HomeMy WebLinkAboutFAI15-0090 026-184-003 2023
FIRE SAFETY CORRECTION NOTICE
FAI NUMBER
PAGE
1
OF
PAGE
3
NAME: Christian Faith Center Palermo
HOURS
1
MINUTES
0
ADDRESS: 7695 Melvina Avenue
THE CALIFORNIA HEALTH AND SAFETY CODE AND THE STATE FIRE MARSHAL’S REGULATIONS REQUIRE THE FOLLOWING FIRE SAFETY DEFICIENCIES BE CORRECTED:
Project Information
A required Fire Life and Safety inspection pursuant to Health and Safety Code § 13146.3 was conducted on August 22nd, 2023 at the above facility. During the inspection, I was accompanied
by Firefighter Charles Schindler. The following deficiencies are required to be repaired and/or corrected. These deficiencies will be labeled as P1, P2 or P3 throughout this report.
P1: Highest priority, must be completed by Tuesday September 9th, 2023
P2: Second highest, priority and must be completed by Tuesday September 9th, 2023
P3: Third highest, priority and must be completed by Tuesday September 9th, 2023
Deficiencies
For all occupied rooms:
A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Storage is prohibited within
the designated working space. CFC 604.6
Extinguishers shall be subjected to maintenance annually as described in Title 19 CCR. With exceptions, this type of service does not require internal examination of the extinguisher.
T19 575.1
Daycare/Infant Room
P1 A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Storage is prohibited within
the designated working space. CFC 604.6
Hallway:
P1 A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Storage is prohibited within
the designated working space. CFC 604.6
All extinguishers on the property:
P1 Extinguishers shall be subjected to maintenance annually as described in Title 19 CCR. With exceptions, this type of service does not require internal examination of the extinguisher.
T19 575.1
Ryan May
Fire Apparatus Engineer
CAL FIRE/ Butte County Fire Department
Palermo Fire Station
Office: (530) 538-7565
ISSUED BY:
Ryan May
RECEIVED BY
Michael Harwell via Email
DATE
08/08/2023
Daycare/Infant Room
P1 A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Storage is prohibited within
the designated working space. CFC 604.6
Hallway:
P1 A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Storage is prohibited within
the designated working space. CFC 604.6
All extinguishers on the property:
P1 Extinguishers shall be subjected to maintenance annually as described in Title 19 CCR. With exceptions, this type of service does not require internal examination of the extinguisher.
T19 575.1
Project Information
A required Fire Life and Safety inspection pursuant to Health and Safety Code § 13146.3 was conducted on August 22nd, 2023 at the above facility. During the inspection, I was accompanied
by Firefighter Charles Schindler. The following deficiencies are required to be repaired and/or corrected. These deficiencies will be labeled as P1, P2 or P3 throughout this report.
P1: Highest priority, must be completed by Tuesday September 9th, 2023
P2: Second highest, priority and must be completed by Tuesday September 9th, 2023
P3: Third highest, priority and must be completed by Tuesday September 9th, 2023
Deficiencies
For all occupied rooms:
A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Storage is prohibited within
the designated working space. CFC 604.6
Extinguishers shall be subjected to maintenance annually as described in Title 19 CCR. With exceptions, this type of service does not require internal examination of the extinguisher.
T19 575.1
Daycare/Infant Room
P1 A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Storage is prohibited within
the designated working space. CFC 604.6
Hallway:
P1 A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Storage is prohibited within
the designated working space. CFC 604.6
All extinguishers on the property:
P1 Extinguishers shall be subjected to maintenance annually as described in Title 19 CCR. With exceptions, this type of service does not require internal examination of the extinguisher.
T19 575.1
Ryan May
Fire Apparatus Engineer
CAL FIRE/ Butte County Fire Department
Palermo Fire Station
Office: (530) 538-7565
ISSUED BY:
Ryan May
RECEIVED BY
Michael Harwell via Email
DATE
08/08/2023