HomeMy WebLinkAboutFAI20-0025 010-210-026 CF FA 2023-08-18 Gridley-High-School Fire Alarm and Life Safety System
Inspection Certificate
For
Gridley High School
300 East Spruce Street
Gridley, CA 95948
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages
of this report provide performance measurements, listed ranges of acceptable results, and complete
documentation of the inspection. Whenever discrepancies exist between acceptable performance
standards and actual test results, notes and/or recommended solutions have been proposed or provided
for immediate review and approval.
Annual Inspection
Inspection Date
Aug 18, 2023
Building: Gridley High School Company:Hue&Cry,Inc.
Contact:Jordan Reeves Contact: Chyna Reed
Title: Superintendent Title:Inspector
Fire Alarm Testing Report
Executive Summary
Generated by:BuildingReports.com
Building Information
Building: Gridley High School Contact: Jordan Reeves
Address: 300 East Spruce Street Phone: 1-530-846-4721
Address: Fax:
City/State/ZIP Code: Gridley, CA 95948 Mobile:
Country: United States of America Email:jreeves@gusd.org
Inspection Performed By
Company: Hue&Cry, Inc. Inspector: Chyna Reed
Address: 1751 Bruce Drive Phone: 530-356-7007
Address: Fax:
City/State/ZIP Code:Anderson, California 96007 Mobile:
Country: United States of America Email: c.reed@hueandcry.com
System Control Unit
Manufacturer: Fire-Lite Inspection Date: 08/18/2023 IDC Style: B
Model Number: MS-10US Install Date: 07/21/2010 SLC Style:
Software Version: Version Date: 07/21/2010 NAC Style: Y
Location: Office Conference Room Current Protection: Breaker
Disconnect Location: Office Conference Room Type: Breaker
Hue&Cry,Inc. Page 2 of 12 Download Date:08/21/2023
Executive Summary
Inspection Summary
Total Items Serviced Passed Failed/Other
Category:
Qty % Qty % Qty % Qty %
Control 8 16.33% 8 100.00% 8 100.00% 0 0.00%
Indicating 19 38.78% 19 100.00% 11 57.89% 8 42.11%
Initiating 22 44.90% 22 100.00% 17 77.27% 5 22.73%
Totals 49 100% 49 100.00% 36 73.47% 13 26.53%
Certification
Company: Hue&Cry, Inc. Building: Gridley High School
Inspector: Chyna Reed Contact: Jordan Reeves
Signed: Aug 18, 2023 Signed:Aug 18, 2023
Hue&Cry,Inc. Page 3 of 12 Download Date:08/21/2023
Executive Summary
Discrepancy Report
Generated by:BuildingReports.com
Building: Gridley High School Control Panel: 1 - Fire-Lite MS-10US
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience.Any item that was inspected that is subject to a recall or part
of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade
Pull Station Fire-Lite BG-10 04/01/2013 1
ScaniD Location Problem Address Reference
Indicating
Horn
2 13975291 400 Wing West Side Failed 1 NFPA72 14.2.2.2.2
Annunciation
1 13975997 Boys Locker Room Special Note 1 NFPA72 14.2.2.2.2
1 13975285 Floral shop Special Note 1 NFPA72 14.2.2.2.2
1 13975993 Girls Locker Room Special Note 1 NFPA72 14.2.2.2.2
1 13975995 Outside Locker Room North Special Note 1 NFPA72 14.2.2.2.2
1 13975283 Wood Shop Special Note 1 NFPA72 14.2.2.2.2
1 13975272 portable 603 Special Note 1 NFPA72 14.2.2.2.2
Horn/Strobe
1 13975287 N/E Portable Special Note 1 NFPA72 14.2.2.2.2
Initiating
Pull Station
1 13975996 Boys Locker Room Special Note 1 NFPA72 14.2.2.2.2
1 60670342 Floral shop Special Note 1 NFPA72 14.2.2.2.2
1 13975994 Girls Locker Room Special Note 1 NFPA72 14.2.2.2.2
1 13975288 N/E Portable Room 603 Special Note 1 NFPA72 14.2.2.2.2
1 13975284 Wood Shop Special Note 1 NFPA72 14.2.2.2.2
Code References
NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
Hue&Cry,Inc. Page 4 of 12 Download Date:08/21/2023
Discrepancy Report
Proposed Solutions Report
Generated by:BuildingReports.com
Building: Gridley High School Control Panel: 1 - Fire-Lite MS-10US
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check
mark where indicated to approve repairs listed within the report.Items listed as T/M are available for repair on a Time
and Materials basis.
ScaniD Location Solution Model# Cost Fix
Indicating
Horn
13975291 400 Wing West Side Investigate SC806A1004 T/M ❑
13975997 Boys Locker Room See notes 4040 T/M ❑
/recommendations
13975285 Floral shop See notes SC806A1004 T/M ❑
/recommendations
13975993 Girls Locker Room See notes 4040 T/M ❑
/recommendations
13975995 Outside Locker Room North See notes 31T-115 T/M ❑
/recommendations
13975283 Wood Shop See notes SC806A1004 T/M ❑
/recommendations
13975272 portable 603 See notes MT-24R T/M ❑
/recommendations
Horn/Strobe
13975287 N/E Portable See notes NS-24MCW T/M ❑
/recommendations
Initiating
Pull Station
13975996 Boys Locker Room See notes 4251-1 125v T/M ❑
/recommendations
60670342 Floral shop See notes S46A1045 T/M ❑
/recommendations
13975994 Girls Locker Room See notes 4251-1 125v T/M ❑
/recommendations
13975288 N/E Portable Room 603 See notes 2099-9101 T/M ❑
/recommendations
13975284 Wood Shop See notes S46A1045 T/M ❑
/recommendations
PO#: (none) T/M
Hue&Cry,Inc. Page 5 of 12 Download Date:08/21/2023
Proposed Solutions Report
Notes & Recommendations
Generated by:BuildingReports.com
Building: Gridley High School
The Notes&Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection.Notes are grouped by Category.
General Note
Pull station &Horns in the 600, 700&locker room buildings are disconnected due to construction
Horn 400 W Wing did not sound
Hue&Cry,Inc. Page 6 of 12 Download Date:08/21/2023
Notes&Recommendations
Inspection & Testing
Generated by:BuildingReports.com
Building: Gridley High School Control Panel: 1 - Fire-Lite MS-10US
The Inspection& Testing section lists all of the items inspected in your building.Items are grouped by Passed or
Failed/Other.Items are listed by Category. Each item includes the services performed, and the time&date at which testing
occurred.
Device Type Location Service Time Date
Passed
Control
Battery 10th Below Connector Cell Room 211 Annual 8:19:54 AM 08/18/2023
Power Supply
Battery FACP Annual 8:14:48 AM 08/18/2023
Battery FACP Left Batt Annual 8:13:21 AM 08/18/2023
Battery Room 211 Power Supply Annual 8:19:45 AM 08/18/2023
Control Panel Office Conference Room Annual 8:44:56 AM 08/18/2023
Disconnect Room 211 #14A Annual 8:24:15 AM 08/18/2023
Disconnect Staff Break Room Hall -C/B A2#2 Annual 9:53:21 AM 08/18/2023
Power Supply Room 211 above Ceiling Tile Annual 8:44:44 AM 08/18/2023
Indicating
Bell Office Hall Annual 9:53:24 AM 08/18/2023
Horn 200 Wing East Annual 9:51:17 AM 08/18/2023
Horn 200 Wing West Annual 9:51:20 AM 08/18/2023
Horn 300 Wing Annual 9:51:24 AM 08/18/2023
Horn 400 Wing North Side Annual 9:51:41 AM 08/18/2023
Horn Leadership Bldg Annual 9:50:18 AM 08/18/2023
Horn Library Hall Annual 9:51:27 AM 08/18/2023
Horn Room 209 Outside Annual 9:53:01 AM 08/18/2023
Horn Team Room Annual 9:51:14 AM 08/18/2023
Horn/Strobe Room 209 Annual 9:49:41 AM 08/18/2023
Horn/Strobe Room 211 Annual 9:49:37 AM 08/18/2023
Initiating
Pull Station 100 Wing Outside Annual 8:53:07 AM 08/18/2023
Pull Station 200 Wing East Annual 8:51:54 AM 08/18/2023
Pull Station 200 Wing West Annual 8:49:01 AM 08/18/2023
Pull Station 300 Wing Annual 9:21:13 AM 08/18/2023
Pull Station 400 Wing East Annual 9:02:37 AM 08/18/2023
Pull Station 400 Wing West Annual 9:47:01 AM 08/18/2023
Pull Station Leadership Bldg Annual 9:31:20 AM 08/18/2023
Hue&Cry,Inc. Page 7 of 12 Download Date:08/21/2023
Inspection&Testing
Device Type Location Service Time Date
Passed
Pull Station Library Hall East Annual 9:00:03 AM 08/18/2023
Pull Station Library Hall West Annual 9:37:43 AM 08/18/2023
Pull Station Office Hall Annual 9:25:29 AM 08/18/2023
Pull Station Room 209 Annual 8:44:37 AM 08/18/2023
Pull Station Room 211 Annual 8:29:56 AM 08/18/2023
Pull Station Team Room Annual 9:49:11 AM 08/18/2023
Smoke Detector Room 209 Annual 8:44:24 AM 08/18/2023
Smoke Detector Room 209 Annual 8:44:28 AM 08/18/2023
Smoke Detector Room 211 Annual 8:31:12 AM 08/18/2023
Smoke Detector Room 211 Annual 8:44:18 AM 08/18/2023
Device Type Location Service Time Date
Failed/Other
Indicating
2 Horn 400 Wing West Side Annual 9:52:23 AM 08/18/2023
1 Horn Boys Locker Room Annual 9:50:43 AM 08/18/2023
1 Horn Floral shop Annual 9:52:39 AM 08/18/2023
1 Horn Girls Locker Room Annual 9:53:48 AM 08/18/2023
1 Horn Outside Locker Room North Annual 9:51:09 AM 08/18/2023
1 Horn Wood Shop Annual 9:52:53 AM 08/18/2023
1 Horn portable 603 Annual 9:53:15 AM 08/18/2023
1 Horn/Strobe N/E Portable Annual 9:49:59 AM 08/18/2023
Initiating
1 Pull Station Boys Locker Room Annual 9:33:25 AM 08/18/2023
1 Pull Station Floral shop Annual 9:33:42 AM 08/18/2023
1 Pull Station Girls Locker Room Annual 9:34:00 AM 08/18/2023
1 Pull Station N/E Portable Room 603 Annual 9:34:38 AM 08/18/2023
1 Pull Station Wood Shop Annual 9:34:23 AM 08/18/2023
Hue&Cry,Inc. Page 8 of 12 Download Date:08/21/2023
Inspection&Testing
Service Summary
Generated by:BuildingReports.com
Building: Gridley High School
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other
Horn/Strobe Annual 1
Horn Annual 7
Pull Station Annual 5
Total 13
Passed
Battery Annual 4
Bell Annual 1
Control Panel Annual 1
Disconnect Annual 2
Horn/Strobe Annual 2
Horn Annual 8
Power Supply Annual 1
Pull Station Annual 13
Smoke Detector Annual 4
Total 36
Grand Total 49
Hue&Cry,Inc. Page 9 of 12 Download Date:08/21/2023
Service Summary
Battery & Power Supply Testing
Generated by:BuildingReports.com
Building: Gridley High School Control Panel: 1 - Fire-Lite MS-10US
The Battery&Power Supply Testing section details the readings and measurements of batteries and power supplies used
to provide power to the fire alarm and life safety systems.Items are grouped by Passed or Failed/Other.
Rated Rated Post
Type Location Ah Volts Pre Test Test Min Ah Tested Ah
Battery
Passed
Sealed Lead Acid 10th Below Connector Cell 7 12 13.04 4.55 7.8
Room 211 Power Supply
Sealed Lead Acid FACP 18 12 12.97 7.80 19
Sealed Lead Acid FACP Left Batt 18 12 12.97 7.80 24
Sealed Lead Acid Room 211 Power Supply 7 12 13.16 4.55 7.8
Hue&Cry,Inc. Page 10 of 12 Download Date:08/21/2023
Battery&Power Supply Testing
Inventory & Warranty Report
Generated by:BuildingReports.com
Building: Gridley High School Control Panel: 1 - Fire-Lite MS-10US
The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report.A
complete inventory count by device type and category is provided.Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Catego %of Inventory Quantity
Battery Control 8.16% 4
Bell Indicating 2.04% 1
Control Panel Control 2.04% 1
Disconnect Control 4.08% 2
Horn Indicating 30.61% 15
Horn/Strobe Indicating 6.12% 3
Power Supply Control 2.04% 1
Pull Station Initiating 36.73% 18
Smoke Detector Initiating 8.16% 4
Type Qty Model# Description Install Date
In Service - 90 Days - 1 Year
Ultra Tech
Battery 1 PS-1270F1 Sealed Lead Acid 02/21/2023
In Service- 3 Years to 5 Years
Power-Sonic
Battery 2 PS-12180NB Sealed Lead Acid 04/20/2020
In Service - 5 Years to 10 Years
Power-Sonic
Battery 1 PS-1270F1 Sealed Lead Acid 10/21/2014
In Service- 10 Years to 15 Years
Altronix
Power Supply 1 AL3000LXR 07/21/2010
Detection Systems
Smoke Detector 4 DS282 Photoelectric 07/21/2010
Fire Lite
Pull Station 1 BG-12L0 Single Action 07/21/2010
Fire-Lite
Control Panel 1 MS-10US 07/21/2010
Pull Station 1 BG-10 Dual Action 07/21/2010
Pull Station 3 BG-12 Dual Action 07/21/2010
Honeywell
Horn 8 SC806A1004 07/21/2010
Pull Station 6 S464A1045 Single Action 07/21/2010
Hue&Cry,Inc. Page 11 of 12 Download Date:08/21/2023
Inventory&Warranty Report
Pull Station 3 S46A1045 Single Action 07/21/2010
Modtech
Disconnect 1 15amp Breaker 07/21/2010
SimplexGrinnell
Horn 3 4040 07/21/2010
Pull Station 1 2099-9101 Single Action 07/21/2010
Pull Station 3 4251-1 125v Single Action 07/21/2010
Square D
Disconnect 1 20amp Breaker 07/21/2010
System Sensor
Horn 1 H12/24K 07/21/2010
Horn/Strobe 2 P2R 07/21/2010
Unknown
Bell 1 12" 07/21/2010
Wheelock
Horn 1 31T-115 07/21/2010
Horn 1 34-24 07/21/2010
Horn 1 MT-24R 07/21/2010
Horn/Strobe 1 NS-24MCW 07/21/2010
Hue&Cry,Inc. Page 12 of 12 Download Date:08/21/2023
Inventory&Warranty Report