIALisTs
530-624-4514
C101C16 License#880862 www.VoltageSpecialists.com Inspection # 1-227
ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection:ANNUAL Date: 3/1/22
Customer DURHAM USD
Site: DURHAM HIGH SCHOOL
Street: 9455 PUTNEY DRIVE Contact: Eric
City/State: DURHAM, CA Phone#: 530-519-4604
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep Eric 530-519-4604
B. Fire Department EDE PATCH 68(18W-6460
C. Central Station Central Station 1-800-722-0364
D. Central Station Acct# 18-9477
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? X
On Test Time: 3:00 Return to Service Time: 9:00
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H.8 Date Batteries Installed: 9/18/20
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
•
Condition of Batteries: Good Note#
Battery Voltage with AC Power: 27.43 Battery Voltage without AC Power: 27.35
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: Silent Knight Model#620EVS System Type: NEZERESSAB
Location of Annunciators: MAIN OFFICE
Location of Primary Power Source:CEMP LAB Panel# 1 B Breaker 17
Comments: Note#
Note#
FCPS: Manufacturer: SIMPLEX Model# 4009 Panel/Breaker# Location:NURSES OFFII
Battery Voltage with A/C Power: 28.00 w/o A/C Power 27.81 Date: 1-19
FCPS: Manufacturer: SIMPLEX Model# 4009 Panel/Breaker# Location:NURSES OFFIt
Battery Voltage with A/C Power: 27.58 w/o A/C Power 25.96 Date: 12-19-18
FCPS: Manufacturer: SIMPLEX Model# 4009 Panel/Breaker# Location:POTTERY
Battery Voltage with A/C Power: 28.28 w/o A/C Power 28.14 Date: 10-2018
Owner/Rep: Phone#: Date:
Inspector: Mat Machado Phone#: 530-362-2609 Date:3/1/22
Owners Rep Sign: Date:3/1/22
Inspector Sign:
ALARM AND DETECTION REPORT Page 281IFg of 6
Property Site: DURHAM HIGH SCHOOL
Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators
5. Zones
6. Manual Stations (Pull)
Hardwire
Addressable 44 44 X
7. Detectors
Photoelectric 13 13 X
Ionization
Heats/Fixed or R of R
Flame
Duct(See#15) 12 12 X
8. Horn/Strobe 22 22 X
Strobe Only 8 8 X
Bell
Speakers
Horn 7 7 X
9.
10. Automatic Door Release
11. Water Flow switches 2 2 X
Did W/F Ring Outside Bell? X
Did W/F Activate Alarm Panel? X
12. Tamper Switches X
13. PIV X
OS &Y X
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X
17. Is system reset for normal conditions? X
18. Is system restored to operational service? X
19. Have Proper Authorities (see#1)been notified system is back in service? X
List Proper Authorities:Central Station, Durham Fire
20. Indicate %of equipment tested this report 25% 50% 75% VJI00%
21. Indicate %of equipment tested YTD 25% 50% 75% 100%
Comments for any"no"answers or explanations (Note#):
3/1/22C/' >
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT DURHAM HIGH SCHOOL Page 3 of 10
DEVICE zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PS Admin East X 97 17
PS Admin West X 97 16
PS Room 101 X 97 18
PS Room 102 X 97 19
PS Room 103 X 97 20
PS Room 104 X 97 21
PS Room 105 X 97 22
PS Room 106 X 97 23
PS Room 107 X 97 24
PS Room 201 North X 97 26
PS Room 201 South X 97 30
PS Room 202 X 97 27
PS Room 202 South X 97 31
PS Room 203 X 97 28
PS Rear Of Science Room X 97 32
PS Room 204 X 97 29
PS Art Room X 97 37
PS Art And Crafts Foyer X 97 38
PS Room 25 X 97 39
PS Ag Shop South X 97 41
PS Ag Shop North X 97 42
PS Ag Shop North West X 97 43
PS AG Room X 97 40
PS Portable 60 X 97 33
PS Portable 61 X 97 34
PS Portable 62 X 97 35
PS Portable 63 X 97 36
PS Music Room South X 97 12
PS Music Room West X 97 11
PS Band Room East X 97 14
PS Cafe South West X 97 56
PS Cafe South East X 97 57
PS Cafe East X 97 58
Owners Rep Sign: Date: 3/1/22 Inspector Sign:
ALARM AND DETECTION REPORT DURHAM HIGH SCHOOL Page 4 of 6
DEVICE zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PS Gym North West X 97 53
PS Boys Locker Room X 97 59
PS Wrestling/Weight Room X 97 09
PS Girls Locker Room X 97 08
PS Gym South West X 97 54
PS Gym East Exit X 97 55
PS Main Office X 97 15
PS AG Shop North X 97 50
PSD Media Center X 97 05
PSD Library X 97 06
PSD Library X 97 07
PSD Room 103 X 97 04
PSD Room 101 X 97 02
PSD Kiln Room X 97 13
PSD AG Class Room Mezzanine X 97 11
PSD AG Class Room Mezzanine X 97 12
PSD AG Class Room Mezzanine X 97 10
PSD AG Class Room Mezzanine X 97 09
PSD AG Class Room Mezzanine X 97 08
PSD nurses office X 97 01
PSD Room 101 X 97 03
PDD 400 Building RTU AC1 X 97 01
PDD 400 Building RTU AC2 X 97 02
PDD 100 Building RTU AC7 X 97 03
PDD 100 Building RTU AC12 X 97 04
PDD 100 Building RTU AC15 X 97 05
PDD 500 Building RTU AC1 X 97 06
PDD 100 Building RTU AC6 X 97 07
Owners Rep Sign: Date: 2/11/21 Inspector Sign:
ALARM AND DETECTION REPORT DURHAM HIGH SCHOOL Page 5 of 6
DEVICE zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PDD Gym RTU HVAC-1 X 97 46
PDD GYM RTU HVAC-3 X 97 47
PDD GYM RTU HVAC-2 X 97 48
PDD GYM RTU HVAC-4 X 97 49
PDD Boys Locker Room Team Room HV3 Duct X 97 65
PS Band Room West X 97 13
PS Room 108 X 97 25
PS Auto Shop X 97 44
PS Auto Shop East X 97 45
PS Kitchen North X 97 10
PS Band Room West X 97 13
WF Gym Riser In Janitors Closet X 97 51
WF Science Riser in Room Dis 14 X 97 52
PSD Gym/ CAFETERIA custodian Room X 97 50
KH Gym Cafeteria kitchen Ansul X 97 62
Owners Rep Sign: Date: 3/1/22 Inspector Sign:
ALARM AND DETECTION REPORT DURHAM HIGH SCHOOL Page 6 of 6
Zone or DEVICE
DEVICE SLC #
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
CO Gym X 97 64
CO GYM X 97 63
CO GYM X 97 62
CO GYM X 97 61
CO Boys Locker Team Room X 97 60
CO Gym Wrestling Room X 97 59
CO Gym Wrestling Room X 97 58
CO Multi Use/Cafeteria X 97 57
CO Multi Use/Cafeteria X 97 56
CO Multi Use/Cafeteria Stage X 97 55
CO Multi Use/Cafeteria Stage X 97 54
HT Multi Use/Cafeteria Kitchen X 97 53
HT Multi Use/Cafeteria Kitchen X 97 52
HT Multi Use/Cafeteria Kitchen X 97 51
LEGEND
PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual
ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch
PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch
IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder
DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve
SSD—SignalStationSmokeDetector B—Bell AV—Audible Visual PIV—Post Indicator Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - - -
NOTE # COMMENT
3/1/22 C)S
Owners Rep Sign: Date: Inspector Sign: