HomeMy WebLinkAbout3.ADM23-0025_PlansHAILLE RDHAILLE RDVICINITY MAPSCALE: NTSSCOPE OF WORK:RENEWABLE SOLAR TO INSTALL 1088.1 KW (DC) GRID TIED PV SYSTEMTOTALING (1674) CANADIAN SOLAR, INC. #CS7N-650MB-AG MODULES WITH(15) CHINT POWER SYSTEMS AMERICA #CPS-SCA-60KTL-DO/US-480INVERTERS. THE PV SYSTEM WILL BE GROUND MOUNTED. SOLAR TOATTACH TO AN EXISTING SERVICE.PV SYSTEM INFORMATION:SYSTEM SIZE:1088.1 KW (DC); 900.0 KW (AC); 997.908228 KW CEC (AC)MODULES:(1674) CANADIAN SOLAR, INC. #CS7N-650MB-AGINVERTER(S):(15) CHINT POWER SYSTEMS AMERICA#CPS-SCA-60KTL-DO/US-480RACKING:SOLAR FLEXRACK GFT SERIES G3P-XINSTALL:PILE DRIVEN GROUND MOUNTPITCH:20°AZIMUTH:180°DESIGN CRITERIA:ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL COMPLYWITH THE FOLLOWING AS APPLICABLE:2022 CEC; 2022 CBC; 2021 IRC; 2023 NEC; 2022 CRC; 2021 UMC, 2021 UPC;2021 IFC; 2022 CFC; 2022 BUILDING EFFICIENCY STANDARDS; AUTHORITYHAVING JURISDICTION (AHJ), FIRE AUTHORITY HAVING JURISDICTIONAND ALL MANUFACTURER INSTRUCTIONS AND LISTINGS.MODULES SHALL CONFORM TO AND ARE LISTED UNDER UL 1703INVERTERS SHALL CONFORM TO AND ARE LISTED UNDER UL 1741-SARACKING SHALL CONFORM TO AND IS LISTED UNDER UL2703INTENDED USE:THE PV SYSTEM WILL BE CONNECTED TO AN EXISTING SERVICE TOOFFSET THE ELECTRICAL USAGE OF ALL METERS LISTED IN THECUSTOMER'S UTILITY NEMA APPLICATION.SHEET INDEX:TITLE:SHEET NO.:COVER SHEETPV1.0SOLAR PV NOTESPV2.0OVERALL SITE PLANPV3.0ENLARGED SITE PLANPV3.1SINGLE LINE DIAGRAMPV4.0CONNECTION DETAILSPV4.1ELECTRICAL DETAILSPV4.2ELECTRICAL NOTES AND PV SIGNAGEPV5.0REFERENCESR1.0 - R1.4SOLAR FLEXRACK STRUCTURAL DRAWINGSS0 - S6BALLARD 2 (#3153)AGRICULTURAL PV GROUND MOUNT INSTALLGENERAL NOTES:1.THIRD PARTY POST INSPECTION REQUIRED. TEN PERCENT (10%) OFPOSTS TO BE INSPECTED UNLESS OTHERWISE NOTED.2.SEE SOLAR FLEXRACK DRAWINGS FOR STRUCTURAL DESIGNPARAMETERS.3.WILLIAMSON ACT DOES APPLY TO PARCEL 047-010-006-000.BUTTE COUNTY NOTES:1.A CHEMICAL TOILET IS REQUIRED ON-SITE DURING CONSTRUCTION, CBC 3305.12.A DEFERRED SUBMITTAL FOR FIRE PROTECTION DISTRICT APPROVAL MUST BE OBTAINEDPRIOR TO FRAME OR SIMILAR INSPECTION. PROVIDE EVIDENCE OF FIRE PROTECTIONDISTRICT APPROVAL3.ALL SHEETS OF THE CONSTRUCTION DRAWINGS SHALL BE "WET SIGNED" BY THE PERSONRESPONSIBLE FOR THE DESIGN, CRC R301.1.3.1. THE REGISTERED DESIGN PROFESSIONALSHALL STAMP AND SIGN STRUCTURAL PLANS, STRUCTURAL CALCULATIONS ANDSTRUCTURAL DETAIL SHEETS4.ALL SPECIAL INSPECTION REPORTS MUST BE SUBMITTED TO AHJ OFFICE PRIOR TO FINALINSPECTION5.CONSTRUCTION WASTE MANAGEMENT PLAN MUST BE FINALIZED PRIOR TO OCCUPANCY6.DRIVEN DEEP FOUNDATIONS. SPECIAL INSPECTIONS AND TESTS SHALL BE PERFORMEDDURING INSTALLATION OF DRIVEN DEEP FOUNDATION ELEMENTS AS SPECIFIED IN TABLE1705A.7. THE APPROVED GEOTECHNICAL REPORT AND THE CONSTRUCTION DOCUMENTSPREPARED BY THE REGISTERED DESIGN PROFESSIONALS SHALL BE USED TO DETERMINECOMPLIANCE, CBC 1705A.77.DRIVEN DEEP FOUNDATIONS OBSERVATION. THE INSTALLATION OF DRIVEN DEEPFOUNDATIONS SHALL BE CONTINUOUSLY OBSERVED BY A QUALIFIED REPRESENTATIVE OFTHE GEOTECHNICAL ENGINEER RESPONSIBLE FOR THAT PORTION OF THE PROJECT, CBC1705A.7.18.GROUND FAULT PROTECTION MUST BE PROVIDED FOR NEW EQUIPMENT RATED 150 - 1,000VOLTS. PERFORMANCE TESTING RESULTS BY AN APPROVED TESTING AGENCY MUST BESUBMITTED TO AHJ OFFICE PRIOR TO THE SERVICE BEING ENERGIZED, CEC SECTION 215.109.THE REPRESENTATIVE OF THE GEOTECHNICAL ENGINEER SHALL MAKE A REPORT OF THEDEEP FOUNDATION PILE-DRIVING OPERATION GIVING SUCH PERTINENT DATA AS THEPHYSICAL CHARACTERISTICS OF THE DEEP FOUNDATION PILE-DRIVING EQUIPMENT,IDENTIFYING MARKS FOR EACH DEEP FOUNDATION PILE, THE TOTAL DEPTH OF EMBEDMENTFOR EACH DEEP FOUNDATION; AND WHEN THE ALLOWABLE DEEP FOUNDATION PILE LOADSARE DETERMINED BY A DYNAMIC LOAD FORMULA, THE DESIGN FORMULA USED, AND THEPERMANENT PENETRATION UNDER THE LAST 10 BLOWS. ONE COPY OF THE REPORT SHALLBE SENT TO THE ENFORCEMENT AGENCY10.THE WILLIAMSON ACT DOES APPLY TO PARCEL 047-010-006-000.DESIGN PROFESSIONALS AND SPECIALINSPECTORS:PILE DRIVING OBSERVATION REPORTSALEM ENGINEERING GROUP4729 W JAQUELYN AVE, FRESNO, CA 93722GROUND FAULT SYSTEM TESTINGPOWER SYSTEMS TESTING COMPANY INC.4688 W JENNIFER AVE, STE 108, FRESNO, CA 93722601 W. GRANGEVILLE BLVD.HANFORD, CA 93230(559) 410-8640LIC# 944636REVDATEDESCRIPTIONPROJECT NAME: BALLARD 2ADDRESS: BALLARD RD. CHICO, CA 95927POI COORDINATES: 39.868279°, -122.021794°DESIGNER: RENEWABLE SOLAR INC.DATE: AUGUST 25, 2023DRAFTER: LAURENCE WOMACKPLOT DATE: OCTOBER 6, 2023PROJECT NUMBER: #3153SHEET SIZE: 24" X 36"BUTTE COUNTY, CASHEET NO.: SCALE:COVER SHEETPV1.0N.T.SFLOOD ZONE NOTES:1.PORTION OF PV ARRAY TO BE INSTALLED IN FLOOD ZONE A. MINIMUMHEIGHT TO BOTTOM OF SOLAR PANELS OR ELECTRICAL EQUIPMENTTO BE 2 FT ABOVE HIGHEST ADJACENT GRADE.2.ENTIRE PV ARRAY SHALL FOLLOW FLOOD ZONE A REQUIREMENTS.3.ALL INVERTERS, DISTRIBUTION PANEL & MAIN SWITCHBOARD SHALLNOT BE INSTALLED IN FLOOD ZONE A AND SHALL NOT REQUIRED TOFOLLOW FLOOD ZONE A REQUIREMENTS.AREA OF WORKSACRAMENTO RIVERNAREA OF WORKSOUTH AVENSOUTHERN PACIFIC R.R.SINGER CREEKHWY 99SOUTHERN PACIFIC R.R.SACRAMENTO RIVERBALLARD RDSOUTH AVECANA HWYPOEPROJECT CONTACTS:AG RESERVES, INC. - SYSTEM OWNER,CLIENTACIP ENERGY, LLC. - CLIENT LIASON855 HARTER PKWY #360.YUBA CITY, CA 95993MARC LAWLESS, PRIMARY AGENT(831) 345-6645DAVID VINCENT(530) 777-2247RENEWABLE SOLAR - CONTRACTOR601 W. GRANGEVILLE BLVD.HANFORD, CA 93230BRANDON LAMATTINO, QC FOREMAN(559) 816-3466ELLIS SHELDON, ACCOUNT MANAGER(559) 589-4487LAURENCE WOMACK, SYSTEM DESIGNER(559) 410-86406100 WILSON LANDING RD. CHICO, CA 95973(530) 891-4900STRUCTURAL ENGINEERING (RACKING)NEWPORT STRUCTURAL DESIGN134 S GLASSELL ST, SUITE G. ORANGE, CA 92866 ABBREVIATIONS: A AMPERAGE AC ALTERNATING CURRENT AFCI ARC FAULT CURRENT INTERRUPTER DC DIRECT CURRENT JB JUNCTION BOX (E)EXISTING INV INVERTER M UTILITY METER MP MAIN SERVICE PANEL (N)NEW N.T.S NOT TO SCALE O.C.ON CENTER PV PHOTOVOLTAIC POI POINT OF INTERCONNECTION PL PROPERTY LINE LC PV LOAD CENTER TL TRANSFORMERLESS TYP TYPICAL U.O.N.UNLESS OTHERWISE NOTED ALL CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL HAVE OVERCURRENT DEVICES LOCATED SO AS TO PROVIDE OVERCURRENT PROTECTION FROM ALL SOURCES, NEC 690.9(A). ALL CONDUCTORS EXPOSED TO WEATHER SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT, NEC 690.31(B), 310.8(D). ALL CONDUCTORS SHALL BE MARKED ON EACH END FOR UNIQUE IDENTIFICATION. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH NEC ARTICLE 250. ALL NEC REQUIRED WARNING SIGNS, MARKINGS, AND LABELS SHALL BE POSTED ON EQUIPMENT AND DISCONNECTS PRIOR TO ANY INSPECTIONS TO BE PERFORMED BY THE BUILDING DEPARTMENT INSPECTOR. ALL OUTDOOR EQUIPMENT SHALL BE NEMA3R RATED. CIRCUIT BREAKER, IF BACKFED, SHALL BE SUITABLE FOR SUCH OPERATION, NEC 705.12(D)(5). CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND OPERATING AT OVER 30 VOLTS SHALL REQUIRE TOOL TO OPEN AND MARKED "DO NOT DISCONNECT UNDER LOAD" OR "NOT FOR CURRENT INTERRUPTING", NEC 690.33(C) & (E)(2). DUE TO THE FACT THAT PV MODULES ARE ENERGIZED WHENEVER EXPOSED TO LIGHT, PV CONTRACTOR SHALL DISABLE THE ARRAY DURING INSTALLATION AND SERVICE BY SHORT CIRCUITING, OPEN CIRCUITING, OR COVERING THE ARRAY WITH OPAQUE COVERING, NEC 690.1. EACH SOURCE CONNECTION SHALL BE MADE AT A DEDICATED CIRCUIT BREAKER OR FUSIBLE DISCONNECTING MEANS, NEC 705.12(D)(1). EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUSBAR OR CONDUCTOR SHALL BE MARKED TO INDICATE THE PRESENCE OF ALL SOURCES, NEC 705.12(D)(4). EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES SMALLER THAN 10 AWG SHALL BE PROTECTED FROM PHYSICAL DAMAGE BY A RACEWAY OR CABLE ARMOR, NEC 690.46 & 250.12(C). EQUIPMENT, INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AC PHOTOVOLTAIC MODULES, SOURCE-CIRCUIT COMBINERS, AND CHARGE CONTROLLERS INTENDED FOR SUE IN PHOTOVOLTAIC POWER SYSTEMS SHALL BE IDENTIFIED AND LISTED FOR THE APPLICATION, NEC 690.4(D). FINE STRANDED CABLES USED FOR BATTERY TERMINALS, DEVICES, AND CONNECTIONS REQUIRE LUGS AND TERMINALS LISTED AND MARKED FOR THE USE, NEC 690.74. FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES, OR CONNECTORS THAT ARE IDENTIFIED AND LISTED FOR SUCH USE, NEC 690.31(F). GROUND BUSHINGS ARE REQUIRED AROUND PRE-PUNCHED CONCENTRIC KNOCKOUTS ON THE DC SIDE OF THE SYSTEM, NEC 250.64(C). GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT, NEC 250.64(C). GROUND-MOUNTED PV PANEL SYSTEMS SHALL COMPLY WITH SECTION 1204.1 AND THIS SECTION. SETBACK REQUIREMENTS SHALL NOT APPLY TO GROUND-MOUNTED, FREE-STANDING PV ARRAYS. A CLEAR, BRUSH-FREE AREA OF 10 FEET SHALL BE REQUIRED FOR GROUND-MOUNTED PV ARRAYS, 2022 CFC 1204.4. PV MODULE NEGATIVE SHALL BE GROUNDED. ALL GROUNDED CONDUCTORS SHALL BE PROPERLY COLOR IDENTIFIED AS GREEN, NEC 200.6. PV SYSTEM CONNECTED ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER SOURCE(S) AT ANY DISTRIBUTION EQUIPMENT ON THE PREMISES SHALL MEET THE FOLLOWING, NEC 705.12(D). SOLAR PV SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SECTIONS 1204.2 - 1204.5, AND THE CBC OR CRC. THE ELECTRICAL PORTION OF SOLAR PV SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE CEC, 2022 CFC 1204.1. THE INTERCONNECTION POINT SHALL BE ON THE LINE SIDE OF ALL GROUND-FAULT PROTECTION EQUIPMENT, NEC 705.12(D)(3). THE MODULE CONDUCTORS MUST BE TYPE USE-2 OR LISTED FOR PHOTOVOLTAIC (PV) WIRE, NEC 690.31(B). THE UTILITY INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE THEIR OUTPUT TO THE CONNECTED ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND SHALL REMAIN IN THE STATE UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED, NEC 690.61. 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE: SOLAR PV NOTES PV2.0 N.T.S 80.6' 841.8' 2463.7' 3298.4' 3488.1' 2556' 507.9' 163' 4683.3' 2959.1' INVINV INV INV INV INV INV INV INV INVINV INV INV INV INV T FARMLAND RESERVES INC APN: 047-010-006-000 265.5 AC SITE PLAN NOTES: 1.NO GAS LINES LOCATED ON PARCEL. 2.NO EASEMENTS ON PARCEL AFFECTING SOLAR/PV ARRAY. 3.YEAR ROUND VEGETATION MANAGEMENT SHALL BE PROVIDED FOR THE SITE. 4.SOLAR PHOTOVOLTAIC PANELS OR MODULES THAT ARE INDEPENDENT STRUCTURES AND DO NOT HAVE ACCESSIBLE/OCCUPIED SPACE UNDERNEATH ARE NOT REQUIRED TO ACCOMMODATE A ROOF PHOTOVOLTAIC LIVE LOAD, PROVIDED THE AREA UNDER THE STRUCTURE IS RESTRICTED TO KEEP THE PUBLIC AWAY. ALL OTHER LOADS AND COMBINATIONS IN ACCORDANCE WITH CBC 1605 SHALL BE ACCOMMODATED. PER CBC 1607.12.5.3 5.EQUIPMENT LOCATIONS AND CONDUIT RUNS SHOWN ON THIS PLAN ARE DIAGRAMMATIC ONLY. CONTRACTOR SHALL VERIFY EXACT CONDUIT PATH AND EQUIPMENT PLACEMENT BASED ON SITE CONDITIONS AND PHYSICAL MEASUREMENTS. N 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE:OVERALL SITE PLAN PV3.0 1" = 175' PROPOSED PV ARRAY POE FROMCANA HWY ACCESS RD LEGEND: EXISTING ELECTRICAL EQUIPMENT N.T.S NEW MAIN SWITCHBOARD "MSB" N.T.S UTILITY TRANSFORMER N.T.S. (15) TYPICAL INVERTER CHINT POWER SYSTEMS AMERICA #CPS-SCA-60KTL-DO/US-480 N.T.S. (1674) TYPICAL PV MODULE CANADIAN SOLAR, INC. #CS7N-650MB-AG EXISTING UTILITY POWER POLE BELOW GRADE CONDUIT RUN PROPERTY LINE E T INV FARMLAND RESERVES INC APN: 047-020-014-000 (NOT USED FOR SOLAR) 231.7'400.7'T27'54'244.3'65.8'45.8'INV INV INV INV INV INV INV INVINVINVINV INV INV INV INV SITE PLAN NOTES:1.ELECTRICAL UTILITY LINE SHALL BE PROTECTED IN PLACE WHEN POSSIBLE. IF EXISTINGELECTRICAL LINE PRESENTS EXCESSIVE CONSTRAINTS, FIELD CREW TO REMOVE ANDRELOCATE EXISTING LINES AS NEEDED.2.EXISTING ENERGIZED EQUIPMENT THAT COMES INTO CONTACT WITH ANY NEWLY INSTALLSOLAR EQUIPMENT INVOLVED IN THIS SCOPE OF WORK SHALL BE DE-ENERGIZED TOPREVENT ANY ELECTRICAL HAZARDS,3.MINIMUM CONDUIT BURIAL DEPTH SHALL BE PER NEC 300.54.ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ELECTRICALEQUIPMENT PER NEC 110.265.SOLAR PHOTOVOLTAIC PANELS OR MODULES THAT ARE INDEPENDENT STRUCTURES ANDDO NOT HAVE ACCESSIBLE/OCCUPIED SPACE UNDERNEATH ARE NOT REQUIRED TOACCOMMODATE A ROOF PHOTOVOLTAIC LIVE LOAD, PROVIDED THE AREA UNDER THESTRUCTURE IS RESTRICTED TO KEEP THE PUBLIC AWAY. ALL OTHER LOADS ANDCOMBINATIONS IN ACCORDANCE WITH CBC 1605 SHALL BE ACCOMMODATED.6.EQUIPMENT LOCATIONS AND CONDUIT RUNS SHOWN ON THIS PLAN ARE DIAGRAMMATICONLY. CONTRACTOR SHALL VERIFY EXACT CONDUIT PATH AND EQUIPMENT PLACEMENTBASED ON SITE CONDITIONS AND PHYSICAL MEASUREMENTS.7.ALL EQUIPMENT AND APPURTENANCES USED IN THIS PROJECT SHALL BE UL (NRTL) LISTEDAND LABELED FOR THE PURPOSE AS PER CEC-2016 ART. 110.3 AND 690.4D8.(9) ROWS OF 2UP X 93 MODULESN601 W. GRANGEVILLE BLVD.HANFORD, CA 93230(559) 410-8640LIC# 944636REVDATEDESCRIPTIONPROJECT NAME: BALLARD 2ADDRESS: BALLARD RD. CHICO, CA 95927POI COORDINATES: 39.868279°, -122.021794°DESIGNER: RENEWABLE SOLAR INC.DATE: AUGUST 25, 2023DRAFTER: LAURENCE WOMACKPLOT DATE: OCTOBER 6, 2023PROJECT NUMBER: #3153SHEET SIZE: 24" X 36"BUTTE COUNTY, CASHEET NO.: SCALE:ENLARGED SITE PLANPV3.11" = 30'LEGEND:EXISTING ELECTRICAL EQUIPMENT N.T.SNEW MAIN SWITCHBOARD "MSB" N.T.SUTILITY TRANSFORMER N.T.S.(15) TYPICAL INVERTER CHINT POWER SYSTEMS AMERICA#CPS-SCA-60KTL-DO/US-480 N.T.S.(1674) TYPICAL PV MODULE CANADIAN SOLAR, INC.#CS7N-650MB-AGEXISTING UTILITY POWER POLEBELOW GRADE CONDUIT RUNPROPERTY LINEETINVEXISTING PUMP CONTROL CABINETEXISTING UTILITY POWER POLENEW UTILITY TRANSFORMERNEW SERVICE CT METERAND MAIN SWITCHBOARDFARMLAND RESERVES INCAPN: 047-020-014-000(NOT USED FOR SOLAR)FARMLAND RESERVES INCAPN: 047-010-006-000265.5 AC 100A 3P 25A 2P NEW MAIN SWITCHBOARD "MSB", 1600A BUS, 480/277V, 3Ø, 4W, 65KAIC, NEMA 3RINV-15TYPICAL PV MODULE CANADIAN SOLAR, INC. #CS7N-650MB-AG TOTAL 1674 6 STRINGS PER INVERTER SEE PV4.1 FOR DETAILS TYPICAL PV INVERTER CHINT POWER SYSTEMS AMERICA #CPS-SCA60KTL-DO/US-480 TOTAL 15 DC HOMERUN TO INVERTER MAX 1-1/4" PVC SCH. 40/80 WITH (12) #10 AWG USE-2 PV WIRE (1) #10 AWG THWN-2 CU GND (MAX STRING LENGTH = 600 FT) 1-1/2" PVC SCH. 40/80 OR EMT WITH (3) #2 AWG THWN-2 AL LINE (1) #6 AWG THWN-2 AL GND (MAX CONDUCTOR LENGTH = 300 FT) 100A 3PINV-1INCOMING UTILITY EXISTING 1600AS 3P 1600AF 3P800A 3P MAIN DEDICATED SOLAR BPS SECTION 800A DISTRIBUTION SECTION 1600A METER SECTION NEW SERVICE CT METER 100A 3P SPARE SOLAR MAIN AC FUSED DISCONNECT, MANUALLY OPERATED, VISIBLY OPEN AND LOCKABLE, 1600A/3P WITH 1600A/3P FUSES. TO EXISTING PUMP CIRCUITS ALSO ENERGY, INC. #PLCS-CM-600-PLUS 25A 2P 15A 1P 3/4" EMT OR EQUIV. WITH (2) #10 AWG THWN-2 CU WIRE (1) #10 AWG THWN-2 CU GND NEW MONITORING SUBPANEL, 60A BUS, 240/120V, 1Ø, 4W, NEMA 3R 5KVA 1-PHASE AUTOTRANSFORMER, 480V-240/120V 3/4" EMT OR EQUIV. WITH (1) #10 AWG THWN-2 CU WIRE (1) #10 AWG THWN-2 CU NEUT (1) #10 AWG THWN-2 CU GND ELECTRICAL NOTES: 1.ALL NEW AC CONDUCTORS SHALL BE 90°C THWN-2 ALUMINUM OR COPPER IN CONDUIT, U.O.N. (AMPACITY FOR CONDUCTOR SELECTION MUST BE DETERMINED/DERATED BY THE ALLOWED TERMINATION RATINGS MARKED/APPROVED ON EACH DEVICE, MOTOR, APPLIANCE, XFMR O.C.P.C. PANEL, ETC. CONDUCTORS INSTALLED IN U.G. OR WET LOCATIONS SHALL BE MARKED "W". PER 2019 CEC 110-14 (C)(1).) 2.SERVICE EQUIPMENT TO BE SUITABLE FOR AVAILABLE SHORT CIRCUIT CURRENT. 3.ALL READILY ACCESSIBLE PV SOURCE AND OUTPUT CIRCUITS OPERATING AT VOLTAGES GREATER THAN 30 VOLTS SHALL BE GUARDED OR INSTALLED IN MC CABLE OR IN RACEWAY PER 2022 CEC 690.31(A), EMT ABOVE GRADE, PVC SCH. 40 BELOW GRADE AND STEEL CONDUIT ON EXTERIOR EXPOSED SURFACE BELOW 8' AFF. FOR PHYSICAL PROTECTION. 4.ALL ELECTRICAL EQUIPMENT SHALL BE LISTED FOR USE AND TERMINATION OF ELECTRICAL CONDUCTORS RATED 90°C. 5.WHERE NOT ROUTED WITH CIRCUIT CONDUCTORS AS PERMITTED IN 250.130(C) AND 250.134(A) EXCEPTION NO. 2, EQUIPMENT GROUND CONDUCTORS SMALLER THAN 6 AWG SHALL BE PROTECTED FROM PHYSICAL DAMAGE BY AN IDENTIFIED RACEWAY OR CABLE ARMOR UNLESS INSTALLED WITHIN HOLLOW SPACES OF THE FRAMING MEMBERS OF BUILIDINGS OR STRUCTURES AND WHERE NOT SUBJECT TO PHYSICAL DAMAGE, PER 2022 CEC 250.120(C). LOAD SUMMARY: 1. SYSTEM SIZE NUMBER OF PV MODULES:1674 MODULE RATING:650 W TOTAL SYSTEM SIZE (DC):1088.1 KW 2. TOTAL APPARENT POWER NUMBER OF INVERTERS:15 INVERTER RATING (AC):60 KW MAX. AC OUTPUT:1082.5 A WITH 125% CONT. RATING:1353.1 A 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE:SINGLE LINE DIAGRAM PV4.0 N.T.S INVERTER 1 STRING 1 INVERTER 1 INVERTER 1 INVERTER 1 INVERTER 1 INVERTER 1 STRING 2 STRING 1 STRING 2 STRING 1 STRING 2 STRING 1 STRING 2 STRING 1 STRING 2 STRING 1 STRING 2 STRING 1 STRING 2 STRING 1 STRING 2 STRING 1 STRING 2 INVERTER 2 INVERTER 3 INVERTER 4 INVERTER 5 INVERTER 6 INVERTER 7 INVERTER 8 INVERTER 9 INVERTER 2 INVERTER 3 INVERTER 4 INVERTER 5 INVERTER 6 INVERTER 7 INVERTER 8 INVERTER 9 INVERTER 2 INVERTER 3 INVERTER 4 INVERTER 5 INVERTER 6 INVERTER 7 INVERTER 8 INVERTER 9 INVERTER 2 INVERTER 3 INVERTER 4 INVERTER 5 INVERTER 6 INVERTER 7 INVERTER 8 INVERTER 9 INVERTER 2 INVERTER 3 INVERTER 4 INVERTER 5 INVERTER 6 INVERTER 7 INVERTER 8 INVERTER 9 INVERTER 2 INVERTER 3 INVERTER 4 INVERTER 5 INVERTER 6 INVERTER 7 INVERTER 8 INVERTER 9 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 5 STRING 6 INVERTER 10 STRING 3 INVERTER 10 STRING 4 INVERTER 10 STRING 1 INVERTER 10 STRING 2 INVERTER 10 STRING 5 INVERTER 10 STRING 6 INVERTER 11 STRING 1 INVERTER 11 STRING 2 INVERTER 11 INVERTER 11 INVERTER 11 INVERTER 11 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 1 STRING 2 STRING 5 STRING 6 STRING 1 STRING 2 STRING 3 STRING 4 STRING 5 STRING 6 STRING 3 STRING 4 STRING 1 STRING 2 STRING 5 STRING 6 STRING 1 STRING 2 STRING 3 STRING 4 STRING 5 STRING 6 INVERTER 12 INVERTER 13 INVERTER 13 INVERTER 14 INVERTER 15 INVERTER 15 INVERTER 12 INVERTER 13 INVERTER 13 INVERTER 14 INVERTER 15 INVERTER 15 INVERTER 13 INVERTER 15 INVERTER 13 INVERTER 15 INVERTER 12 INVERTER 14 INVERTER 12 INVERTER 14 INVERTER 12 INVERTER 14 INVERTER 12 INVERTER 14 INV-15INV-9 INV-14 INV-8INV-7 INV-13 INV-6 INV-12INV-5 INV-4 INV-11 INV-3 INV-10 INV-2INV-1 SEE SINGLE LINE DIAGRAM FOR WIRING TYPICAL PV MODULES TYPICAL INVERTER1-61-51-41-31-21-1GROUND BUS (TYP) SEE SINGLE LINE DIAGRAM FOR WIRINGSTRING #6 OF 18 PV ARRAYSTRING #5 OF 18 PV ARRAYSTRING #4 OF 18 PV ARRAYSTRING #3 OF 18 PV ARRAYSTRING #2 OF 18 PV ARRAYSTRING #1 OF 18 PV ARRAYG A Ø B Ø C Ø INVERTER #10-151-61-51-41-31-21-1STRING #6 OF 19 PV ARRAYSTRING #5 OF 19 PV ARRAYSTRING #4 OF 19 PV ARRAYSTRING #3 OF 19 PV ARRAYSTRING #2 OF 19 PV ARRAYSTRING #1 OF 19 PV ARRAYG A Ø B Ø C Ø INVERTER #1-9 - + G G - + 1 19 MC4 COMPATIBLE CONNECTORS (TYP) STEEL RACKING STRUCTURE FOR GROUNDING PATH. BOND ALL PV WITH BONDING WASHERS AND BOLTS SEE SINGLE LINE DIAGRAM FOR WIRING TYPICAL PHOTOVOLTAIC (PV) ARRAY IN SERIES CONNECTION WITH INTEGRAL MODULE LEADS - + 2 - + 3 - + 4 - + 5 G G CONNECTION DETAILS PV4.1 N.T.S 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE: A INVERTER CONNECTION DETAIL (TYP) N.T.S B TYPICAL PHOTOVOLTAIC (PV) MODULE CONNECTION DETAIL N.T.S STRINGING NOTES: 1.STRING SIZES OF 18 OR 19 MODULES. (6) STRINGS PER INVERTER. 2.(9) ROWS OF 2UP X (93) MODULES 3.STRINGS OF DIFFERENT SIZES SHALL NOT SHARE THE SAME MPPT. SCA60KTL-DO/US-480 (STRING LANDINGS) MPPT 1 MPPT 2 MPPT 3 STRING 1 STRING 3 STRING 5 STRING 2 STRING 4 STRING 6 STRING LENGTH (18)STRING LENGTH (19) GRADE WIRE GUTTER (SIZE SHALL VARY PER PROJECT) TYPICAL 50/60KW INVERTER FRONT VIEW AC DISCONNECT CAUTION:DO NOT REMOVE COVER UNTIL5 MINUTES AFTER DISCONNECTINGALL SOURCES OF SUPPLY. DANGER:BEFORE OPENING THE DEVICE,DISCONNECT FROM GRID ANDTHE PV GENERATOR.THE DEVICEMAY ONLY BE OPENED BY SERVICEPERSONNEL. WARNING:HAZARDOUS VOLTAGE AND ENERGYINSIDE, DISCHARGE BY SERVICEPERSONNEL BEFORE OPENINGTHE DEVICE. ELECTRIC SHOCKHAZARD. THE DC CONDUCTORSOF THIS PHOTOVOLTAIC SYSTEMARE UNGROUNDED AND MAY BEENERGIZED. CAUTION:RISK OF BURNING. DO NOT TOUCH! 5min Serial Number SIDE VIEW MOUNTING DEEP-SLOTTED UNISTRUT, NUT, WASHER AND BOLT (TYP) I-BEAM (TYP) EMT CONDUIT FOR AC & DC RUNS (TYP) (SIZE SHALL VARY PER PROJECT) RAIN-TIGHT CONNECTORS (TYP) PVC CHASE NIPPLE (TYP) PVC SCH40/SCH80 CONDUIT (TYP) (COUNT AND SIZE SHALL VARY PER PROJECT) INVERTER 1INVERTER ## ELECTRICAL CONDUIT PER PLANS CAUTION TAPE NATIVE MATERIAL PLACED IN 8" LAYERS & COMPACTED TO 90% 18" (MIN.) 1'-0" (MIN.) 1'-0" 1-1/4" LB METAL C-PILE (TYP) 4" X 4" X 12" WIRE GUTTER NEMA 3R 1-1/4" LL OR LR METAL 1-1/4" ONE-HOLE EMT STRAP CORD GRIP (TYP) (SIZE SHALL DEPEND ON STRING AMOUNT) 1-1/4" EMT GRADE PVC CHASE NIPPLE (TYP) PVC SCH80 CONDUIT (TYP) (SIZE SHALL VARY PER PROJECT) 1-1/4" CHASE NIPPLE (TYP) ELECTRICAL DETAILS PV4.2 N.T.S NOTES: 1.ALL ELECTRICAL EQUIPMENT SHALL BE LISTED FOR TERMINATION OF ELECTRICAL CONDUCTORS RATED 75°C MINIMUM. 2.THE METHODS IN NEC 250 SHALL BE FOLLOWED FOR GROUNDING AND BONDING ANY ELECTRICAL SYSTEMS OR EQUIPMENT THAT IS LIKELY TO BECOME ENERGIZED. 3.WHERE TWO OR MORE GROUND RODS ARE INSTALLED, MINIMUM SEPARATION SHALL BE 6'-0" PER NEC 250.53(A)(2) AND (3). 4.ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED OR CREDITED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION . 5.ALL ABOVE GRADE CONDUIT CONSTRUCTION SHALL FOLLOW CEC/NEC 342, 344 OR 350 FOR IMC, RMC, OR LFMC CONSTRUCTION. 6.BOXES AND CONDUIT BODIES USED AS PULL OR JUNCTION BOXES SHALL COMPLY WITH NEC 314.28(A) THROUGH (E) 7.CONDUIT ROUTING, CONDUIT BODY TYPE AND CONDUCTORS SHALL BE FIELD VERIFIED PER EQUIPMENT LOCATION 8.CONTRACTOR SHALL USE SPACERS OR CHAIRS, DESIGNED FOR UNDERGROUND INSTALLATIONS TO MAINTAIN SEPARATION AND SYMMETRY FOR ALL UNDERGROUND CONDUIT RUNS. MINIMUM CONDUIT COVER AND TRENCH DEPTH SHALL BE PER NEC 300.5 9.MINIMUM CONDUIT COVER AND TRENCH DEPTH SHALL BE PER NEC 300.5, MINIMUM 18-INCHES. 10.A MINIMUM 20-INCH SPACING SHALL BE MAINTAINED AROUND ALL INVERTERS. A TYPICAL 50/60KW CHINT POWER SYSTEMS INVERTER INSTALLATION N.T.S B TYPICAL ELECTRICAL UTILITY TRENCH N.T.S C TYPICAL HOMERUN DETAIL N.T.S 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE: INV INV INV INV INV INV INV INV INV INV INV INV INV INV INV ELECTRICAL NOTES: - ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH CODE AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. - ALL PV EQUIPMENT SHALL BE LISTED BY A RECOGNIZED TESTING LAB. - INSTALLER SHALL NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM. - WHEN BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, BREAKER SHALL NOT READ LINE AND LOAD. - WHEN A BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, THE BREAKER SHALL BE INSTALLED AT THE OPPOSITE END OF THE BUS BAR OF THE MAIN BREAKER. - WORK CLEARANCES AROUND ELECTRICAL EQUIPMENT WILL BE MAINTAINED PER NEC 110.26 (A) (1), 110.26 (A) (2), AND 110.26 (A) (3). - ALL EXTERIOR CONDUITS, FITTINGS, AND BOXES SHALL BE RAIN-TIGHT AND APPROVED FOR USE IN WET LOCATIONS PER NEC 314.15. - ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS. - ALL PV EQUIPMENT, SYSTEMS AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL BE INSTALLED BY QUALIFIED PERSONS. - THE PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED. THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATED COLOR CODING, MARKING TAPE, TAGGING OR OTHER APPROVED MEANS. NEC 690.4(B). - ADEQUATE SPACING MUST BE MAINTAINED BETWEEN ANY PLUMBING SEWER VENTS EXTENDING THROUGH THE ROOF AND THE UNDERSIDE OF THE PHOTOVOLTAIC PANELS (6" MINIMUM RECOMMENDED). - EXTERNALLY OPERATED KNIFE BLADE TYPE AC DISCONNECT SWITCH WHICH IS LOCKABLE IN THE OPEN POSITION AND "ON" AND "OFF" VISIBLE DESIGNATIONS WHICH IS DIRECTLY ACCESSIBLE TO LOCAL UTILITY DEPARTMENT EMPLOYEES AT ALL TIMES. ADHESIVE FASTENED SIGNS: - THE LABEL SHALL BE SUITABLE FOR THE ENVIRONMENT WHERE IT IS INSTALLED. - WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL FIELD APPLIED LABELS, WARNINGS, AND MARKINGS SHOULD COMPLY WITH ANSI Z535 4 [NEC 110.21 (B) FIELD MARKING] - ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLY ADHERED VINYL SIGNS SHALL BE WEATHER RESISTANT [IFC 605.11 1.3] SIGNS AND PLACARDS: CAUTION PLACARD 5" x 4.75" RED WITH WHITE LETTERS POWER IS SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN. WARNING ELECTRIC SHOCK HAZARD - DO NOT TOUCH TERMINALS TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION MUST SHOW DRAWINGS OF THE PROPERTY AND EQUIPMENT LAYOUT PER NEC 690.56 MAIN ELECTRICAL SERVICE DISCONNECT AND SOLAR MAIN AC DISCONNECT N 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE:ELECTRICAL NOTES AND PV SIGNAGE PV5.0 N.T.S NEC 690.5 (C) - AT THE INVERTER AND/OR GROUND FAULT INDICATOR LOCATION (AND ALL BATTERY LOCATIONS IF APPLICABLE): NEC 690.35 (F) - UNGROUNDED PV SYSTEMS ONLY AT EACH JUNCTION BOX, COMBINER BOX, DISCONNECT AND DEVICE WHERE THE UNGROUNDED CIRCUITS MAY BE EXPOSED DURING SERVICE: NEC 690.17 - AT JUNCTION BOX, COMBINER BOXES AND AC/DC DISCONNECTS: CSFM - DC CONDUIT EVERY 10' INTERIOR/EXTERIOR: NEC 705.12 (D) (7) - BY BREAKER AT DISTRIBUTION EQUIPMENT: LOCATED AT POINT OF INTERCONNECTION PER CEC ART 690.17 (D) (1) NEC 605.11.1 4 - AT INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES, AND CABLE ASSEMBLIES AT LEAST EVERY 10', AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL COMBINER/JUNCTION BOXES CEC 690.13 (B) - AT ANY POINT OF INTERCONNECT: CEC 690.54 - ON AC DISCONNECT: NEC 690.53 - ON DC DISCONNECT: NEC 690.14 (C) (2), 690.15 - ON AC/DC DISCONNECT: RAPID SHUTDOWN REQUIREMENT PER CEC ART 690.12, PLACARD LOCATED ON INVERTER, MAIN SERVICE PANEL, AC DISCONNECT, AND FRONT OF ELECTRICAL ROOM: NEC 110.16 (A) - ELECTRICAL EQUIPMENT, SUCH AS SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, INDUSTRIAL CONTROL PANELS, METER SOCKET ENCLOSURES, AND MOTOR CONTROL CENTERS, THAT ARE IN OTHER THAN DWELLING UNITS, AND ARE LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE WHILE ENERGIZED, SHALL BE FIELD OR FACTORY MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. THE MARKING SHALL MEET THE REQUIREMENTS IN 110.21(B) AND SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE EQUIPMENT. MAIN SOLAR SYSTEM AC DISCONNECT MAIN SOLAR SYSTEM DC DISCONNECT PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN PHOTOVOLTAIC AC DISCONNECT MAXIMUM AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: 1600 A 480 V WARNING: PHOTOVOLTAIC POWER SOURCE SOLAR DISCONNECT PV SOLAR BREAKER DO NOT RELOCATE THIS OVERCURRENT DEVICE CAUTION SOLAR CIRCUIT DUAL POWER SUPPLY SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM ELECTRICAL SHOCK HAZARD IF A GROUND FAULT IS INDICATED, NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED WARNING WARNING ELECTRICAL SHOCK HAZARD. THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT ELECTRICAL ARC FLASH HAZARD. WILL CAUSE SEVERE INJURY OR DEATH. TURN OFF ALL POWER BEFORE OPENING. FOLLOW ALL REQUIREMENTS IN NFPA 70E FOR SAFE WORK PRACTICES AND FOR PERSONAL PROTECTIVE EQUIPMENT. WARNING WARNING WARNING INVERTER #1 INVERTER #15 #QTY.PLACARD LOCATION 0 SWITCHBOARD / PANELBOARD / METER ENCLOSURES 0 INVERTER 0 JUNCTION BOXES 0 JUNCTION BOXES 0 DC CONDUIT AT 10'-0" INVTERVALS 0 BREAKER AT DISTRIBUTION EQUIP. 0 POINT OF INTERCONNECTION 0 JUNCTION BOXES 0 POINT OF INTERCONNECTION 1 AC DISCONNECT SWITCH 15 INVERTER 0 AC DISCONNECT SWITCH 0 AC DISCONNECT SWITCH 0 INVERTER 1 POINT OF INTERCONNECTION 2X # OF INV INVERTER AND BREAKER BALLARD RD. CHICO, CA 95927 39.868279°, -122.021794° O P E R A T I N G D C CU R R E NT: M P P T V O L T A G E R A N G E : M A X D C I N P UT V O L T A G E: S H O R T C IRC UIT CU RRE N T: 90A 540-850V 1000V 204A PHOTOVOLTAIC SYSTEM DC DISCONNECT SOLAR DC DISCONNECT(S) REFERENCES R1.0 N.T.S 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE: 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE:REFERENCES R1.1 N.T.S 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE:REFERENCES R1.2 N.T.S 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE:REFERENCES R1.3 N.T.S 601 W. GRANGEVILLE BLVD. HANFORD, CA 93230 (559) 410-8640 LIC# 944636 REV DATE DESCRIPTION PROJECT NAME: BALLARD 2 ADDRESS: BALLARD RD. CHICO, CA 95927 POI COORDINATES: 39.868279°, -122.021794° DESIGNER: RENEWABLE SOLAR INC. DATE: AUGUST 25, 2023 DRAFTER: LAURENCE WOMACK PLOT DATE: OCTOBER 6, 2023 PROJECT NUMBER: #3153 SHEET SIZE: 24" X 36" BUTTE COUNTY, CA SHEET NO.: SCALE:REFERENCES R1.4 N.T.S RENEWABLE SOLAR HANFORDBALLARD 2CHICO, CA 95927S023000 Harvard Road, Suite BCleveland, OH 44122Copying in part or as a whole is prohibited. This is only to be usedby the party described in the "Title" section. This is proprietaryinformation of FlexRack by Qcells© Copyright, FlexRack by Qcells All Rights Reserved. RENEWABLE SOLAR HANFORDBALLARD 2CHICO, CA 95927S123000 Harvard Road, Suite BCleveland, OH 44122Copying in part or as a whole is prohibited. This is only to be usedby the party described in the "Title" section. This is proprietaryinformation of FlexRack by Qcells© Copyright, FlexRack by Qcells All Rights Reserved. RENEWABLE SOLAR HANFORDBALLARD 2CHICO, CA 95927S223000 Harvard Road, Suite BCleveland, OH 44122Copying in part or as a whole is prohibited. This is only to be usedby the party described in the "Title" section. This is proprietaryinformation of FlexRack by Qcells© Copyright, FlexRack by Qcells All Rights Reserved. RENEWABLE SOLAR HANFORDBALLARD 2CHICO, CA 95927S323000 Harvard Road, Suite BCleveland, OH 44122Copying in part or as a whole is prohibited. This is only to be usedby the party described in the "Title" section. This is proprietaryinformation of FlexRack by Qcells© Copyright, FlexRack by Qcells All Rights Reserved. RENEWABLE SOLAR HANFORDBALLARD 2CHICO, CA 95927S423000 Harvard Road, Suite BCleveland, OH 44122Copying in part or as a whole is prohibited. This is only to be usedby the party described in the "Title" section. This is proprietaryinformation of FlexRack by Qcells© Copyright, FlexRack by Qcells All Rights Reserved. RENEWABLE SOLAR HANFORDBALLARD 2CHICO, CA 95927S523000 Harvard Road, Suite BCleveland, OH 44122Copying in part or as a whole is prohibited. This is only to be usedby the party described in the "Title" section. This is proprietaryinformation of FlexRack by Qcells© Copyright, FlexRack by Qcells All Rights Reserved. RENEWABLE SOLAR HANFORDBALLARD 2CHICO, CA 95927S623000 Harvard Road, Suite BCleveland, OH 44122Copying in part or as a whole is prohibited. This is only to be usedby the party described in the "Title" section. This is proprietaryinformation of FlexRack by Qcells© Copyright, FlexRack by Qcells All Rights Reserved.