HomeMy WebLinkAboutRev 7.21.23 Harold Cope Solar Drawing_RevE 76 North Meadowbrook Drive Scott E. Wyssling, PE Alpine, UT 84004 Coleman D. Larsen, SE, PE office (201) 874-3483 Gregory T. Elvestad, PE swyssling@wysslingconsulting.com April 25, 2023 California Renewable Energy Suite 105 Re: Engineering Services Cope Residence 1326 Honey Run Road, Chico, CA 19.760 kW System To Whom it May Concern, Pursuant to your request, we have reviewed the following information regarding ground mount solar panel installation at the above referenced location: 1. Structural drawings prepared by IronRidge identifying specific racking layout and components for the proposed ground mount system. 2. Design drawings of the proposed system including a site plan, and details for the solar panels. This information was prepared by California Renewable Energy and will be utilized for approval and construction of the proposed system. Based on our review of the (2) Photovoltaic Array installed at 5 modules high and 5 modules wide (Array 1) and 5 modules high and 6 modules wide (Array 2), the PV arrays shall have a maximum pier spacing of 9’-0” north/south and 13’-2” east/west. Based on a wind speed of 100 mph, Exposure C and a ground snow load of 0 PSF, it was determined that the minimum required footing depth is 66 inches below grade with a 24” diameter concrete footing. The footing size based upon the worst case loading due to horizontal and vertical wind loading. Based on the above evaluation, it is the opinion of this office that with appropriate construction the footing and post assembly will adequately support the proposed solar array. This evaluation is in conformance with the 2022 California Building Code, current industry and standards, and based on information supplied to us at the time of this report. This certification is specific to the footing design for the solar system and does not include the racking system. Racking system and components designed and specified by the manufacturer (IronRidge). Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling, PE California License No. 83664 2024 Opportunity Dr. Roseville, CA 95678 REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWPROJECT DATAGENERAL NOTESVICINITY MAPSHEET INDEXCODE REFERENCESPROJECTADDRESS1326 HONEY RUN ROAD,CHICO, CA 95928OWNER:HAROLD COPELICENSE #017 230060000SCOPE:19.760 KW DC GROUND MOUNTSOLAR PV SYSTEM WITH52 JINKO SOLAR: JKM380M-6RL3-B 380WPV MODULES WITH52 ENPHASE IQ8PLUS-72-2-US (290)MICROINVERTERS02 ENPHASE ENCHARGE 10-1P-NAHOUSE PHOTOCOVER SHEETPHOTOVOLTAIC GROUND MOUNT SYSTEM52 MODULES-GROUND MOUNTED - 19.760 KW DC, 15.080 KW AC1326 HONEY RUN ROAD, CHICO, CA 95928PV-1AUTHORITIES HAVING JURISDICTION:BUILDING: BUTTE COUNTYZONING: BUTTE COUNTYUTILITY: PG&EPARCEL ID:017230060000CONTRACTOR:CALIFORNIA RENEWABLE ENERGY2024 OPPORTUNITY DR. STE 150ROSEVILLE, CA 95678DESIGNER:ESRPV-1 COVER SHEETPV-2 PLOT PLAN WITH GROUND PLANPV-3 GROUND PLAN & MODULESPV-4 ELECTRICAL PLANPV-5 MOUNTING DETAIL-1PV-5A MOUNTING DETAIL-2PV-5B MOUNTING DETAIL-3PV-6 ELECTRICAL LINE DIAGRAMPV-7 WIRING CALCULATIONPV-8 LABELSPV-9 PLACARDPV-10 OPTIMIZER CHARTPV-11+ EQUIPMENT SPECIFICATIONS1. ALL COMPONENTS ARE UL LISTED AND CEC CERTIFIED, WHERE WARRANTED.2. THE SOLAR PV SYSTEM WILL BE INSTALLED IN ACCORDANCE WITH ARTICLE 690 OF THE 2022 CEC.3. THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM INSPECTED PRIOR TO PARALLELOPERATION.4. ALL CONDUCTORS OF A CIRCUIT, INCLUDING THE EGC, MUST BE INSTALLED IN THE SAME RACEWAY, OR CABLE, OROTHERWISE RUN WITH THE PV ARRAY CIRCUIT CONDUCTORS WHEN THEY LEAVE THE VICINITY OF THE PV ARRAY.5. WHERE METALLIC CONDUIT CONTAINING DC CONDUCTORS IS USED INSIDE THE BUILDING, IT SHALL BE IDENTIFIED AS"CAUTION: SOLAR CIRCUIT" EVERY 10FT.6. HEIGHT OF THE AC DISCONNECT SHALL NOT EXCEED 6'-7" PER CEC CODE 240.24.7. A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH CEC 690.47 AND 250.50 THROUGH 60 AND 250-166 SHALL BEPROVIDED. PER CEC GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND BONDED TO THE SERVICEENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE OR INADEQUATE A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE USEDAT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT. GROUND ROD WITH ACORN CLAMP. GROUNDING ELECTRODECONDUCTORS SHALL BE NO LESS THAN #8 AWG AND NO LARGER THAN #6 AWG COPPER AND BONDED TO THE EXISTINGGROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM.8. PHOTOVOLTAIC MODULES ARE TO BE CONSIDERED NON-COMBUSTIBLE.9. PHOTOVOLTAIC INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING. MECHANICAL, OR BUILDING ROOF VENTS.10. ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND LISTED FOR SUCH USE.WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF THE ROOF SURFACE.11. ALL SINAGE TO BE PLACED IN ACCORDANCE WITH THE LOCAL BUILDING CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UVRESISTANT. ALL PLAQUES AND SINAGE WILL BE INSTALLED AS REQUIRED BY THE CEC AND AHJ.12. MICROINVERTER(S) USED IN UNGROUNDED SYSTEM SHALL BE UL 1741 LISTED.13. THE INSTALLATION OF EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTION SHALL BE PERFORMED ONLY BYQUALIFIED PERSONS [ CEC 690.4(C)]14. ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED (OR BETTER), INCLUDING ALL GROUND MOUNTED TRANSITION BOXESAND SWITCHES.15. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH CEC ARTICLE 250.16. SYSTEM GROUNDING SHALL BE IN ACCORDANCE WITH CEC 690.41.17. PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION IN ACCORDANCE WITHCEC 690.1218. DISCONNECTING MEANS SHALL BE LOCATED IN A VISIBLE, READILY ACCESSIBLE LOCATION WITHIN THE PV SYSTEMEQUIPMENT OR A MAXIMUM OF 10 FEET AWAY FROM THE SYSTEM [ CEC 690.13(A)]19. ALL WIRING METHODS SHALL BE IN ACCORDANCE WITH CEC 690.3120. WORK CLEARANCES AROUND ELECTRICAL EQUIPMENT WILL BE MAINTAINED PER CEC 110.26(A)(1), 110.26(A)(2) AND 10.26(A)(3).21. GROUND MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED & IDENTIFIED IN ACCORDANCE WITHUL170322. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT EXPANSION JOINTS AND ANCHOR CONDUIT RUNS AS REQUIRED PER CEC.23. IN ACCORDANCE WITH 2022 CALIFORNIA RESIDENTIAL CODE SECTION R324.7.2. A CLEAR, BRUSH-FREE AREA OF 10 FEET(3048MM) SHALL BE REQUIRED FOR GROUND-MOUNTED PHOTOVOLTAIC ARRAYSPROJECT TO COMPLY WITH THE FOLLOWING:2022 CALIFORNIA BUILDING CODE2022 CALIFORNIA RESIDENTIAL CODE2022 CALIFORNIA ELECTRICAL CODE2022 CALIFORNIA FIRE CODE2022 CALIFORNIA GREEN BUILDING STANDARDS CODEASCE 7-16CCC 361' -6 "413' -4 "114'-9"101'-11"12'-5"5'-2 "16'-7 "30'-7 "17'-0"17'-0"36'-8 "324'-1 " JB JBSLC MSPUMAC D 12'-4"BL P IQ SC ACD BATBATACD11'-7"72'-0"71'-8"20' - 0 "10'-0"13'-4"1PLOT PLAN WITH GROUND PLANSCALE: 1/32" = 1'-0"PV-2REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWGROUND #1(25)JINKO SOLAR: JKM380M-6RL3-B 380WMONO MODULES WITH ENPHASEIQ8PLUS-72-2-US (290) MICROINVERTERSPROJECT DESCRIPTION:52 X JINKO SOLAR: JKM380M-6RL3-B 380W PV MODULESGROUND MOUNTED SOLAR PHOTOVOLTAIC MODULESDC SYSTEM SIZE: 19.760KW DCAC SYSTEM SIZE: 15.080KW ACPV-2PLOT PLAN WITHGROUND PLANGROUND MOUNT ARRAY AREA #1:- 513.50 SQ FT.EXIST INGPATHWAY1-STORYHOUSE(E) UTILITY METER/MAIN COMBO(E) FENCEEQUIPMENT SUMMARY52 JINKO SOLAR: JKM380M-6RL3-B 380W MONO MODULES52 ENPHASE IQ8PLUS-72-2-US (290) MICRO-INVERTERSGROUND #2(27)JINKO SOLAR: JKM380M-6RL3-B 380WMONO MODULES WITH ENPHASEIQ8PLUS-72-2-US (290) MICROINVERTERSHONEY RUN ROAD(E) GATE (TYP.)(N) VISIBLE, LOCKABLE, LABELED NONFUSED AC DISCONNECT (LOCATEDWITHIN 10' OF UTILITY METER)(N) BACKUP LOAD PANEL (MOUNTED ON BACKBOARD)(N) VISIBLE, LOCKABLE, LABELED NON FUSED PVAC DISCONNECT (MOUNTED ON BACKBOARD)(N) ENPHASE IQ SYSTEM CONTROLLER-2 (MOUNTED ON BACKBOARD)(N) VISIBLE, LOCKABLE, LABELED NON FUSED ESS ACDISCONNECT (MOUNTED ON BACKBOARD)(N) ENPHASE ENCHARGE 10-1P-NA BATTERY (MOUNTED ON BACKBOARD)(N) ENPHASE ENCHARGE 10-1P-NA BATTERY (MOUNTED ON BACKBOARD)(N) JUNCTION BOX(N) JUNCTION BOX(N) SOLAR LOAD CENTERGROUND MOUNT ARRAY AREA #2:- 554.58 SQ FT.(E) SEPTIC TANKFUTURE SEPTIC TANK AREA(E) LEACH FIELDAAEDC TRENCHING THROUGH DIRT APPROX 74'-0"PVC BURIAL (MIN. 18")(N) TRENCH TBD ON-SITEAB 10’ FREE OF VEGETATIONAROUND THE ARRAYCNOTE: BATTERIES SHALL BE INSTALLED ATLEAST 3' AWAY FROM ANY OPEN SPACE.CFUTURE LEACH FIELD(420 SQUARE FEET)E JBJBSLCMSPUMACDBLPIQSC ACDBA T BATACDMODULE TYPE, DIMENSIONS & WEIGHT1GROUND PLAN & MODULESPV-3SCALE: 1/16" = 1'-0"GROUND PLAN &MODULESREVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWNUMBER OF MODULES = 52 MODULESMODULE TYPE = JINKO SOLAR: JKM380M-6RL3-B 380W MONO MODULESMODULE WEIGHT = 45.86 LBS / 20.8KG.MODULE DIMENSIONS = 73.03" x 40.51" = 20.54 SFJINKO SOLAR:JKM380M-6RL3-B380W MODULES73.03"40.51"PV-3LEGEND- JUNCTION BOXJBBATUMMSPSLC- BATTERY- SOLAR LOAD CENTER- UTILITY METER- MAIN SERVICE PANELACD- AC DISCONNECTACD- AC DISCONNECTIQSC- ENPHASE IQ SYSTEMCONTROLLER-2BLP- BACKUP LOADPANELSUB- SUB-PANELGROUND #1(25)JINKO SOLAR: JKM380M-6RL3-B 380WMONO MODULES WITH ENPHASEIQ8PLUS-72-2-US (290) MICROINVERTERSGROUND #2(27)JINKO SOLAR: JKM380M-6RL3-B 380WMONO MODULES WITH ENPHASEIQ8PLUS-72-2-US (290) MICROINVERTERSDC TRENCHING THROUGHDIRT APPROX 74'-0"PVC BURIAL (MIN. 18")(N) JUNCTION BOX(N) TRENCH TBD ON-SITE(N) SOLAR LOAD CENTER(N) JUNCTION BOXARRAY #1PITCH - 20°AZIM . - 152°ARRAY #2PITCH - 20°AZIM . - 152°(E) UTILITY METER/MAIN COMBO(N) VISIBLE, LOCKABLE, LABELED NONFUSED AC DISCONNECT (LOCATEDWITHIN 10' OF UTILITY METER)(N) BACKUP LOAD PANEL (MOUNTED ON BACKBOARD)(N) VISIBLE, LOCKABLE, LABELED NON FUSED PVAC DISCONNECT (MOUNTED ON BACKBOARD)(N) ENPHASE IQ SYSTEM CONTROLLER-2 (MOUNTED ON BACKBOARD)(N) VISIBLE, LOCKABLE, LABELED NON FUSED ESS ACDISCONNECT (MOUNTED ON BACKBOARD)(N) ENPHASE ENCHARGE 10-1P-NA BATTERY (MOUNTED ON BACKBOARD)(N) ENPHASE ENCHARGE 10-1P-NA BATTERY (MOUNTED ON BACKBOARD)(N) BACKBOARD JB JB S LC MSPUMACDB LP IQ SC ACDBATBA T ACD1ELECTRICAL PLANPV-4SCALE: 1/16" = 1'-0"ELECTRICALPLANREVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWPV-4CIRCUIT #4(9 MODULES)CIRCUIT #5(8 MODULES)CIRCUIT #6(8 MODULES)CIRCUIT #1(9 MODULES)(52)ENPHASEIQ8PLUS-72-2-US (290)MICROINVERTERS(N) JUNCTION BOX(N) SOLAR LOAD CENTER(N) JUNCTION BOXCIRCUIT #2(9 MODULES)CIRCUIT #3(09 MODULES)CIRCUIT #5CIRCUIT #6CIRCUIT #1CIRCUIT #2CIRCUIT #3CIRCUIT #4CIRCUIT LEGENDSDC TRENCHING THROUGHDIRT APPROX 74'-0"PVC BURIAL (MIN. 18")(N) TRENCH TBD ON-SITELEGEND- JUNCTION BOXJBBATUMMSPSLC- BATTERY- SOLAR LOAD CENTER- UTILITY METER- MAIN SERVICE PANELACD- AC DISCONNECTACD- AC DISCONNECTIQSC- ENPHASE IQ SYSTEMCONTROLLER-2BLP- BACKUP LOADPANELSUB- SUB-PANEL(E) UTILITY METER/MAIN COMBO(N) VISIBLE, LOCKABLE, LABELED NONFUSED AC DISCONNECT (LOCATEDWITHIN 10' OF UTILITY METER)(N) BACKUP LOAD PANEL (MOUNTED ON BACKBOARD)(N) VISIBLE, LOCKABLE, LABELED NON FUSED PVAC DISCONNECT (MOUNTED ON BACKBOARD)(N) ENPHASE IQ SYSTEM CONTROLLER-2 (MOUNTED ON BACKBOARD)(N) VISIBLE, LOCKABLE, LABELED NON FUSED ESS ACDISCONNECT (MOUNTED ON BACKBOARD)(N) ENPHASE ENCHARGE 10-1P-NA BATTERY (MOUNTED ON BACKBOARD)(N) ENPHASE ENCHARGE 10-1P-NA BATTERY (MOUNTED ON BACKBOARD) 30'-7"4'-0"9'-0"1'-6"13'-9"4'-0"36'-8"4'-7"13'-9"4'-0"9'-0"REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWPV-51ARRAY#2 PLAN WITH MOUNTING DETAILPV-5SCALE: NTS(N) IRONRIDGE XR-1000 RAILGROUND MOUNT #1(25)JINKO SOLAR: JKM380M-6RL3-B 380W MONOMODULES WITHSOLAREDGE P505 POWER OPTIMIZERS(N) RAIL CONNECTOR(N) 3" PIER PIPE(N) TOP CAP(N) 3" CROSS PIPEGROUND #2(27)JINKO SOLAR: JKM380M-6RL3-B 380WMONO MODULES WITH ENPHASEIQ8PLUS-72-2-US (290) MICROINVERTERSMOUNTINGDETAIL-1B1ARRAY#1 PLAN WITH MOUNTING DETAILPV-5SCALE: NTS REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWPV-5AMOUNTINGDETAIL-2B REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWPV-5BMOUNTINGDETAIL-3B GN- + - +2- +13=====BRANCH #2BRANCH #3L1L2L1L2- + - +2- +13=====BRANCH #1JUNCTION BOX#1,600V, NEMA 3R,UL LISTEDSOLAR LOAD CENTER240V, 1ɸ, 3W125A RATED, NEMA 3R20A/2P20A/2P20A/2P20A/2P15A/2PIQGATEWAY- + - +2- +13=====(27) JINKO SOLAR: JKM380M-6RL3-B380W MODULESL1L220A/2P2GIQ GATEWAYENCLOSUREL1L2NG6LOADGNVISIBLE, LOCKABLE,LABELED AC DISCONNECTLOCATED WITHIN 10'OF UTILITY METERPV/ESS ACDISCONNECT240V, 1ɸ, 3W200A RATEDNEMA 3RLINE6L1L2NGL1L2NG3AC TRENCHING THROUGHDIRT APPROX 74' PVCBURIAL (MIN. 18")PVGL2NGENBATTL1(N) ENPHASE IQ SYSTEMCONTROLLER 2EP200G101-M240US01NEMA 3R, 160A RATED, 240V4GGN640A/2PBATTNFT80A/2PPV GENGROUNDNEUTRALTO IQ GATEWAYCONSUMPTIONCT'SNEUTRALFORMINGXFMRM.I.DENPHASE ENPOWER SMART-SWITCHIS EQUIPPED W/ M.I.D. (MICRO-GRIDISLANDING DEVICE) - WHICH DURING AGRID OUTAGE, WILL OPEN AND NOTALLOW BACKFEED TO THE GRID.125A/2PNC2NC3NC4NO3NO1NO2NC1VISIBLE, LOCKABLE,LABELED AC DISCONNECTLOADGNLINEPV AC DISCONNECT,240V, 1ɸ, 3W100A RATEDNEMA 3R(N) BACKUP LOAD PANEL125A RATED, 120/240V, 1ɸ,3W, NEMA 3R, UL LISTEDCIRCUITS WILL BE REMOVED OUTOF EXISTING PANEL ANDEXTENDED TO THE CRITICALLOADS PANEL IN THE VICINITY OFTHE EXISTING PANELLOADGNLINEESS AC DISCONNECT,240V, 1ɸ, 3W60A RATEDNEMA 3RVISIBLE, LOCKABLE,LABELED BATTERYDISCONNECT5GL2L1GL2L1CONTROLLER(N) ENPHASEENCHARGE-10-1P-NABATTERYL1L2G5CONTROLLER(N) ENPHASEENCHARGE-10-1P-NABATTERYNOTE: BATTERY WILLBE LEFT IN BACK-UPMODE BY TECHBATTERIES ARECONNECTED IN DAISYCHAIN MECHANISM- + - +2- +13=====BRANCH #5BRANCH #6L1L2L1L2- + - +2- +13=====BRANCH #4JUNCTION BOX#2,600V, NEMA 3R,UL LISTED- + - +2- +13=====L1L22G198987878ENPHASE IQ8PLUS-72-2-US (290)LOCATED UNDER EACH PANEL (240V)FEEDER CONNECTIONREF2022 CEC 705.12(B)(3)(2)NL2L1M(E) MAIN BREAKER TO HOUSE240 V, 200A/2PGECGNBI-DIRECTIONALUTILITY METER# 1008954263120/240V 1ɸ, 3-WMETERTO UTILITY GRID(E) MAIN SERVICEPANEL, EATON120/240V, 1ɸ, 3W200A RATEDLOAD SIDEINTERCONNECTION ATMAIN PANEL/SUB-PANELPER ART. 705.12125A/2PEXISTING GROUNDINGELECTRODE SYSTEM TO EARTHREF. CEC 250.52, 250.53(A)GL2L1N19898(25) JINKO SOLAR: JKM380M-6RL3-B380W MODULESBRANCHTERMINATOR(ET-TERM)BRANCHTERMINATOR(ET-TERM)GROUND RODGROUND RODREVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWELECTRICAL LINEDIAGRAM1ELECTRICAL LINE DIAGRAMPV-6SCALE: NTSDC SYSTEM SIZE: 19.760 KW DCAC SYSTEM SIZE: 15.080 KW AC(52) JINKO SOLAR: JKM380M-6RL3-B 380 W MONO MODULES WITH(52)ENPHASE IQ8PLUS-72-2-US (290) MICROINVERTERS(4) BRANCH CIRCUITS OF 09 MODULES AND(2) BRANCH CIRCUIT OF 08 MODULES CONNECTED IPARALLELPV-6QTYCONDUCTOR INFORMATIONCONDUIT TYPECONDUITSIZE(12)CU #12AWG -ENPHASE ENGAGE CABLE(L1 &L2 NO NEUTRAL)N/AN/A(1)CU #6AWG - BARE COPPER IN FREE AIR(6)CU #10AWG - THWN-2 L1 &L2EMT OR LFMC IN ATTIC(1)CU #10AWG - THWN-2 GND(3)CU #4AWG -THWN-2 OR THHN L1,L2 &NPVC BURIAL (MIN. 18")(1)CU #8AWG - THWN-2 OR THHN GND(3)123(3)(1)CU #6 AWG -53/4"CU #1 AWG -(1)EMT,LFMC OR PVC(2)CU #8AWG -(1)CU #10AWG -41 1/4"THWN-2 OR THHN L1,L2 &NTHWN-2 OR THHN GNDTHWN-2 OR THHN L1,&L2THWN-2 OR THHN GNDTHWN-2 OR THHN L1,L2 &NTHWN-2 OR THHN GND6EMT,LFMC OR PVCEMT,LFMC OR PVC3/4"#10/2 ROMEXIN ATTICCU #4AWG -CU #8AWG -1"1"INTERCONNECTION NOTES:1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCEDETERMINED IN ACCORDANCE WITH [CEC 705.12], AND [CEC 690.59].2. GROUND FAULT PROTECTION IN ACCORDANCE WITH [CEC 215.9],[CEC 230.95].3. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING.4. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THEBUSBAR RELATIVE TO THE MAIN BREAKER.DISCONNECT NOTES:1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHENTHE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARECONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLYTHE UPPER TERMINALS)2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITYPERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCHRACKING NOTES:1. BOND EVERY OTHER RAIL WITH #6 BARE COPPERGROUNDING & GENERAL NOTES:1. REQUIRED GROUND ROD FOR THE SOLAR ARRAY STRUCTURE, AS PER C.E.CARTICLE 690.47 AND 2502. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESSTYPE.3. DC GEC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTINGELECTRODE4. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT ISFOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINALINSPECTION.5. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THEFIELD - JUNCTION BOX DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRETYPE TRANSITIONS.6. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHERAC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT.7. RACEWAYS AND CABLES EXPOSED TO SUNLIGHT ON ROOFTOPS SHOULD BEINSTALLED MORE THAN 7/8" ABOVE THE ROOF USING CONDUIT SUPPORTS.8. ALL NEW SERVICE INSTALLATIONS AND REPLACEMENTS REQUIRE ASURGE-PROTECTIVE DEVICE (SPD) IN ACCORDANCE WITH [CEC 230.67]. THE SPDSHALL BE TYPE 1 OR TYPE 2 AND IS REQUIRED TO BE AN INTEGRAL PART OF THESERVICE EQUIPMENT OR LOCATED IMMEDIATELY ADJACENT THERETO.CCC REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWWIRINGCALCULATIONSPV-7PERCENT OFVALUESNUMBER OF CURRENTCARRYING CONDUCTORS IN EMT.804-6.707-9.5010-20SOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL #JINKO SOLAR: JKM380M-6RL3-B 380WMODULE VMP36.90V IMP10.30A VOC44.22V ISC11.12A TEMP. COEFF. VOC-0.29%/K MODULE DIMENSION73.03"L x 40.51"W x 1.38"D (In Inch)INVERTER SPECIFICATIONSMANUFACTURER / MODEL #ENPHASE IQ8PLUS-72-2-US (290)MICROINVERTERMIN/MAX DC VOLT RATING22V MIN/ 48V MAXMAX INPUT POWER235W-350WNOMINAL AC VOLTAGE RATING240V/ 211-264VMAX AC CURRENT1.0AMAX MODULES PER CIRCUIT16 (SINGLE PHASE)MAX OUTPUT POWER240 VAAMBIENT TEMPERATURE SPECSRECORD LOW TEMP-2°AMBIENT TEMP (HIGH TEMP 2%)37°CONDUCTOR TEMPERATURE RATE90°MODULE TEMPERATURE COEFFICIENT OF Voc-0.29%/°CELECTRICAL NOTES1.ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION.2.ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT.3.WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSEAS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.4.WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH CEC 110.26.5.DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARYOUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS.6.WHERE SIZES OF SOLADECK, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEMACCORDINGLY.7.ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE.8.MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THEGROUNDING CLIP MANUFACTURER'S INSTRUCTION.9.MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.10.TEMPERATURE RATINGS OF ALL CONDUCTORS, TERMINATIONS, BREAKERS, OR OTHER DEVICES ASSOCIATED WITH THESOLAR PV SYSTEM SHALL BE RATED FOR AT LEAST 75 DEGREE C. REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWLABELSPV-8PHOTOVOLTAICAC DISCONNECTNOMINAL OPERATING AC VOLATGE240 V62.92 ARATED AC OUTPUT CURRENTCAUTION:AUTHORIZED SOLARPERSONNEL ONLY!LABEL-1:TERMINALS ON THE LINE AND LOAD SIDES MAYBE ENERGIZED IN THE OPEN POSITIONWARNING!ELECTRICAL SHOCK HAZARDLABEL- 2:!WARNING DUAL POWER SOURCESECOND SOURCE IS PHOTOVOLTAIC SYSTEMLABEL- 3:TURN OFF PHOTOVOLTAIC ACDISCONNECT PRIOR TOWORKING INSIDE PANELWARNING!LABEL- 4:LABEL- 5:CAUTION!PHOTOVOLTAIC SYSTEM CIRCUIT ISBACKFEEDLABEL- 6:SOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNTURN RAPID SHUTDOWNSWITCH TO THE"OFF" POSITION TOSHUT DOWN PV SYSTEMAND REDUCESHOCK HAZARDIN THE ARRAYSOLAR ELECTRICPV PANELSLABEL- 7:RAPID SHUTDOWN SWITCHFOR SOLAR PV SYSTEMLABEL- 8:PHOTOVOLTAICAC DISCONNECTLABEL- 9:LABEL- 10:WARNINGPOWER SOURCE OUTPUTCONNECTION. DO NOTRELOCATE THISOVERCURRENT DEVICE!MAIN PHOTOVOLTAICSYSTEM DISCONNECTLABEL- 11:LABEL LOCATION:AC DISCONNECTCODE REF: CFC 2022 1205.4.1(1) & 2022 CEC 690.56(C)LABEL LOCATION:AC DISCONNECTCODE REF: 2022 CEC 690.56(C)(2)LABEL LOCATION:AC DISCONNECTCODE REF: 2022 CEC 690.13(B)LABEL LOCATION:MAIN SERVICE PANELSUBPANELAC DISCONNECTCODE REF: 2022 CEC 690.54LABEL LOCATION:MAIN SERVICE DISCONNECT (ONLY IF MAIN SERVICE DISCONNECT IS PRESENT)CODE REF: 2022 CEC 690.54LABEL LOCATION:AC DISCONNECTCODE REF: 2022 CEC 690.13(B)LABEL LOCATION:AC DISCONNECTCOMBINERMAIN SERVICE PANELSUBPANELMAIN SERVICE DISCONNECTCODE REF: 2022 CEC 690.13(B)LABEL LOCATION:PRODUCTION METERUTILITY METERMAIN SERVICE PANELSUBPANELCODE REF: 2022 CEC 705.12(D)(3) & 2022 CEC 690.59LABEL LOCATION:MAIN SERVICE PANELSUBPANELMAIN SERVICE DISCONNECTCOMBINERCODE REF: 2022 CEC 110.27(C) & OSHA 1910.145 (f) (7)LABEL LOCATION:MAIN SERVICE PANEL (ONLY IF SOLAR IS BACK-FED)SUBPANEL (ONLY IF SOLAR IS BACK-FED)CODE REF: 2022 CEC 705.12(C) & 2022 CEC 690.59LABEL LOCATION:MAIN SERVICE PANEL (ONLY IF SOLAR IS BACK-FED)SUBPANEL (ONLY IF SOLAR IS BACK-FED)CODE REF: 2022 CEC 705.12(B)(3)(2) JB JB SLC MSPUM ACD BLP IQS C ACD BAT BAT ACD REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWPLACARDDIRECTORYPERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THESERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM.(ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN:CEC 690.56(A)(B), [CEC 705.10])1326 HONEY RUN ROAD, CHICO, CA 95928PV-9LABELING NOTES:1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACTREQUIREMENTS IN THE FIELD PER CURRENT CEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS.2. LABELING REQUIREMENTS BASED ON THE 2022 CEC, OSHA STANDARD 19010.145, ANSI Z535.3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [CEC 110.21]5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLYAFFIXED [CFC 605.11.1.1]MULTIPLE SOURCES OF POWERCAUTION:(N) JUNCTION BOX(N) SOLAR LOAD CENTER(N) JUNCTION BOX(E) UTILITYMETER/MAIN COMBO(N) VISIBLE, LOCKABLE, LABELED NONFUSED AC DISCONNECT (LOCATEDWITHIN 10' OF UTILITY METER)(N) BACKUP LOAD PANEL (MOUNTED ON BACKBOARD)(N) VISIBLE, LOCKABLE, LABELED NON FUSED PVAC DISCONNECT (MOUNTED ON BACKBOARD)(N) ENPHASE IQ SYSTEM CONTROLLER-2(MOUNTED ON BACKBOARD)(N) VISIBLE, LOCKABLE, LABELEDNON FUSED ESS AC DISCONNECT(MOUNTED ON BACKBOARD)(N) ENPHASE ENCHARGE 10-1P-NA BATTERY(MOUNTED ON BACKBOARD)(N) ENPHASE ENCHARGE 10-1P-NA BATTERY(MOUNTED ON BACKBOARD) REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWMICRO INVERTERCHARTMICRO INVERTER CHART1-1023411-2021-3031-4041-5051-60561-706789101PV-10 REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWEQUIPMENTSPECIFICATIONPV-11 REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWEQUIPMENTSPECIFICATIONPV-12 REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWEQUIPMENTSPECIFICATIONPV-13 REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWEQUIPMENTSPECIFICATIONPV-14 REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWEQUIPMENTSPECIFICATIONPV-15 REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWEQUIPMENTSPECIFICATIONPV-16 REVSHEET NAMESHEET SIZESHEET NUMBERHAROLD COPE RESIDENCE 1326 HONEY RUN ROAD, CHICO, CA 95928ANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAME & ADDRESSDATE:12/17/2021DRAWN BYESR2024 OPPORTUNITY DR.STE 150, ROSEVILLE, CA 95678TEL. (888) 414-8002CALIFORNIARENEWABLE ENERGYA06/02/2023CITY COMMENTSB06/28/2023CITY COMMENTSC06/30/2023AHJ COMMENTSD07/04/2023EQUIPMENTLOCATION CHANGEE07/20/2023FUTURE LEACHFIELD/TANK SHOWEQUIPMENTSPECIFICATIONPV-17