HomeMy WebLinkAboutB23-1216,1217,1218 and B23-1223,1224,1225 CF PC Orchard View Gridley CAL Butte County Fire Department FIRE 11E C06 Fire Prevention Bureau 41YA „: - 176 Nelson Avenue Oroville, CA 95965 Butte County RESCUE Office (530)538-7888 www.buttecountv.net/fire •{A L I F O R N I A• NON RESIDENTIAL PLAN REVIEW LETTER May 30,2023 PACIFIC WEST BUILDERS INC 430 E STATE ST SUITE 100 EAGLE, ID 83616 APN: 021-110-033 Building Permit Number: B23-1223 Plan Check#1 Description: 8 APTS (13,984) OPEN(2950)BLDG B#100 Occupancy Classification: R-2/U Fire Sprinklers: Yes Building Total Area: R-2 @ 13984 sf/U @ 0 sf Dear Applicant, The plans you recently submitted have been reviewed by the Fire Department referencing the 2022 edition of the California Building Standards Codes. The numbered comments listed below in the body of this letter must be addressed in writing prior to Fire Department Approval of your project. 1. Sheet T1.2, Fire Department Notes, Sheet LS-101, Insert a note that "Fire extinguishers shall be a minimum 2A:10B:C, with a travel distance not to exceed 75' from any point. Extinguishers shall be mounted in a conspicuous place, easily accessible and readily available, and shall be along normal paths of travel. Extinguishers shall be mounted so that the top of the extinguisher is no higher than five feet above the finished floor. Where extinguishers may be subject to physical damage they shall be adequately protected." CFC 906.2 2. Sheet T1.2, An automatic fire sprinkler per NFPA 13/13R and fire alarm will be required, and it is noted that submittal is deferred. 3. Sheet T1.2, Fire Department Requirements, add a note to the plans "Prior to the arrival of combustible materials onsite, provide an approved water supply for fire protection" CFC 3312 4. Sheet T 1.2, Fire Department Requirements, add a note to the plans "Approved vehicle access for firefighting shall be provided to within 100 feet of temporary or permanent fire department connections. Vehicle access shall be provided by either temporary or permanent roads, capable of supporting vehicle loading under all weather conditions. Vehicle access shall be maintained until permanent fire apparatus access roads are available." CFC 3310 5. Sheets A2.1 through A2.7, Place a note on the plans and indicate the locations of all smoke and carbon monoxide detectors. CBC Sections 907.2.11.2 and 915.1.1. 6. Sheet A3.IA, General Notes AA, Revise comment to state "Provide a key box adjacent to the office main entry. Indicate on the plans that the key box shall be Knox brand"KNOXVAULT® 4400"model or similar. The box may be surface or recessed mounted. Contact Butte County Fire Marshal at 530-538-6320 for order information. The box shall contain keys for the main entry, fire sprinkler riser access, O.S.&Y Valve, MEP rooms, and alarm panel. CFC 506.1 7. Sheets Si.A4 and S 1.B4, General notes, place a note on the plans, and indicate locations of attic access. CBC 1209.2 The Fire Prevention Bureau is currently open to the public from 8:00 am to 5:00 pm. If you wish to discuss these plan check comments, please call during our business hours or contact us by e- mail at the address below. Permit status can be tracked by logging on to http://www.buttecounty.net/dds and clicking Building Permits Status. Chris Boyd Troy Hand Deputy Fire Marshal Fire Protection Planning 530.538.6320 530.538.6320 Chris.bovd@fire.ca.gov Trov.Hand@fire.ca.2ov