HomeMy WebLinkAboutFAI15-0049 CF FA Durham Elementary 2.28.22 ALARM AND DETECTION REPORT Page 1 of 4
VOLTAG PECIALisTs
530-624-4514
C101C16 License#880862 www.VoltageSpecialists.com Inspection # 1-001
ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection:ANNUAL Date: 2/28/22
Customer DURHAM USD
Site: DURHAM ELEMENTARY SCHOOL
Street: 9421 PUTNEY DRIVE Contact: Eric
City/State: DURHAM, CA Phone#: 530-514-4604
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep Eric 530-514-4604
B. Fire Department SAL FIRE 530-891-2788
C. Central Station Central Station 1800-722-0364
D. Central Station Acct# #18-9516
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? X
On Test Time: 3:00 Return to Service Time: 6:30
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H.18/20/18 Date Batteries Installed: 10/19/21
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
Condition of Batteries: Good Note#
Battery Voltage with AC Power: 27.28 Battery Voltage without AC Power: 27.23
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: SILENT KNIGHT Model#6820EVS System Type: CAB
Location of Annunciators: MAIN OFFICE
Location of Primary Power Source: Panel# Breaker
Comments: Note#
Note#
FCPS: Manufacturer: SIMPLEX Model# 4009 Panel/Breaker# Location:BY FACP
Battery Voltage with A/C Power: 27.94 w/o A/C Power 27.19 Date: 12/21/18
FCPS: Manufacturer: SIMPLEX Model# 4009 Panel/Breaker# Location:BY FACP
Battery Voltage with A/C Power: 27.96 w/o A/C Power 27.90 Date: 12/21/18
FCPS: Manufacturer: Silent Knight Model# EVS-50W Panel/Breaker# Location:BY FACP
Battery Voltage with A/C Power: 27.28 w/o A/C Power 27.20 Date: 10/19/21
Owner/Rep: Phone#: Date:
Inspector: Mat Machado Phone#: 530-362-2609 Date:2/28/22
Owners Rep Sign: Date: Inspector Inspector Sign:
ALARM AND DETECTION REPORT Page 2 of 4
Property Site: DURHAM ELEMENTARY SCHOOL
Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators 1 1 X
5. Zones
6. Manual Stations (Pull)
Hardwire
Addressable 27 27 X
7. Detectors
Photoelectric 1 1 X
Ionization
Heats/Fixed or R of R 2 2 X
Flame
Duct(See#15) 1 1 X
8. Horn/Strobe 39 39 X
Strobe Only 14 14 X
Bell
Speakers
Horn 8 8 X
9.
10. Automatic Door Release X
11. Water Flow switches X
Did W/F Ring Outside Bell? X
Did W/F Activate Alarm Panel? X
12. Tamper Switches X
13. PIV X
OS &Y X
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X
17. Is system reset for normal conditions? X
18. Is system restored to operational service? X
19. Have Proper Authorities (see#1)been notified system is back in service? X
List Proper Authorities:Durham Fire
20. Indicate %of equipment tested this report 25% 50% 75% VJI00%
21. Indicate %of equipment tested YTD 25% 50% 75% 100%
Comments for any"no"answers or explanations (Note#):
2/28/22C/' >
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Page 3 of 4
Property Site: DURHAM ELEMENTARY SCHOOL
DEVICE zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PS SOUTH WEST MAIN HALL X 97 M1
PS SOUTH MAIN HALL X 97 M2
PS MULTI PURPOSE X 97 M4
PS MULTI PURPOSE X 97 M5
PS SOUTH WEST COURTYARD X 97 M6
PS LIBRARY X 97 M7
PS NORTH WEST COURTYARD X 97 M8
PS NORTH WEST MAIN HALL X 97 M9
PS NORTH MAIN HALL X 97 M10
PS MAIN EAST ENTRANCE X 97 M11
PS ROOM 32 NORTH X 97 M12
PS ROOM 32 SOUTH X 97 M13
PS ROOM 31 NORTH X 97 M14
PS ROOM 31 SOUTH X 97 M15
1PS Portable Island Side 1 X 97 M16
12PS Portable Island Side 2 X 97 M17
ADS ROOM 40 X 97 M18
PS ROOM 39 X 97 M19
PS ROOM 38 X 97 M20
PS ROOM 37 X 97 M21
PS ROOM 36 X 97 M22
PS ROOM 35 X 97 M23
PS ROOM 34 X 97 M24
2PS ROOM 33 X 97 M25
PS ROOM 41 X 97 M26
PS ROOM 42 X 97 M27
PS ROOM 29 X 97 M29
c),S
Owners Rep Sign: Date: 2/28/22 Inspector Sign:
p J
ALARM AND DETECTION REPORT DURHAM ELEMENTARY SCHOOL Page 4 of 4
Zone or DEVICE
DEVICE SAC #
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
KH Cafeteria kitchen Hood X 97 2
PSD Janitors Closet Above FACP X 97 1
HT Kitchen X 97 2
PDD Kitchen AC 28 X 97 3
HT Kitchen X 97 4
LEGEND
PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual
ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch
PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch
IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder
DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve
SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual Ply—Post Indicator Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - - -
NOTE # COMMENT
2/28/22 C)S
Owners Rep Sign: Date: Inspector Sign: