Loading...
HomeMy WebLinkAboutB21-3505 041-230-009 CF FA 2023 in any form permitted without written permission of NFPASi.Far inquiries or to report unauthorized use.contact licensingianfpa.org. DOCUMENTATION 72-39 SYSTEM RECORD OF COMPLETION This form is to be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets, data,or calculations as necessary to provide a complete record. Form Completion bale: 7/21/2°22 Supplemental Pages Attached: N/A 1. PROPERTY INFORMATION Name of property: PG&E Table Mountain RPAC Substation Address: 945 Cottonwood Road.Oroville.California 95965 Description of property: Utility Name of property representative: Chase Chaussee Address: 945 Cottonwood Road,Oroville,California 95965 Phone: 1(530)635-4871 Fax: E-mail: 2. INSTALLATION,SERVICE,TESTING,AND MONITORING INFORMATION Installation contractor. Cusco Fire Protection Address' 4320 Anthony Court.Suite 8.Rocklin,CA 95677 Phone. 916-652.1306 Fax, 916.652.1307 E-mail: www,coscafire.com Costa Fire Protection Service organization: Address' 4320 Anthony Court,Suite 8.Rocklin,CA 95677 Phone. 916.652.1306 916.652.1307Fn E lwww.coscofire.com j Testing organization- Cusco Fire Protection • Address' 4320 Anthony Court.Suite 8,Rocidin.CA 95677 • Phone 916-652.1306 Fax- 916.652.1307 E-mail: www.coscofire.com Effective date for test and inspection contract: Monitoring organization: Address- Phone' FaY' E-mail- Account number: Phone line 1• Phone line 2: Means of transmission' Entity to which alarms are retransmitted: Phono- 3. DOCUMENTATION On-site location of the required record documents and site-specific softwar document can under FACP e 4. DESCRIPTION OF SYSTEM OR SERVICE • This is a: 1 New system J Modification to existing system Permit number: NFPA 72 edition: 4.1 Control Unit Manufacturer. Notifier Model number NFS-320 4.2 Software and Firmware Firmware revision number V29 4.3 Alarm Verification Ei This system does not incorporate alarm verification. Number of devices subject to alarm verification• Alarm verification set for seconds 2015 National Fire Protection Association NFPA 72(p.1 of 3) FIGURE 7.8.2(a) System Record of Completion. (SIG-FUN) 2016 Edition 6r arty farm perminad vMfiout written permission of NFPA®.For prgruries or to report unauthorized use,contact licensing@nfpa.org. 72—}() NATIONAL FIRE ALARM AND SIGNALING CADE SYSTEM RECORD OF COMPLETION (continued) 5. SYSTEM POWER 5.1 Control Unit 5.1.1 Primary Power Input voltage of control panel: 12OVAC Control panel amps: 3-9 Overcurrent protection: Type: Circuit Breaker Amps: 20A Branch circuit disconnecting means location: Panel 12 Number: Circuit 13 5.1.2 Secondary Power `Type of secondary power: Sealed Lead Add Battery Location,if remote from the plant: inside FACP Calculated capacity of secondary power to drive the system: In standby mode(hours): 24 Hours In alarm mode(minutes): 5 5.2 Control Unit J This system does not have power extender panels J Power extender panels are listed on supplementary sheet A B. CIRCUITS AND PATHWAYS Dual Media Separate Survivability Pathway Type Pathway Pathway Class Level Signaling Line I I ] g Device Power I I I N/A Initiating Device I I I g Notification Appliance I I I g Other(specify): 7. REMOTE ANNUNCIATORS Type I Location 8. INITIATING DEVICES Addressable or Alarm or Sensing Type Quantity Conventional Supervisory Technology Manual Pull Stations 1 Addressable I Alarm I switch Smoke Detectors 2 Addressable I Alarm I photoelectric Duct Smoke Detectors N/A I I Heat Detectors N/A I I I Gas Detectors N/A I I I Watertlow Switches I N/A I I Tamper Switches N/A I I I ®2015 National Fire Protection Association NFPA 72lp.2 of 3) FIGURE 7.8.2(a) Continued �w..� 2016 Edrtion in any form permitted without written permission of NFPA09.For inquiries or to report unauthorized use,contact kcensingainfpa.org. DOCUMENTATION 72-11 SYSTEM RECORD OF COMPLETION (continued) 9. NOTIFICATION APPLIANCES Type I Quantity I Description Audible I N/A I Visible I N/A I Combination Audible and Visible 1 2 I 1 qty ceiling mount red and 1 qty wall mount red weatherproof 10. SYSTEM CONTROL FUNCTIONS Type Quantity Hold-Open Door Releasing Devices N/A HVAC Shutdown 1 Fire/Smoke Dampers N/A Door Unlocking N/A Elevator Recall N/A Elevator Shunt Trip N/A • 11. INTERCONNECTED SYSTEMS el This system does not have interconnected systems. J Interconnected systems are listed on supplementary sheet . 12. CERTIFICATION AND APPROVALS 12.1 System Installation Contractor This system as s ifie in has been installed according to all NFPAFP standards cited herein. Signed: /I�� Printed name.,0417 Zr^ Date:/�-/4-P-j Organizati n:Go'SGa !�1 r-t- Title: e.I Phone: 916.652.13os 12.2 System Operational Test This system as specific, h in has tested according to all NFPA standards citeeddd herein. Signed: l//I�—� Printed name:/K�6�ar/�r f��i�1v24 Date/A" /4" /7 916.652-1306 Organization:��l O f/�-t- Title:fs.G� Phone: 12.3 Acceptance Test �.r� Date and time of acceptance test: /D/O // _ ! • YG / i Installing contractor representativ Testing contractor representative- Property representative: //� ,.. I�__ r f AH3 representative: Lam"\ I (�9 2015 National Fire Protection Association NFPA 72(p.3 of 3) FIGURE 7.8.2(a) Continued 2016 Edition a