HomeMy WebLinkAboutFAI22-0003 010-051-001 CF FA 8-21-2023_McKinley-Elementary-School Fire Alarm and Life Safety System
Inspection Certificate
For
McKinley Elementary School
1045 Sycamore Street
Gridley, CA 95948
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages
of this report provide performance measurements, listed ranges of acceptable results, and complete
documentation of the inspection. Whenever discrepancies exist between acceptable performance
standards and actual test results, notes and/or recommended solutions have been proposed or provided
for immediate review and approval.
Annual Inspection
Inspection Date
Aug 21, 2023
Building:McKinley Elementary School Company:Hue&Cry,Inc.
Contact: Jordan Reeves Contact: Chyna Reed
Title: Superintendent Title: Inspector
Fire Alarm Testing Report
Executive Summary
Generated by:BuildingReports.com
Building Information
Building: McKinley Elementary School Contact: Jordan Reeves
Address: 1045 Sycamore Street Phone: 1-530-846-4721
Address: Fax:
City/State/ZIP Code: Gridley, CA 95948 Mobile:
Country: United States of America Email:jreeves@gusd.org
Inspection Performed By
Company: Hue&Cry, Inc. Inspector: Chyna Reed
Address: 1751 Bruce Drive Phone: 530-356-7007
Address: Fax:
City/State/ZIP Code:Anderson, California 96007 Mobile:
Country: United States of America Email: c.reed@hueandcry.com
System Control Unit
Manufacturer: Silent Knight Inspection Date: 08/21/2023 IDC Style: B
Model Number: 5820XL Install Date: 01/31/2005 SLC Style:4
Software Version: 9.08 Version Date: 05/11/2007 NAC Style: Y
Location: Rear Electrical Room in Electric Box Current Protection: Breaker
Disconnect Location: Rear Electrical Room in Electric Box Type: Breaker
Hue&Cry,Inc. Page 2 of 13 Download Date:08/22/2023
Executive Summary
Inspection Summary
Total Items Serviced Passed Failed/Other
Category:
Qty % Qty % Qty % Qty %
Auxiliary 1 1.54% 1 100.00% 1 100.00% 0 0.00%
Control 8 12.31% 8 100.00% 8 100.00% 0 0.00%
Indicating 17 26.15% 17 100.00% 17 100.00% 0 0.00%
Initiating 38 58.46% 38 100.00% 38 100.00% 0 0.00%
Monitor 1 1.54% 1 100.00% 1 100.00% 0 0.00%
Totals 65 100% 65 100.00% 65 100.00% 0 0.00%
Certification
Company: Hue&Cry, Inc. Building: McKinley Elementary School
Inspector: Chyna Reed Contact: Jordan Reeves
(_,-' 1 -AU-74--
Signed: Aug 21, 2023 Signed:Aug 21, 2023
Hue&Cry,Inc. Page 3 of 13 Download Date:08/22/2023
Executive Summary
Notes & Recommendations
Generated by:BuildingReports.com
Building: McKinley Elementary School
The Notes&Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection.Notes are grouped by Category.
General Note
Battery is room 3 power supply replaced&approved by Adrianna
Hue&Cry,Inc. Page 4 of 13 Download Date:08/22/2023
Notes&Recommendations
Inspection & Testing
Generated by:BuildingReports.com
Building: McKinley Elementary School Control Panel: 1 - Silent Knight 5820XL
The Inspection& Testing section lists all of the items inspected in your building.Items are grouped by Passed or
Failed/Other.Items are listed by Category. Each item includes the services performed, and the time&date at which testing
occurred.
Device Type Location Service Time Date
Passed
Auxiliary
Lighting Control Room 12 Above Tile North End Annual 1:27:49 PM 08/21/2023
Control
Annunciator Main Hall East by Custodian Room Annual 1:09:53 PM 08/21/2023
Battery FACP Annual 11:57:19 AM 08/21/2023
Battery FACP Annual 11:57:44 AM 08/21/2023
Battery Room 3 Replaced 1:18:45 PM 08/21/2023
Battery Room 3 Replaced 1:18:51 PM 08/21/2023
Control Panel Rear Electrical Room in Electric Box Annual 11:58:40 AM 08/21/2023
Disconnect Rear Electrical Room in Electric Box Annual 11:59:02 AM 08/21/2023
Voice Evacuation Room 3 Annual 12:10:01 PM 08/21/2023
Indicating
Horn East Playground Annual 1:10:25 PM 08/21/2023
Horn South Outside Electrical Room Annual 1:10:30 PM 08/21/2023
Horn West Playground Annual 1:10:21 PM 08/21/2023
Horn Room 2 Annual 1:10:18 PM 08/21/2023
Horn/Strobe Main Hall East Annual 1:06:41 PM 08/21/2023
Horn/Strobe Main Hall West Annual 1:06:47 PM 08/21/2023
Horn/Strobe Room 12 Annual 1:07:02 PM 08/21/2023
Horn/Strobe Room 14 Annual 1:06:58 PM 08/21/2023
Horn/Strobe Room 15 Annual 1:06:54 PM 08/21/2023
Horn/Strobe Room 16 ELO2 4.7k resistor 25.7v Annual 1:06:50 PM 08/21/2023
Speaker/Strobe Restroom 1 Annual 12:32:34 PM 08/21/2023
Speaker/Strobe Room 2 Annual 12:50:37 PM 08/21/2023
Speaker/Strobe Room 3 Annual 12:50:44 PM 08/21/2023
Speaker/Strobe Room1 Annual 12:50:41 PM 08/21/2023
Speaker/Strobe Women Restroom Annual 12:28:14 PM 08/21/2023
Speaker/Strobe Work Room Annual 12:50:34 PM 08/21/2023
Strobe Room 3 Bathroom Annual 12:50:48 PM 08/21/2023
Initiating
Hue&Cry,Inc. Page 5 of 13 Download Date:08/22/2023
Inspection&Testing
Device Type Location Service Time Date
Passed
Heat Detector Portable restroom above ceiling Annual 1:07:57 PM 08/21/2023
Heat Detector Room 1 Above Tile Annual 1:07:07 PM 08/21/2023
Heat Detector Room 12 Above Tile South End Annual 1:09:17 PM 08/21/2023
Heat Detector Room 14 Above Tile North End Annual 1:09:40 PM 08/21/2023
Heat Detector Room 14 Above Tile South End Annual 1:09:20 PM 08/21/2023
Heat Detector Room 15 Above Tile North End Annual 1:09:36 PM 08/21/2023
Heat Detector Room 15 Above Tile South End Annual 1:09:23 PM 08/21/2023
Heat Detector Room 16 Above Tile North End Annual 1:09:32 PM 08/21/2023
Heat Detector Room 16 Above Tile South End Annual 1:09:29 PM 08/21/2023
Heat Detector Room 2 Above Tile Annual 1:07:11 PM 08/21/2023
Heat Detector Room 3 Above Tile Annual 1:07:14 PM 08/21/2023
Heat Detector Work Room @rooml Annual 1:08:00 PM 08/21/2023
Pull Station Main Hall East by Room 8 Annual 1:26:50 PM 08/21/2023
Pull Station Main Hall West by Room 6 Annual 1:26:47 PM 08/21/2023
Pull Station Room 1 Annual 1:05:52 PM 08/21/2023
Pull Station Room 2 Annual 1:05:57 PM 08/21/2023
Pull Station Room 3 Annual 1:05:55 PM 08/21/2023
Pull Station West Playground Annual 12:22:30 PM 08/21/2023
Pull Station Work Room @rooml Annual 1:06:01 PM 08/21/2023
Smoke Detector Restroom Annual 12:31:45 PM 08/21/2023
Smoke Detector Room 1 Annual 12:47:37 PM 08/21/2023
Smoke Detector Room 1 Annual 12:47:40 PM 08/21/2023
Smoke Detector Room 12 West Annual 1:05:43 PM 08/21/2023
Smoke Detector Room 14 East Annual 1:02:45 PM 08/21/2023
Smoke Detector Room 14 West Annual 1:02:41 PM 08/21/2023
Smoke Detector Room 15 East Annual 12:57:45 PM 08/21/2023
Smoke Detector Room 15 West Annual 12:57:48 PM 08/21/2023
Smoke Detector Room 16 East Annual 12:57:41 PM 08/21/2023
Smoke Detector Room 16 West Annual 12:57:38 PM 08/21/2023
Smoke Detector Room 2 Annual 12:47:43 PM 08/21/2023
Smoke Detector Room 2 Annual 12:47:46 PM 08/21/2023
Smoke Detector Room 3 Annual 12:47:51 PM 08/21/2023
Smoke Detector Room 3 Annual 12:47:53 PM 08/21/2023
Smoke Detector Women Restroom Annual 12:28:03 PM 08/21/2023
Smoke Detector Work Room @rooml Annual 12:50:26 PM 08/21/2023
Smoke Detector Work Room @rooml Annual 12:50:29 PM 08/21/2023
Smoke Detector Room 12 East Annual 1:05:46 PM 08/21/2023
Hue&Cry,Inc. Page 6 of 13 Download Date:08/22/2023
Inspection&Testing
Device Type Location Service Time Date
Passed
Smoke Detector Room 3 restroom Annual 12:34:47 PM 08/21/2023
Monitor
Monitor Device Room 3 Annual 12:10:21 PM 08/21/2023
Hue&Cry,Inc. Page 7 of 13 Download Date:08/22/2023
Inspection&Testing
Service Summary
Generated by:BuildingReports.com
Building: McKinley Elementary School
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed
Annunciator Annual 1
Battery Annual 2
Battery Replaced 2
Control Panel Annual 1
Disconnect Annual 1
Heat Detector Annual 12
Horn/Strobe Annual 6
Horn Annual 4
Lighting Control Annual 1
Monitor Device Annual 1
Pull Station Annual 7
Smoke Detector Annual 19
Speaker/Strobe Annual 6
Strobe Annual 1
Voice Evacuation Annual 1
Total 65
Grand Total 65
Hue&Cry,Inc. Page 8 of 13 Download Date:08/22/2023
Service Summary
Auxiliary Functions Testing
Generated by:BuildingReports.com
Building: McKinley Elementary School Control Panel: 1 - Silent Knight 5820XL
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are
controlled by the system control unit.Items are grouped by Passed or Failed/Other. The items are listed by device type,
and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScaniD Simulated
Passed
Lighting Control
Room 12 Above Tile North End Passed 11531210 ❑
Smoke Detector
Smoke Compartment Restroom Passed 51368394
Smoke Compartment Room 1 Passed 46435456
Smoke Compartment Room 1 Passed 46435455
Smoke Compartment Room 12 West Passed 11531212
Smoke Compartment Room 14 East Passed 11531215
Smoke Compartment Room 14 West Passed 11531217
Smoke Compartment Room 15 East Passed 11531219
Smoke Compartment Room 15 West Passed 11531218
Smoke Compartment Room 16 East Passed 11531224
Smoke Compartment Room 16 West Passed 11531225
Smoke Compartment Room 2 Passed 46435453
Smoke Compartment Room 2 Passed 46435452
Smoke Compartment Women Restroom Passed 51368393
Smoke Compartment Work Room @rooml Passed 51368403
Smoke Compartment Work Room @rooml Passed 51368402
Smoke Compartment Room 12 East Passed 11531211
Smoke Compartment Room 3 restroom Passed 51368401
Hue&Cry,Inc. Page 9 of 13 Download Date:08/22/2023
Auxiliary Functions Testing
Battery & Power Supply Testing
Generated by:BuildingReports.com
Building: McKinley Elementary School Control Panel: 1 - Silent Knight 582OXL
The Battery&Power Supply Testing section details the readings and measurements of batteries and power supplies used
to provide power to the fire alarm and life safety systems.Items are grouped by Passed or Failed/Other.
Rated Rated Post
Type Location Ah Volts Pre Test Test Min Ah Tested Ah
Battery
Passed
Sealed Lead Acid FACP 7 12 12.66 4.55 11
Sealed Lead Acid FACP 7.0 12 12.66 4.55 11
Sealed Lead Acid Room 3 8 12 12.66 4.55 4.6
Sealed Lead Acid Room 3 8 12 12.62 4.55 4.2
Hue&Cry,Inc. Page 10 of 13 Download Date:08/22/2023
Battery&Power Supply Testing
Inventory & Warranty Report
Generated by:BuildingReports.com
Building: McKinley Elementary School Control Panel: 1 - Silent Knight 5820XL
The Inventory& Warranty Report lists each of the devices and items that are included in your Inspection Report.A
complete inventory count by device type and category is provided.Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Catego %of Inventory Quantity
Annunciator Control 1.54% 1
Battery Control 6.15% 4
Control Panel Control 1.54% 1
Disconnect Control 1.54% 1
Heat Detector Initiating 18.46% 12
Horn Indicating 6.15% 4
Horn/Strobe Indicating 9.23% 6
Lighting Control Auxiliary 1.54% 1
Monitor Device Monitor 1.54% 1
Pull Station Initiating 10.77% 7
Smoke Detector Initiating 29.23% 19
Speaker/Strobe Indicating 9.23% 6
Strobe Indicating 1.54% 1
Voice Evacuation Control 1.54% 1
Type Qty Model# Description Install Date
In Service - 2 Years to 3 Years
Duracell
Battery 2 12-8F2 Sealed Lead Acid 01/04/2021
In Service - 3 Years to 5 Years
Power-Sonic
Battery 2 PS 1270-F1 Sealed Lead Acid 11/19/2018
In Service - 5 Years to 10 Years
Fire-Lite
Pull Station 1 BG-12LO/SD500- Dual Action 11/13/2014
MIM
In Service- 15 Years to 25 Years
Cutler/Hammer
Disconnect 1 20amp Breaker 01/31/2005
Silent Knight
Annunciator 1 5860 01/31/2005
Control Panel 1 5820XL 01/31/2005
Monitor Device 1 SD500-ARM Relay 01/31/2005
Pull Station 6 SD500-PS Single Action 01/31/2005
Smoke Detector 8 SD505-APS Photoelectric 01/31/2005
Hue&Cry,Inc. Page 11 of 13 Download Date:08/22/2023
Inventory&Warranty Report
Smoke Detector 2 SD505-PHOTO 01/31/2005
Smoke Detector 9 SD505-PHOTO Photoelectric 01/31/2005
System Sensor
Heat Detector 12 5602 Combination 01/31/2005
Lighting Control 1 5602 01/31/2005
Wheelock
Horn 1 01/31/2005
Horn 3 AH-24WP 01/31/2005
Horn/Strobe 6 AS24-MCW 01/31/2005
Speaker/Strobe 6 LSPSTR 01/31/2005
Strobe 1 LSPSTR 01/31/2005
Voice Evacuation 1 SP40S 01/31/2005
Hue&Cry,Inc. Page 12 of 13 Download Date:08/22/2023
Inventory&Warranty Report
Zone Address Report
Generated by:BuildingReports.com
Building: McKinley Elementary School Control Panel: 1 - Silent Knight 5820XL
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a
common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScaniD
Zone/Circuit: 01-
1 Heat Detector Room 12 Above Tile South End Combination 16404062
Zone/Circuit: 02-
1 Lighting Control Room 12 Above Tile North End 11531210
1 Heat Detector Room 14 Above Tile North End Combination 11531214
2 Heat Detector Portable restroom above ceiling Combination 56777923
2 Heat Detector Room 1 Above Tile Combination 56777930
2 Heat Detector Room 14 Above Tile South End Combination 16404061
2 Heat Detector Room 2 Above Tile Combination 56777929
2 Heat Detector Room 3 Above Tile Combination 56777928
2 Heat Detector Work Room @rooml Combination 56777921
Zone/Circuit: 03-
1 Heat Detector Room 15 Above Tile South End Combination 16404060
2 Heat Detector Room 15 Above Tile North End Combination 11531221
3 Heat Detector Room 16 Above Tile North End Combination 11531222
4 Heat Detector Room 16 Above Tile South End Combination 16404059
Zone/Circuit: 05-
Smoke Detector Room 12 West Photoelectric 11531212
Zone/Circuit: 06-
Smoke Detector Work Room @rooml Photoelectric 51368402
Smoke Detector Work Room @rooml Photoelectric 51368403
Smoke Detector Room 12 East Photoelectric 11531211
Smoke Detector Room 3 restroom Photoelectric 51368401
Zone/Circuit: M33
P015 Pull Station West Playground Dual Action 32021985
07 Smoke Detector Room 14 West Photoelectric 11531217
08 Smoke Detector Room 14 East Photoelectric 11531215
09 Smoke Detector Room 15 East Photoelectric 11531219
10 Smoke Detector Room 15 West Photoelectric 11531218
11 Smoke Detector Room 16 West Photoelectric 11531225
12 Smoke Detector Room 16 East Photoelectric 11531224
Hue&Cry,Inc. Page 13 of 13 Download Date:08/22/2023
Zone Address Report