HomeMy WebLinkAboutFAI21-0014 078-240-023 7-2023 Recommendation- Organize the agriculture loft for means of egress.
Room 1702:
L_1 Recommendation- Organize storage for means of egress.
Items Discussed/Requested
Please provide the following:
I I Fire Drill Log
❑ Copy of Campus Emergency Plan including lockdown procedures
❑ Fire Alarm Systems- Annual testing and maintenance reports
❑ List of Campus Contacts
❑ Zone map for fire alarm
Ryan May
Fire Apparatus Engineer
CAL FIRE/ Butte County Fire Department
Palermo Fire Station
Office: (530) 538-7565
ISSUED BY: RECEIVED BY DATE
Ryan May �` 08/08/2023
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 1500 Staff Room:
O P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 1504:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of light
hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of ordinary hazard
fuel load. Travel distance shall not exceed 75 feet.
Student Store:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Grounds Shop:
O P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
•
Weight Room:
O P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Horticulture Lab:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Agricultural Shop:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 614:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 615:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 616:
❑ Recommendation- remove secondary extinguisher mount with no extinguisher.
Room 623:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 1017:
❑ P1 One Class 2-A rated fire extinguisher shall•be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 1019:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 1203:
•
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 2001:
Front office/ Copy Room:
❑ P1 A working space of not less than 30 inches in width, 36 inches in depth and 78
inches in height shall be provided in front of electrical service equipment. Storage is
prohibited within the designated working space.
Room 111:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 112:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 114:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 215:
O P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Room 313:
❑ P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
600 Hallway:
O P1 One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet.
Butte County Fire Department
CFIRE
�' Fire Prevention Bureau
176 Nelson Avenue Oroville, CA 95965
Office(530)538-7888 Butte County
www.buttecountv.net/fire
FIRE SAFETY CORRECTION NOTICE
FAI NUMBER PAGE OF PAGE
FA 121-0014 1 5
NAME : Las Plumas High School HOURS MINUTES
3 0
ADDRESS: 2380 Las Plumas Avenue
THE CALIFORNIA HEALTH AND SAFETY CODE AND THE STATE FIRE MARSHAL'S
REGULATIONS REQUIRE THE FOLLOWING FIRE SAFETY DEFICIENCIES BE CORRECTED:
Proiect Information
A required Fire Life and Safety inspection pursuant to Health and Safety Code § 13146.3 was
conducted on August 7th, 2023 at the above facility. During the inspection, I was accompanied by
Firefighter Charles Schindler. The following deficiencies are required to be repaired and/or corrected.
These deficiencies will be labeled as P1, P2 or P3 throughout this report.
P1: Highest priority, must be completed by Monday August 21st, 2023
P2: Second highest, priority and must be completed by Monday August 21st, 2023
P3: Third highest, priority and must be completed by Monday August 21st, 2023
Deficiencies
For all occupied rooms:
r, A working space of not less than 30 inches in width, 36 inches in depth and 78 inches
in height shall be provided in front of electrical service equipment. Storage is prohibited
within the designated working space. CFC 604.6
C One Class 2-A rated fire extinguisher shall be provided for each 3000 square feet of
light hazard fuel load or one Class 2-A extinguisher for each 1500 square feet of
ordinary hazard fuel load. Travel distance shall not exceed 75 feet. T19 567/568