HomeMy WebLinkAboutADM23-0026 Plan SetTITLE SHEET PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: T-1 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD SITE INFORMATION: SITE ADDRESS:200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 COUNTY:BUTTE COORDINATES:39.506867° / -121.502308° (FOR NAVIGATION ONLY) PROPERTY LANDLORD OR OWNER:PG&E TAX ID #:068-150-099 ZONING:RC (RESOURCE CONSERVATION) OCCUPANCY GROUP:U - UNMANNED CONSTRUCTION TYPE:II-B POWER COMPANY:PG&E FLOOD ZONE:X A.D.A. COMPLIANCE:FACILITY IS UNMANNED AND NOT FOR HUMAN HABITATION at t & VICINITY MAP: SITE 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 N GOOGLE MAPS 2023 APPROVALS : AT&T MANAGER ______________________________________________ CONSTRUCTION MANAGER ______________________________________________ SITE ACQ. MANAGER ______________________________________________ PROPERTY OWNER ______________________________________________ LANDLORD ______________________________________________ R DIG LINE: THE PLANS SHOW SOME KNOWN SUBSURFACE STRUCTURES, ABOVE GROUND STRUCTURES, AND/OR EXISTING UTILITIES BELIEVED TO BE IN THE WORKING AREA. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL UTILITIES, PIPELINES AND OTHER STRUCTURES SHOWN OR NOT SHOWN ON THESE PLANS. ANY DAMAGE TO EXISTING UTILITIES SHALL BE REPAIRED TO THE SATISFACTION OF THE OWNER AND ENGINEER AT THE CONTRACTOR'S EXPENSE. AREA MAP: SITE GOOGLE MAPS 2023DO NOT SCALE DRAWINGS: CONTRACTOR SHALL VERIFY ALL PLANS, EXISTING DIMENSIONS, CONDITIONS ON THE JOB SITE AND SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR THE SAME. CODE COMPLIANCE: ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN ACCORDANCE WITH THE CURRENT EDITIONS OF ALL GOVERNING CODES AS ADOPTED BY THE LOCAL GOVERNING AUTHORITIES. NOTHING IN THESE PLANS ARE TO BE CONSTRUCTED TO PERMIT WORK NOT CONFORMING TO THESE CODES: CALIFORNIA BUILDING CODE (CBC) 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA FIRE CODE (CFC) 2022 INTERNATIONAL BUILDING CODE (IBC) 2021 NATIONAL ELECTRICAL CODE (NEC) 2020 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 13,30,37,58,70,72,110,111 AMERICAN CONCRETE INSTITUTE (ACI) 318 AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA) 222 TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA) 607 SCOPE OF WORK: INSTALL (1) ARTICLE 702 OPTIONAL STANDBY DIESEL GENERATOR (GENERAC SD030) WITH UL-2085 BASE FUEL TANK ON CONCRETE PAD AND 200A ATS / CAMLOCK (GENERAC TAS200) WITHIN PROPOSED CHAINLINK FENCE COMPOUND EXPANSION w/ SECURITY TOPPER NEAR EXISTING AT&T EQUIPMENT AREA. INTEGRATE NEW GENERATOR WITH EXISTING SERVICE. NOTE: NO CHANGES OR ALTERATIONS TO THE TOWER, MOUNTS, ANTENNAS, FEEDLINES, ETC. IS PROPOSED AS A PART OF THIS SCOPE OF WORK. OLIVE HIGHWAY FA#: 10132952 LINE NAME: ATT-CN0696/OLIVE HIGHWAY TABLE MOUNTAIN-PALERMO TOWER NUMBER: 10/48 SAP TOWER#: 40871778 GENERATOR INSTALLATION PROJECT 30KW GENERAC DIESEL GENERATOR WITH ASSOCIATED UL-2085 FUEL TANK SHEET INDEX: SHEET DESCRIPTION T-1 TITLE SHEET N-1 GENERAL NOTES A-0 PARCEL SITE PLAN A-1 OVERALL SITE PLAN A-2 ENLARGED SITE PLAN A-3 ELEVATION VIEWS S-1 GENERATOR PAD DETAILS S-2 GENERAL STRUCTURAL DETAILS S-3 FENCE & GATE DETAILS S-4 COMPOUND EXPANSION DETAIL E-1 ELECTRICAL DETAILS E-2 ELECTRICAL DETAILS E-3.0 ELECTRICAL DETAILS E-3.1, E-3.2, E-3.3 PG&E GROUNDING SPECIFICATIONS E-4.0 <> E4.4 GENERATOR SPECIFICATIONS E-5.0 ATS SPECIFICATIONS E-5.1 CAM-LOCK BOX SPECIFICATIONS PG&E-2 CONTACT INFORMATION: APPLICANT:AT&T MOBILITY 1375 CAMINO REAL STE 120 SAN BERNARDINO, CA 92408 PHONE: 951.534.8967 PROJECT MANAGER:GENERAL DYNAMICS WIRELESS SERVICES, LLC. 19240 DES MOINES DR. S. BLDG C STE 300 SEA TAC, WA 98048 PHONE: 425.606.8785 CONTACT: CHRISTOPHER HERMAN LEASING / PERMITTING:JT LAND MANAGEMENT 10615 QUAIL HOLLOW LANE REDDING, CA 96003 PHONE: 530.722.0743 CONTACT: FRANK SCHABARUM ARCHITECTURE & ENGINEERING: GEOSTRUCTURAL, LLC. PO BOX 2621 BOISE, ID 83701 PHONE: 530.539.4787 CONTACT: DON GEORGE G NOTES TO SUBCONTRACTOR: 1. THE GENERAL SUBCONTRACTOR MUST VERIFY ALL DIMENSIONS, CONDITIONS AND ELEVATIONS BEFORE PROCEEDING WITH THE WORK. ALL DISCREPANCIES SHALL BE RESOLVED BEFORE PROCEEDING WITH THE WORK. ALL WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN ACCORDANCE WITH ACCEPTED CONSTRUCTION PRACTICES. 2. IT IS THE INTENTION OF THESE DRAWINGS TO SHOW THE COMPLETED INSTALLATION. THE SUBCONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY BRACING, SHORING, TIES, FORM WORK, ETC. IN ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL ORDINANCES, TO SAFELY EXECUTE ALL WORK AND SHALL BE RESPONSIBLE FOR SAME. ALL WORK SHALL BE IN ACCORDANCE WITH LOCAL CODES. 3. THE SUBCONTRACTOR SHALL USE ADEQUATE NUMBER OF SKILLED WORKMAN WHO ARE THOROUGHLY TRAINED AND EXPERIENCED IN THE NECESSARY CRAFTS AND WHO ARE COMPLETELY FAMILIAR WITH THE SPECIFIED REQUIREMENTS AND METHOD NEEDED FOR PROPER PERFORMANCE OF THE WORK. 4. SUBCONTRACTOR AGREES THAT IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, CONSTRUCTION SUBCONTRACTOR WILL BE REQUIRED TO ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THE PROJECT, INCLUDING THE SAFETY OF ALL PERSONS AND PROPERTY, THAT THIS REQUIREMENT SHALL BE MADE TO APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS AND SUBCONTRACTOR FURTHER AGREES TO INDEMNIFY AND HOLD DESIGN ENGINEER HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH PERFORMANCE OF WORK ON THIS PROJECT. 5. SITE GROUNDING SHALL COMPLY WITH AT&T WIRELESS SERVICES TECHNICAL SPECIFICATIONS FOR FACILITY GROUNDING FOR CELL SITE STANDARDS, LATEST EDITION, AND COMPLY WITH AT&T TOWERS GROUNDING CHECKLIST, LATEST VERSION. WHEN NATIONAL AND LOCAL GROUNDING CODES ARE MORE STRINGENT THEY SHALL GOVERN. 6. ALL WORK SHALL COMPLY WITH OSHA AND STATE SAFETY REQUIREMENTS. PROCEDURES FOR THE PROTECTION OF EXCAVATIONS, EXISTING CONSTRUCTION AND UTILITIES SHALL BE ESTABLISHED PRIOR TO FOUNDATION INSTALLATION. 7. ALL WORK SHALL BE ACCOMPLISHED IN ACCORDANCE WITH ALL LOCAL, STATE, AND FEDERAL CODES OR ORDINANCES. THE MOST STRINGENT CODE WILL APPLY IN THE CASE OF DISCREPANCIES OR DIFFERENCES IN THE CODE REQUIREMENTS. 8. ANY DAMAGE TO THE ADJACENT PROPERTIES WILL BE CORRECTED AT THE SUBCONTRACTOR'S EXPENSE TO THE SATISFACTION OF THE LANDOWNER AND THE CONSTRUCTION MANAGER. 9. THE COMPLETE BID PACKAGE INCLUDES THESE CONSTRUCTION DRAWINGS ALONG WITH THE SPECIFICATIONS. SUBCONTRACTOR IS RESPONSIBLE FOR REVIEW OF TOTAL BID PACKAGE PRIOR TO BID SUBMITTAL. 10. SUBCONTRACTOR SHALL VERIFY LOCATION OF ALL EXISTING UTILITIES WITHIN CONSTRUCTION LIMITS PRIOR TO CONSTRUCTION. 11. THE SUBCONTRACTOR IS RESPONSIBLE FOR MAINTAINING POSITIVE DRAINAGE ON THE SITE AT ALL TIMES. SILT AND EROSION CONTROL SHALL BE MAINTAINED ON THE DOWNSTREAM SIDE OF THE SITE AT ALL TIMES. ANY DAMAGE TO ADJACENT PROPERTIES WILL BE CORRECTED AT THE SUBCONTRACTOR'S EXPENSE. 12. CLEARING OF TREES AND VEGETATION ON THE SITE SHOULD BE HELD TO A MINIMUM. ONLY THE TREES NECESSARY FOR CONSTRUCTION OF THE FACILITIES SHALL BE REMOVED. ANY DAMAGE TO THE PROPERTY OUTSIDE THE LEASED PROPERTY SHALL BE REPAIRED BY THE SUBCONTRACTOR. 13. ALL SUITABLE BORROW MATERIAL FOR BACK FILL OF THE SITE SHALL BE INCLUDED IN THE BID. EXCESS TOPSOIL AND UNSUITABLE MATERIAL SHALL BE DISPOSED OF OFF SITE AT LOCATIONS APPROVED BY GOVERNING AGENCIES PRIOR TO DISPOSAL. 14. PERMITS: THE SUBCONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND INCURRING THE COST OF ALL REQUIRED PERMITS, INSPECTIONS, CERTIFICATES, ETC. 15. RECORD DRAWINGS: MAINTAIN A RECORD OF ALL CHANGES, SUBSTITUTIONS BETWEEN WORK AS SPECIFIED AND INSTALLED. RECORD CHANGES ON A CLEAN SET OF CONTRACT DRAWINGS WHICH SHALL BE TURNED OVER TO THE CONSTRUCTION MANAGER UPON COMPLETION OF THE PROJECT. 16. THE PLANS SHOW SOME KNOWN SUBSURFACE STRUCTURES, ABOVE GROUND STRUCTURES AND/OR EXISTING UTILITIES BELIEVED TO BE IN THE WORKING AREA. IT IS THE RESPONSIBILITY OF THE SUBCONTRACTOR TO VERIFY ALL UTILITIES, PIPELINES AND OTHER STRUCTURES SHOWN OR NOT SHOWN ON THESE PLANS. THE SUBCONTRACTOR SHALL CONTACT THE LOCAL LOCATE SERVICE BEFORE DIGGING OR DRILLING. ANY DAMAGE TO EXISTING UTILITIES SHALL BE REPAIRED TO THE SATISFACTION OF THE OWNER AND ENGINEER AT THE SUBCONTRACTOR'S EXPENSE. GENERAL PROJECT NOTES: 1. THIS PROPOSAL IS FOR THE ADDITION OF A NEW GENERATOR ON A NEW CONCRETE PAD TO AN EXISTING UNMANNED TELECOMMUNICATIONS FACILITY CONSISTING OF AN EQUIPMENT SHELTER/PLATFORM AND TOWER. 2. THE PROPOSED FACILITY WILL BE UNMANNED AND DOES NOT REQUIRE POTABLE WATER OR SEWER SERVICE. 3. THE PROPOSED FACILITY IS UNMANNED AND IS NOT FOR HUMAN HABITAT. (NO HANDICAP ACCESS IS REQUIRED) 4. OCCUPANCY IS LIMITED TO PERIODIC MAINTENANCE AND INSPECTION, APPROXIMATELY 2 TIMES PER MONTH BY AT&T TECHNICIANS. 5. OUTDOOR STORAGE AND SOLID WASTE CONTAINERS ARE NOT PROPOSED. 6. ALL MATERIAL SHALL BE FURNISHED AND WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. 7. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING ANY DAMAGE CAUSED BY THE CONSTRUCTION OPERATION. 8. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS AND INSPECTION REQUIRED FOR CONSTRUCTION. 9. SUBCONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE SITE ON A DAILY BASIS. ELECTRICAL NOTES: A. GENERAL 1. COORDINATE LOCATION AND POWER REQUIREMENTS OF ALL EQUIPMENT WITH AT&T AND EQUIPMENT SUPPLIER PRIOR TO INSTALLATION. 2. COORDINATE LOCATION AND REQUIREMENTS FOR ELECTRICAL AND TELEPHONE SERVICES WITH THE PROPERTY REPRESENTATIVE, AT&T AND UTILITY COMPANIES. ROUTING OF CONDUITS MAY BE MODIFIED TO MEET SITE REQUIREMENTS. EXACT CONDUIT ROUTING TO BE DETERMINED IN THE FIELD. 3. ALL WIRING AND EQUIPMENT SHOWN ON ELECTRICAL SHEETS SHALL BE FURNISHED AND INSTALLED UNDER ELECTRICAL PORTION OF CONTRACT UNLESS OTHERWISE NOTED 4. UNINTERRUPTED ELECTRICAL SERVICE FOR EXISTING EQUIPMENT SHALL BE MAINTAINED DURING THE INSTALLATION OF THE WORK DESCRIBED UNDER THESE DOCUMENTS. TEMPORARY EQUIPMENT, CABLES AND WHATEVER ELSE IS NECESSARY SHALL BE PROVIDED AS REQUIRED TO MAINTAIN ELECTRICAL SERVICE. TEMPORARY SERVICE FACILITIES, IF REQUIRED AT ANY TIME, SHALL NOT BE DISCONNECTED OR REMOVED UNTIL NEW SERVICE EQUIPMENT IS IN PROPER OPERATION. IF ANY SERVICE OR SYSTEM MUST BE INTERRUPTED, THE CONTRACTOR SHALL REQUEST PERMISSION IN WRITING STATING THE DATE, TIME, ETC. THE SERVICE WILL BE INTERRUPTED AND THE AREAS AFFECTED. THIS REQUEST SHALL BE MADE IN SUFFICIENT TIME FOR PROPER ARRANGEMENTS TO BE MADE. WRITTEN PERMISSION SHALL BE OBTAINED FROM THE OWNER BEFORE INTERRUPTING ELECTRICAL SERVICE. 5. COORDINATE NEW WORK WITH OTHER TRADES AND VERIFY EXISTING CONDITIONS TO AVOID INTERFERENCE. IN CASE OF INTERFERENCE, AT&T'S REPRESENTATIVE WILL DECIDE WHICH WORK IS TO BE RELOCATED, REGARDLESS OF WHICH WAS FIRST INSTALLED. 6. THE INSTALLATION MUST COMPLY WITH NEC AND ALL FEDERAL, STATE AND LOCAL RULES AND REGULATIONS. 7. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND EQUIPMENT UNLESS OTHERWISE DEFINED BY DIMENSIONS OR DETAILS. EXACT EQUIPMENT LOCATIONS AND RACEWAY ROUTING SHALL BE GOVERNED BY ACTUAL FIELD CONDITIONS AND/OR DIRECTIONS FROM AT&T'S REPRESENTATIVE. 8. CONTRACTOR SHALL PAY ALL PERMITS AND FEES REQUIRED. 9. ALL MATERIALS SHALL BE FURNISHED AND WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE STANDARDS REFERENCED BELOW: a. ANSI (AMERICAN NATIONAL STANDARDS INSTITUTE) b. ASTIM (AMERICAN SOCIETY FOR TESTING MATERIALS) c. ETL (ELECTRICAL TESTING LABORATORY) d. ICEA (INSULATED CABLE ENGINEERS ASSOCIATION) e. IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS) f. MBFU (NATIONAL BOARD OF FIRE UNDERWRITERS) g. NESC (NATIONAL ELECTRICAL SAFETY CODE) h. NEMA (NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION) i. NFPA (NATIONAL FIRE PROTECTION ASSOCIATION) j. UL (UNDERWRITER'S LABORATORY) k. NEC (NATIONAL ELECTRICAL CODE) 10. CONTRACTOR SHALL REVIEW PLANS, DETAILS AND SPECIFICATIONS IN DETAIL AND ADJUST WORK TO CONFORM WITH ACTUAL SITE CONDITIONS SO THAT ELECTRICAL DEVICES AND EQUIPMENT WILL BE LOCATED AND READILY ACCESSIBLE. QUANTITIES LISTED IN MATERIAL LISTS ON THE DRAWINGS ARE FOR INFORMATION ONLY. THE CONTRACTOR SHALL PROVIDE HIS OWN TAKEOFF FOR MATERIAL QUANTITY AND TYPES BASED ON ACTUAL SITE CONDITIONS, IN ADDITION, CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIALS TO INSTALL EQUIPMENT FURNISHED BY AT&T OR ITS SUPPLIERS. ALL ITEMS NOT SPECIFICALLY MENTIONED HEREIN OR SHOWN ON THE DRAWINGS, BUT WHICH ARE OBVIOUSLY NECESSARY TO MAKE A COMPLETE WORKING INSTALLATION, SHALL BE INCLUDED. 11. THE CONTRACTOR OR BIDDER SHALL BEAR THE RESPONSIBILITY OF NOTIFYING (IN WRITING) AT&T'S REPRESENTATIVE OF ANY CONFLICTS PRIOR TO THE SUBMISSION OF CONTRACTOR'S PROPOSAL OR PERFORMANCE OF WORK, IN THE EVENT OF DISCREPANCIES THE CONTRACTOR SHALL PRICE THE MORE COSTLY OR EXTENSIVE WORK, UNLESS DIRECTED IN WRITING OTHERWISE. ELECTRICAL NOTES: 12. ALL FLOORS WHERE PENETRATIONS ARE REQUIRED IN BUILDING ARE TO BE CORE DRILLED AND THEN FIREPROOFED. B. WIRING/CONDUIT 1. PROVIDE PULL BOXES AND JUNCTION BOXES WHERE SHOWN OR AS REQUIRED BY CODE SUCH THAT NO MORE THAN THE EQUIVALENT OF FOUR QUARTER BENDS (360 DEGREES TOTAL) EXIST IN A CONDUIT RUN. 2. ALL POWER AND CONTROL/INDICATION WIRING SHALL BE TYPE THHN/THWN 600V RATED 75 DEGREES CELSIUS, UNLESS NOTED OTHERWISE. 3. CONDUIT BENDS SHALL BE MADE IN ACCORDANCE WITH NEC TABLE 346-10. NO RIGHT ANGLE DEVICE OTHER THAN STANDARD CONDUIT ELBOWS WITH 12" MINIMUM INSIDE SWEEPS FOR ALL CONDUITS 2" OR LARGER. 4. POWER WIRING SIZE SHALL NOT BE SMALLER THAN #12 AWG. 5. ALL WIRING SHALL BE COPPER. ALUMINUM WILL NOT BE ACCEPTABLE ALL POWER CIRCUITS SHALL CONTAIN A GROUND WIRE. 6. PHASE MARKINGS TO BE USED AT POWER CONDUCTOR TERMINATIONS. 7. CONTRACTOR SHALL ENSURE INTEGRITY IS MAINTAINED WHEN INSTALLING CONDUIT AND WIRING. 8. INSTALL PULL STRING IN ALL CONDUIT. 9. FOR ROOFTOP INSTALLS AND BUILD-OUTS, CONDUITS INSIDE BUILDING AND ON ROOF SHALL BE RGS, UNLESS OTHERWISE NOTED. FOR RAW LAND SITES AND CO-LOCATES, PVC SCHEDULE 80 SHALL BE UTILIZED UNLESS NOTED OTHERWISE. 10. MAINTAIN MINIMUM 1'-0" VERTICAL AND 1'-0" HORIZONTAL SEPARATIONS FROM ANY MECHANICAL GAS PIPING. 11. ALL WIRING ROUTED IN PLENUM TO BE RATED OR IN METALLIC FLEX (LIQUIDTITE) CONDUIT. C. EQUIPMENT 1. EQUIPMENT/PARTS CONNECTED TO EXISTING PANELS, DUCTS, ETC. SHALL MATCH THE CHARACTERISTICS (A/C, V, A) OF THAT EQUIPMENT. 2. ALL ELECTRICAL EQUIPMENT OUTSIDE SHALL BE NEMA 3R RATED. D. GROUNDING 1. ALL GROUND CONNECTIONS TO BUILDING SHALL BE MADE USING TWO-HOLE CONNECTORS. PROVIDE STAINLESS STEEL BOLTS AND LOCK WASHERS ON ALL MECHANICAL GROUND CONNECTIONS. 2. ALL EQUIPMENT SURFACES TO BE BONDED TO GROUNDING SYSTEM SHALL BE STRIPPED OF ALL PAINT AND DIRT AT ANY POINT OF CONNECTION. CONNECTIONS TO VARIOUS METALS SHALL BE OF A TYPE AS TO PREVENT A GALVANIC OR CORROSIVE REACTION. AREA SHALL BE REPAINTED FOLLOWING BONDING. 3. ANY METALLIC ITEM WITHIN 6' OF ANY EQUIPMENT OR METALLIC INFRASTRUCTURE (RACKS, CABLE TRAY.. ETC.) OR GROUND CONDUCTORS MUST BE CONNECTED TO THE GROUNDING SYSTEM PER AT&T STANDARDS. 4. EXTERIOR, ABOVE GRADE GROUND CONNECTIONS SHALL BE FURNISHED WITH A LIBERAL PROTECTIVE COATING OF ANTI-OXIDATION COMPOUND. 5. ALL MATERIALS AND LABOR REQUIRED FOR THE GROUNDING SYSTEM AS INDICATED ON THE PLANS AND DETAILS, AND AS DESCRIBED HEREIN SHALL BE FURNISHED BY THE CONTRACTOR UNLESS OTHERWISE NOTED. 6. EXACT LOCATION OF GROUND CONNECTION POINTS SHALL BE DETERMINED IN FIELD. ADJUST LOCATIONS INDICATED ON PLANS ACCORDING TO ACTUAL EQUIPMENT LOCATIONS TO KEEP THE GROUND CONNECTION CABLES AS SHORT AND STRAIGHT AS PRACTICAL. 7. PROVIDE ALL ELECTRICAL SYSTEM AND EQUIPMENT GROUNDS AS REQUIRED BY THE CURRENT EDITION OF THE NATIONAL ELECTRIC CODE, THE CURRENT EDITION OF THE NATIONAL ELECTRICAL SAFETY CODE AND AT&T STANDARDS. BONDING JUMPERS WITH APPROVED GROUND FITTINGS SHALL BE INSTALLED AT ALL RACEWAYS, EQUIPMENT ENCLOSURES, PULL BOXES, ETC. TO MAINTAIN GROUND CONTINUITY WHERE REQUIRED BY CODE. 8. ALL BURIED EQUIPMENT GROUND CONDUCTORS SHALL BE #2 AWG BARE, TINNED, SOLID COPPER UNLESS NOTED OTHERWISE ON THE DRAWINGS. E. INSPECTION/DOCUMENTATION 1. THE CONTRACTOR, UPON COMPLETION OF HIS WORK, SHALL PROVIDE AS-BUILT DRAWINGS. INFORMATION SHOULD BE GIVEN TO THE GENERAL CONTRACTOR FOR INCLUSION IN FINAL AS-BUILT SURVEY DOCUMENTS TO BE GIVEN TO THE OWNER. 2. CONTRACTOR SHALL SUPPLY DOCUMENTATION ATTESTING TO THE COMPLETE GROUND SYSTEM'S RESISTANCE TO GROUND (MAX. 5 OHMS). 3. AN ELECTRICAL INSPECTION SHALL BE MADE BY AN INSPECTING AGENCY APPROVED BY AT&T'S REPRESENTATIVE. CONTRACTOR SHALL COORDINATE ALL INSPECTIONS AND OBTAIN POWER COMPANY APPROVAL. 4. CONTRACTOR SHALL HAVE ATS AND GENERATOR RELAY INSTALLATION AND CONNECTIONS INSPECTED BY OTHERS TO ENSURE THAT UL LISTING FOR THAT EQUIPMENT IS NOT VOIDED. 230817 REQUIRED SPECIAL INSPECTIONS: 1. PER IBC 1705.4 SPECIAL INSPECTION OF MASONRY. (IF REQUIRED) CEC l. CEC (CALIFORNIA ELECTRICAL CODE)CBC GENERAL NOTES PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: N-1 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD RADIATOR/EXHAUST/FUEL ENDDISCHARGEBATTERY BOXPOWER CENTER &CONTROLSBOLT ON PANELS 5' VENTRADIUS5' VENTRADIUS PARCEL SITE PLAN PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: A-0 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD PARCEL SITE PLAN N 1SCALE: 1" = 400'-0" (11x17)200 FEET NORTH OF ORO QUINCY HIGHWAYOROVILLE, CA 95966TAX ID#: 068-150-099NOTE: EVERYTHING SHOWN IS EXISTING UNLESS MARKED PROPOSED EXISTING CONDITIONS: THESE DRAWINGS WERE PRODUCED WITH INFORMATION PROVIDED BY THE CLIENT. LINES, EASEMENTS, AND SETBACKS SHALL BE VERIFIED PRIOR TO START OF CONSTRUCTION, GEOSTRUCTURAL DOES NOT GUARANTEE THE ACCURACY OF SAID PROPERTY LINE, EASEMENTS AND SETBACKS. PROJECT SITE, SEE SHEET A-1 FOR OVERALL SITE PLAN PARCEL LINE PARCEL LINEPARCEL LINEPARCEL LINEOROVILLE Q U I N C Y H W Y X X X X XXXXXXXXXXXXX XX XXXXXX X XX X X XRADIATOR/EXHAUST/FUEL END DISCHARGE BATTERY BOXPOWER C E N T E R &CONTROLSBOLT ON PA N E L S 5' VENTRADIUS 5' VENTRADIUS OVERALL SITE PLAN PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: A-1 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD OVERALL SITE PLAN N 1SCALE: 1" = 50'-0" (11x17) PROPOSED GENERATOR LOCATION, SEE SHEET A-2 FOR ENLARGED SITE PLAN 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 TAX ID#: 068-150-099 NOTE: EVERYTHING SHOWN IS EXISTING UNLESS MARKED PROPOSED EXISTING CONDITIONS: THESE DRAWINGS WERE PRODUCED WITH INFORMATION PROVIDED BY THE CLIENT. LINES, EASEMENTS, AND SETBACKS SHALL BE VERIFIED PRIOR TO START OF CONSTRUCTION, GEOSTRUCTURAL DOES NOT GUARANTEE THE ACCURACY OF SAID PROPERTY LINE, EASEMENTS AND SETBACKS. AT&T CONCRETE EQUIPMENT PAD (BELOW TRANSMISSION TOWER)OVERHEAD CONDUCTORSPG&E LATTICE TRANSMISSION TOWER w/ AT&T ANTENNAS (ANTENNAS NOT SHOWN) P E1 AT&T LEASE AREAS EXISTING APPROXIMATE 12'-0"x25'-0" (300 SQ.FT.) LEASE AREA PROPOSED 17'-0"x10'-0" (170 SQ.FT.) GENERATOR LEASE AREA EXISTING LEASE AREA SIZES WERE OBTAINED FROM LEASE DOCUMENTS PROVIDED TO GEOSTRUCTURAL AND ARE SHOWN FOR REFERENCE ONLY. REFER TO FINAL LEASE DOCUMENTS FOR APPROVED EXISTING AND PROPOSED LEASE AREAS. E1 P PARCEL LINEPARCEL LINEPARCEL LINEPARCEL BOUNDARYPARCEL BOUNDARY35'-9" OROVILLE QUI N C Y H W Y DIRT ACCESS DRIVE ACCESS GATES CUMULATIVE VOLUME CALCULATIONS: THE PHYSICAL DIMENSIONS OF THE PROPOSED GENERATOR w/ ENCLOSURE AND BASE FUEL TANK ARE LESS THAN 250 CU. FT. IN VOLUME. BASE FUEL TANK = 120.2"x43.0"x34.5" = 103.2 CU. FT. GENERATOR BODY w/ ENCLOSURE = 94.8"x61.1"x38" = 127.4 CU. FT. TOTAL CUMULATIVE VOLUME OF GENSET = 103.2 + 127.4 = 230.6 CU. FT. GENSET USE, CEQA & BAAQMD EXEMPTION: THE PROPOSED GENERAC SD030 GENSET: * IS RATED AT 49 HP AT MAXIMUM RATED kW OUTPUT, * IS INSTALLED WITH AN ABOVE-GROUND DOUBLE-WALL SECONDARY CONTAINMENT BALLISTIC BASE FUEL TANK WITH 132 USABLE (140 MAX) GALLONS OF FUEL, * USES ULTRA LOW SULFUR DIESEL FUEL (15 ppm SULFUR), * IS LIMITED TO 100 HOURS PER YEAR OF NON-EMERGENCY USE (TESTING & MAINTENANCE), * IS INSTALLED WITH A LEVEL 2 ACOUSTIC ENCLOSURE, WHICH BUFFERS SOUND OUTPUT TO A MAXIMUM OF 62 dB AT 7 METERS (~23 FEET), * IS COMPLIANT WITH APPLICABLE AIR QUALITY REGULATIONS, * IS EXEMPT FROM AIR QUALITY PERMITS IN MOST JURISDICTIONS UNDER THE PROVISIONS OF CLASS 1, SEC. 15301 OF THE CALIFORNIA ENVIRONMENTAL QUALITY ACT (CEQA) GUIDELINES, * IS EXEMPT PER BAAQMD REG. 2, RULE 1, SEC. 2-1-114-2.2.1.; LESS THAN 50 BHP. X X X X XXXXXXXXXXXXXXXXXXXXXXXXXXXRADIATOR/EXHAUST/FUEL ENDDISCHARGEBATTERY BOXPOWER CENTER &CONTROLSBOLT ON PANELS5' VENTRADIUS5' VENTRADIUS 1ENLARGED SITE PLAN N SCALE: 1/4" = 1'-0" (11x17) UTILITY NOTE: THE UTILITIES AS SHOWN ON THIS SET OF DRAWINGS WERE DEVELOPED FROM RECORD INFORMATION. THE INFORMATION PROVIDED IS IMPLIED NOT INTENDED TO BE A COMPLETE INVENTORY OF THE UTILITIES IN THIS AREA. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE LOCATION OF ALL UTILITIES (WHETHER SHOWN OR NOT) AND PROTECT SAID UTILITIES FROM ANY DAMAGE CAUSED BY CONTRACTOR'S ACTIVITIES. EXISTING CONDITIONS: THESE DRAWINGS WERE PRODUCED WITH INFORMATION PROVIDED BY THE CLIENT. LINES, EASEMENTS, AND SETBACKS SHALL BE VERIFIED PRIOR TO START OF CONSTRUCTION, GEOSTRUCTURAL DOES NOT GUARANTEE THE ACCURACY OF SAID PROPERTY LINE, EASEMENTS AND SETBACKS. SCOPE OF WORK DETAILS: GENERAL: · NEW GENERAC DIESEL GENERATOR PROVIDED BY GENERAL DYNAMICS & INSTALLED BY GENERAL CONTRACTOR. SEE SHEETS E-4.0, E-4.1, E-4.2. · NEW CONCRETE PAD PROVIDED & INSTALLED BY GENERAL CONTRACTOR. SEE SHEET S-1. · NEW GENERAC AUTOMATIC TRANSFER SWITCH PROVIDED BY GENERAL DYNAMICS & INSTALLED BY CONTRACTOR. SEE SHEETS S-2, E-5.0, E-5.1. · NEW COMPOUND FENCE AND CONCRETE FOUNDATION EXPANSION PROVIDED & INSTALLED BY GENERAL CONTRACTOR. SEE SHEETS S-3, S-4. · CONTRACTOR TO VERIFY ALL EXISTING UTILITIES PRIOR TO CONSTRUCTION. · CONTRACTOR SHALL RESTORE & REPAIR ANY DAMAGED AREAS CAUSED BY CONSTRUCTION TO ORIGINAL OR BETTER CONDITION. · INNER AND OUTER TANK TESTING DOCUMENTATION SHALL BE PROVIDED ONCE TANK IS IN PLACE ON SITE IN ACCORDANCE WITH NFPA 30. · A CALIBRATION CHART OF PERMANENT AND DURABLE CONSTRUCTION SHALL BE LOCATED AT THE FILL BOX. CONDUITS: · INSTALL PULL STRING IN EACH CONDUIT. · (2) NEW ELECTRICAL CONDUITS WITH CONDUCTORS TO BE INSTALLED FROM NEW GENERATOR TO NEW ATS. CONDUIT PROVIDED AND INSTALLED BY GENERAL CONTRACTOR. SEE SHEETS E-1, E-2. · (2) NEW ELECTRICAL CONDUITS WITH CONDUCTORS TO BE INSTALLED FROM NEW GENERATOR TO AC PANEL. CONDUIT PROVIDED & INSTALLED BY GENERAL CONTRACTOR. SEE SHEETS E-1, E-2. · (1) NEW ALARM CONDUIT & CABLING PROVIDED & INSTALLED BY GENERAL CONTRACTOR. SEE SHEETS E-1, E-2. GROUNDING: · NEW EXOTHERMIC CONNECTION FROM EXISTING GROUND RING TO NEW MECHANICAL CONNECTION AT GENERATOR CHASSIS. GENERAL CONTRACTOR TO VERIFY LOCATION IN FIELD. LOCATE GROUND RODS NO MORE THAN 8'-0" APART. SEE SHEET E-3. H-FRAME: · CONTRACTOR TO PROVIDE NEW H-FRAME FOR ATS INSTALLATION (IF REQUIRED). MATCH EXISTING H-FRAME MATERIAL FOR CONSTRUCTION OF NEW H-FRAME. SEE SHEET S-2. R GENERATOR KEYED NOTES: PROPOSED AT&T 30KW DIESEL GENERATOR w/ SOUND ATTENUATED ENCLOSURE, NORMAL/EMERGENCY TANK VENTING AND BASE FUEL TANK. SEE SHEETS S-1, S-2, E-3. FUEL FILL SHALL BE PROVIDED WITH SPILL CONTROL, WITH A SOLID FILL CONNECTION, AND WITH OVERFILL PREVENTION FUEL TANK NORMAL AND EMERGENCY VENTS SHALL TERMINATE AT LEAST 12'-0" ABOVE THE ADJACENT GRADE. SEE SHEET S-2. NFPA 704 PLACARD AND OTHER SIGNAGE. SEE SHEET S-2. GEN 1 2 3 INT CON GEN 1 2 3 FIRE OFF NOTE: EVERYTHING SHOWN IS EXISTING UNLESS MARKED PROPOSED H-FR ATS / EQUIPMENT KEYED NOTES: -FIRE EXTINGUISHER, (2A-20BC OR APPROVED EQUAL) PER CFC 906.3 -FIRE EXTINGUISHER CABINET (BFC-7009 OR APPROVED EQUAL), MOUNT TO H-FRAME PER CFC 906.9 (5'-0" MAX. ABOVE GRADE) LOCKABLE EMERGENCY SHUTOFF SWITCH, MOUNT TO H-FRAME PER CFC 906.9 (5'-0" MAX. ABOVE GRADE) PROPOSED ATS w/ CAMLOCK MOUNTED TO NEW H-FRAME WITH 36" FRONT CLEARANCE. SEE SHEET S-2. PROPOSED H-FRAME WITH UNISTRUT RAILS, SEE SHEET S-2. FIRE OFF ATS H-FR POWER ROUTING KEYED NOTES: EXISTING INTEGRATED LOAD CENTER (ILC) INTERCEPT EXISTING CONDUIT AND CONDUCTORS PRIOR TO ILC AND RE-ROUTE THROUGH PROPOSED ATS (~10'). COORDINATE PATH WITH CONSTRUCTION MANAGER PROPOSED AT&T RIGID CONDUIT ROUTE. ATTACH CONDUIT TO TOP SURFACE OF CONCRETE. MARK WITH HAZARD PAINT. SEE SHEET E-2. SEE SHEET E-1 FOR SINGLE LINE DIAGRAM. ILC INT CON DIESEL GENERATOR w/ UL-2085 FUEL TANK PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: A-2 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD ENLARGED SITE PLANACCESS CLEARANCE, TYP.36" BREAKERS/ALTERNATOR24" INTAKE/EXHAUSTCABINET CABINET CABINET CABINET EQUIPMENT H-FRAME UTILITY H-FRAME AT&T 12'X25' CONCRETE EQUIPMENT PAD (BELOW TRANSMISSION TOWER) RADIO HEAD EQUIPMENT H-FRAME PROPOSED 9' TALL CHAIN-LINK FENCE WITH CHAIN-LINK SECURITY TOPPER, SEE SHEET S-3 CONCRETE TOWER FOUNDATION, TYP. CONCRETE STOOP GEN PLUG 3'-5" 3'-0"10'-0" FOUNDATION 3'-0"17'-0"FOUNDATION3'-0"EXISTING 6' TALL CHAIN-LINK FENCE WITH SECURITY TOPPER, FENCE POSTS TO ANCHORED TO TOP OF EXISTING CONCRETE SLAB. PROPOSED 36" WIDE x 4" THICK CONCRETE APRON ON 2" SAND BASE AROUND PERIMETER OF CHAIN-LINK FENCE AS SHOWN. PROVIDE TOOLED JOINTS AT 4'-0" O.C. AND AT INTERFACES BETWEEN EXISTING CONCRETE/STRUCTURAL ELEMENTS. SLOPE AWAY FROM COMPOUND 1/4" PER FOOT. SUBGRADE TO BE CLEARED, GRUBBED, PROOF-ROLLED AND COMPACTED TO 90% MAXIMUM DENSITY PER D1557. PROVIDE EXPANSION JOINT; DO NOT TIE NEW APRON INTO EXISTING CONCRETE, TYP. 3'-0" 3'-0"3'-5"APPROXIMATE LOCATION OF OVERHEAD CONDUCTORS APPROXIMATE LOCATION OF OVERHEAD CONDUCTORS 9'-11"±4'-9"3'-5" PROVIDE EXPANSION JOINT BETWEEN PROPOSED AND EXISTING CONCRETE PROPOSED CONCRETE COMPOUND EXPANSION. SEE SHEETS S-1 AND S-4. SET TOP OF CONCRETE ELEVATION AT SAME ELEVATION AS EXISTING COMPOUND PAD. 48" SQUARE CONCRETE APRON EXTENSION CENTERED ON ACCESS GATE AS SHOWN PROPOSED 4'-0"± WIDE x 6' TALL CHAIN-LINK SWING GATE w/ GATE STOP, SEE SHEET S-3. EXISTING 4'-0"± WIDE x 6' TALL CHAIN-LINK SWING GATE w/ GATE STOP ~1'-8" PG&E LATTICE TRANSMISSION TOWER w/ AT&T ANTENNAS CONTRACTOR TO COVER ANY GAP BETWEEN THE 6' FENCE & 9' FENCE WITH A FENCE SECTION AS REQUIRED TO MAINTAIN SECURITY. SEE SHEET S-3 ILC ATS METER UNDER TOWER INSTALLATION NOTE: CONTRACTOR TO COORDINATE WITH PG&E AND CONSTRUCTION MANAGER TO ANALYZE TOWER FOR POTENTIAL BRACING MEMBER TEMPORARY REMOVAL DURING INSTALLATION OF GENERATOR (IF REQUIRED). UNDER NO CIRCUMSTANCES ARE ANY TOWER BRACING MEMBERS TO BE TEMPORARILY REMOVED WITHOUT FIRST OBTAINING PERMISSION AND VERIFICATION FROM PG&E AND RESPONSIBLE THIRD-PARTY ENGINEER IN CHARGE OF EXAMINING TOWER STRENGTH AND STABILITY WITH SAID BRACING MEMBER(S) TEMPORARILY REMOVED. ANY MEANS AND METHODS OF TEMPORARY BRACING REMOVAL SHALL BE CONDUCTED IN ACCORDANCE WITH THE RECOMMENDATIONS OF PG&E AND THE THIRD-PARTY ENGINEER IN CHARGE, AND ARE OUTSIDE THE SCOPE OF THIS WORK. GRADE0'-0" TOP OF VENTILATION PIPES12' MIN. *UL2085* TOP OF GENERATOR8'-8" PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: A-3 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD ELEVATION VIEWS 2SCALE N.T.S.1SCALE N.T.S.EXISTING ELEVATION VIEW PROPOSED ELEVATION VIEW TOP OF TRANSMISSION TOWER147'-0"± PROPOSED AT&T DIESEL GENERATOR WITHIN PROPOSED COMPOUND EXPANSION VENT PIPE, TYP. OF (3) PG&E LATTICE TRANSMISSION TOWER w/ AT&T ANTENNAS (ANTENNAS NOT SHOWN) EXISTING AT&T EQUIPMENT COMPOUND PROPOSED 9' TALL CHAIN-LINK FENCE W/ CHAIN-LINK SECURITY TOPPER GRADE0'-0" EXISTING 6' TALL CHAIN-LINK FENCE w/ SECURITY TOPPER FS SEE SITE PLAN1'-0" BLOCKOUT 2'-7"BLOCKOUT2"BASE EXTENTS PERMANUFACTURER#4 U-BARS CONDUIT STUB-UP AREA; CONFIRM LOCATION & SIZE WITH MANUFACTURER (BLOCKOUT NOT REQ'D IF RUNNING CONDUITS ALONG SURFACE) A SEE SITE PLAN BASE EXTENTS PER MANUFACTURER OUTLINE OF GENERATOR FOOTPRINT SLAB REINFORCEMENT, SEE SHEET S-4 A GENERATOR PAD - SECTION A-A GENERATOR PAD DETAIL #4 U-BARS CONDUIT STUB-UP AREA FLEXIBLE STUB CONDUITS. SEE SHEET E-2. CONCRETE PAD 134" CLR. TYP. LONGITUDINAL TRANSVERSESCALE: 1/2"=1'-0"(11x17) 1"=1'-0" (24x36) SCALE: 1/2"=1'-0"(11x17) 1"=1'-0" (24x36) (8) 58"Ø x 334" EMBED HILTI KWIK BOLT TZ2 STAINLESS STEEL EXPANSION ANCHOR (OR APPROVED EQUAL). REFERENCE ICC-ES ESR-4266 REPORT. INSTALLATION TORQUE = 60 FT-LB 6"414"HOLE DEPTH1116"Ø HOLE (58"Ø BIT) ANCHOR FRAME TYPICAL ANCHOR334"EMBEDMENTCONCRETE NOTES: 1.PRIOR TO EXCAVATION, CHECK THE AREA FOR UNDERGROUND FACILITIES. 2.ALL CONCRETE SHALL BE IN ACCORDANCE WITH CHAPTER 19 OF THE IBC & ACI 318, "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", LATEST EDITION & HAVE THE FOLLOWING PROPERTIES: A MINIMUM 28-DAY COMPRESSIVE STRENGTH (f'c) OF 4,000 PSI. B CEMENT SHALL BE "LOW-ALKALI" TYPE IIA (MODERATE SULFATE RESISTANCE, AIR ENTRAINING) CONFORMING TO ASTM C150. C MAXIMUM WATER/CEMENT RATIO OF 0.45 AND AIR-ENTRAINED 4% TO 7%. D CONCRETE PROPORTIONING SHALL BE DESIGNED BY AN APPROVED LABORATORY. TOLERANCES IN ACCORDANCE WITH ACI 117. COPIES OF CONCRETE MIX SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO PLACEMENT. E ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. USE ONLY AGGREGATES KNOWN NOT TO CAUSE EXCESSIVE SHRINKAGE. MAXIMUM AGGREGATE SIZE TO BE 34". F MAXIMUM SLUMP: REFER TO GEOTECHNICAL REPORT WHEN APPLICABLE. 3.FORMWORK FOR CONCRETE SHALL CONFORM TO ACI 347. TOLERANCES FOR FINISHED CONCRETE SURFACES SHALL MEET CLASS-C REQUIREMENTS. IN NO CASE SHALL FINISHED CONCRETE SURFACES EXCEED THE FOLLOWING VALUES AS MEASURED FROM NEAT PLAN LINES AND FINISHED GRADES: ± 14" VERTICAL, ± 1" HORIZONTAL. 4.CHAMFER ALL EXPOSED CORNERS AND FILLET ENTRANT ANGLES 34" U.N.O. 5.CONCRETE FINISHING: CONCRETE SURFACES SHALL BE FINISHED IN ACCORDANCE WITH ACI. PROVIDE ROUGH FINISH FOR ALL SURFACES NOT EXPOSED TO VIEW AND SMOOTH FINISH FOR ALL OTHERS, U.N.O. 6.STEEL REINFORCEMENT AND CONCRETE SHOULD BE PLACED IMMEDIATELY UPON COMPLETION OF THE FOUNDATION EXCAVATION. CONTRACTOR SHALL NOT ALLOW A COLD JOINT TO FORM IN THE CONCRETE. PORTION AT GRADE SHOULD BE FORMED. TEMPORARY CASING MAY BE REQUIRED TO PREVENT CAVING PRIOR TO CONCRETE PLACEMENT. REINFORCING STEEL NOTES: 1.ALL REINFORCING STEEL SHALL CONFORM TO ASTM A615. VERTICAL/HORIZONTAL BARS SHALL BE GRADE 60; TIES OR STIRRUPS SHALL BE A MINIMUM OF GRADE 40. ALL REINFORCING STEEL SHALL HAVE 3" (± 38") OF CONCRETE COVER, U.N.O. 2.ALL BAR BENDS, HOOKS, SPLICES AND OTHER REINFORCING STEEL SHALL CONFORM TO THE REQUIREMENTS OF ACI 315. 3.ALL BARS SHALL BE SPLICED WITH A MINIMUM LAP OF 48 BAR DIAMETERS. LAP SPLICES OF DEFORMED BARS IN TENSION ZONES SHALL BE CLASS-B SPLICES. WELDING OF BARS IS NOT PERMITTED. 4.AT ALL CORNERS AND WALL INTERSECTIONS, PROVIDE BENT HORIZONTAL BARS TO MATCH THE HORIZONTAL REINFORCING STEEL. 5.PROVIDE VERTICAL DOWELS IN FOOTINGS AND AT CONSTRUCTION JOINTS TO MATCH VERTICAL REINFORCING BAR SIZE AND SPACING. 6.ACI-APPROVED PLASTIC-COATED BAR CHAIRS OR PRECAST CONCRETE BLOCKS SHALL BE PROVIDED FOR SUPPORT OF ALL GRADE-CAST REINFORCING STEEL & SHALL BE SUFFICIENT IN NUMBER TO PREVENT SAGGING. METAL CLIPS OR SUPPORTS SHALL NOT BE PLACED IN CONTACT WITH THE FORMS OR THE SUB-GRADE. 7.DOWELS AND ANCHOR BOLTS SHALL BE WIRED OR OTHERWISE HELD IN CORRECT POSITION PRIOR TO PLACING CONCRETE. IN NO CASE SHALL DOWELS OR ANCHOR BOLTS BE "STABBED" INTO FRESHLY-POURED CONCRETE. MECHANICAL ANCHOR NOTES: 1.HILTI PRODUCTS MUST BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS, AS INCLUDED IN THE PACKAGING. 2.CONTRACTOR SHALL AVOID DRILLING HOLES IN VERTICAL/HORIZONTAL REINFORCING BARS. 3.HOLES MUST BE WIRE BRUSHED AND BLASTED WITH COMPRESSED AIR PRIOR TO INSTALLATION. TEMPERATURES/METHODS/WORKING TIME/ETC. ARE TO BE IN ACCORDANCE WITH MANUFACTURER SPECIFICATIONS. FOUNDATION & SOIL NOTES: 1.FOUNDATION DESIGN BASED ON PRESUMPTIVE MINIMUM SOIL PARAMETERS (ALLOWABLE BEARING = 1,500 PSF; ALLOWABLE PASSIVE SLIDING = 100 PSF/FT) IN ACCORDANCE WITH THE IBC. 2.THE EXCAVATION SHALL BE INSPECTED PRIOR TO THE PLACEMENT OF CONCRETE AND THE CONTRACTOR SHALL PROVIDE A NOTICE OF INSPECTION FOR THE BUILDING INSPECTOR FOR REVIEW AND RECORDS PURPOSES. 3.THE CONTRACTOR SHALL DETERMINE THE MEANS AND METHODS NECESSARY TO SUPPORT THE EXCAVATION DURING CONSTRUCTION. 4.ALL FOUNDATIONS TO BE PLACED ON FIRM, UNDISTURBED, INORGANIC MATERIAL. PROOF ROLL SUB-GRADE PRIOR TO PLACING CONCRETE WHERE THE MATERIAL HAS BEEN DISTURBED BY EQUIPMENT. UNACCEPTABLE/DISTURBED MATERIAL SHALL BE OVER-EXCAVATED AND REPLACED WITH "LEAN CONCRETE FILL" OR REPLACED WITH STRUCTURAL BACKFILL. 5.STRUCTURAL BACKFILL SHALL BE GRANULAR FREE-DRAINING MATERIAL FREE OF DEBRIS, ORGANICS, REFUSE AND OTHERWISE DELETERIOUS MATERIALS. MATERIAL SHALL BE PLACED IN LIFTS NO GREATER THAN 6" IN DEPTH AND COMPACTED TO 95% OF MAXIMUM DENSITY AS DETERMINED PER ASTM D1557 (MODIFIED PROCTOR). CBC 2,500 AND CBC. 1,000 GENERATOR PAD DETAILS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: S-1 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD STRUCTURAL DESIGN NOTES: ALL LOADS DERIVED FROM REQUIREMENTS OF THE IBC 2021, CBC 2022, ASCE 7 & ANSI TIA-222. BUILDING & COMMUNICATION STRUCTURES: (39.506867° / -121.502308°) 1.WIND LOADS: IBC 2021, CBC 2022 & ASCE 7-16 w/ SUPPLEMENT 1 V = 94 MPH ULTIMATE WIND SPEED STRUCTURE CLASS = II; EXPOSURE CATEGORY = C; TOPOGRAPHIC CATEGORY = 1. IMPORTANCE FACTOR = 1.0. 2.SEISMIC LOADS: IBC 2021, CBC 2022 & ASCE 7-16 w/ SUPPLEMENT 1 STRUCTURE CLASS = II; SITE CLASS = D - DEFAULT. SS = 0.634 ; S1 = 0.272 ; SDS = 0.546 ; ap = 1.0 ; Rp = 2.5 (10) #4 REBAR INSTALLED @ 12" O.C. S-4 G DOUBLE WALL FUEL TANK BASE SPECIFICATION: REF: AT&T 30KW GENERATOR PACKAGE UL REGISTRATION NUMBER: MH 18459 UL 142 DOUBLE WALL FUEL TANK BASE SPECIFICATION FUEL TANK BASE CONSTRUCTION: + BE CONSTRUCTED IN ACCORDANCE WITH UNDERWRITERS LABORATORIES STANDARD UL-142. BE CONSTRUCTED IN ACCORDANCE WITH FLAMMABLE COMBUSTIBLE LIQUIDS CODE, NFPA 30; THE STANDARD FOR INSTALLATION USE OF STATIONARY COMBUSTIBLE ENGINE GAS TURBINES, NFPA 37; AND THE STANDARD FOR EMERGENCY STANDBY POWER SYSTEMS, NFPA 110. +MINIMUM ANCHOR QUANTITY PER MANUFACTURER OR THIS PLAN SET; WHICHEVER IS LARGER. SUB BASE TANK TESTING: +PRIMARY TANK & SECONDARY CONTAINMENT BASIN SECTIONS SHALL BE PRESSURIZED AT 3-5 PSI AND LEAK-CHECKED TO ENSURE INTEGRITY OF SUB BASE WELD SEAMS PER UL-142 STANDARDS FUEL FILL: 2.5 - 5 GALLON SPILL CONTAINMENT WITH ALARM +40% REMAINING FOR ALARM +20% REMAINING FOR SHUT-DOWN FACTORY PRE-SET AT 90% FULL FOR ALARM FUEL CONTAINMENT BASIN: + SUB BASE TANK SHALL INCLUDE A WELDED STEEL CONTAINMENT BASIN, SIZED AT A MINIMUM OF 110% OF THE TANK. CAPACITY TO PREVENT ESCAPE OF FUEL INTO THE ENVIRONMENT IN THE EVENT OF A TANK RUPTURE. A FUEL CONTAINMENT BASIN LEAK DETECTOR SWITCH SHALL BE PROVIDED. 15" x 15" SIGN PLACE ON (2) VISIBLE SIDES OF PROPOSED GENERATOR TANK 11" x 11" SIGN PLACE ON (2) VISIBLE SIDES OF PROPOSED GENERATOR TANK 6.5" x 3" SIGN DIESEL TANK CHECKLIST: READILY ACCESSIBLE MANUAL SHUTOFF VALVES SHALL BE INSTALLED ON SUPPLY PIPING AT THE POINT OF USE AND THE TANK (IFC 5003.2.2.1) SECONDARY CONTAINMENT-TYPE TANKS SHALL BE UL LISTED, UL-142, AND COMPLY WITH ALL OF THE FOLLOWING REQUIREMENTS; OTHERWISE TRADITIONAL SPILL CONTROL OR SECONDARY CONTAINMENT MEASURES, SUCH AS DIKING, SHALL BE UTILIZED (NFPA 30 22.11.4) +CAPACITY OF DIESEL TANK SHALL NOT EXCEED 50,000 GAL. +PIPING CONNECTIONS SHALL BE ABOVE THE LIQUID LEVEL +MEANS SHALL BE PROVIDED TO PROTECT RELEASE OF LIQUID BY SIPHON FLOW. +MEANS TO DETERMINE LIQUID LEVEL IN TANK SHALL BE PROVIDED TO DRIVER. +MEANS TO PREVENT OVERFILLING BY AN ALARM AT 90% CAPACITY AND AUTOMATICALLY STOPPING DELIVERY OF LIQUID TO THE TANK AT 95% CAPACITY. +SPACING BETWEEN ADJACENT TANKS SHALL NOT BE LESS THAN 3'. +TANK SHALL BE PROTECTED AGAINST DAMAGE FROM VEHICLES. +INTERSTITIAL SPACE SHALL HAVE EMERGENCY VENTING. +INTEGRITY OF SECONDARY CONTAINMENT SHALL BE ESTABLISHED. +THE SECONDARY CONTAINMENT SHALL WITHSTAND THE HYDROSTATIC HEAD OF THE MAXIMUM AMOUNT OF LIQUID STORED IN THE PRIMARY TANK. TANK LABELING AND PROTECTIONS: THE FOLLOWING SIGNS AND LABELS SHALL BE AFFIXED TO THE TANK. +"DIESEL FUEL - NO SMOKING" (IFC 5703.5 & IFC 5003.7.1) +NFPA 704 PLACARD (IFC 5003.5) +EH&S +AT&T MOBILITY SIGN #3 CRASH PROTECTION COMPLYING WITH IFC 312 SHALL BE PROVIDED (IFC 5003.9.3) (IF APPLICABLE) GENERATOR FEATURES: GENERATORS SHALL BE UL 2200 LISTED AND COMPLY WITH NFPA 37 AND NFPA 110. (IFC 1203.1.1) INSTALLATIONS SHALL HAVE A LABELED REMOTE MANUAL STOP (NFPA 110 5.6.5.6 & 5.6.5.6.1 AND NFPA 37 9.2.1.1) NEPA NOTES: 1.CONSTRUCTION, INSTALLATION, MAINTENANCE, & OPERATIONAL TESTING OF EPSS SHALL COMPLY WITH THE LATEST ADOPTED EDITION OF NFPA 110. 2.ALL ELECTRICAL WORK SHALL COMPLY WITH LATEST ADOPTED EDITION OF NFPA 70 - NATIONAL ELECTRICAL CODE. FUEL TANK NOTES: THE TANK SHALL BE MANUFACTURED WITH THE FOLLOWING: -INTERSTITIAL ELECTRONICALLY MONITORED RUPTURE BASIN -ALARM TO MONITOR THE SPACE BETWEEN THE PRIMARY AND SECONDARY TANK. -OVERFILL ALERT TO VISUALLY WARN WHEN THE TANK IS FILLED UPON CAPACITY. -OVERSPILL CONTAINMENT AT FILL PORT TO PREVENT SPILL OF FUEL DURING FILLING OPERATIONS. -2.5/5 GALLON OVERSPILL CONTAINMENT W/ LOCKABLE CAP. REQUIRED LABELING & SIGNAGE CONTRACTOR TO PROVIDE REQUIRED SIGNAGE FOR ELECTRICAL PANELS, DISCONNECTS, TRANSFER SWITCHES, ETC. PER NATIONAL ELECTRICAL CODE ARTICLE 702.7 SECTION A-A 38"Ø STAINLESS STEEL U-BOLT w/ NUT AND LOCK-WASHER. MAX. U-BOLT TORQUE = 30 FT-LBS. GALVANIZED H-FRAME POST 3'-0" MIN. (4'-0" MIN. IF SUB PANEL REQ'D)6'-0"PIPE CAP, TYP. H-FRAME DETAIL (IF REQUIRED) A A 6" MAX. 158" P1000T UNISTRUT MEMBER INSTALLED TO H-FRAME POSTS. APPLY TWO COATS OF COLD-GALV COMPOUND TO "CUT" ENDS. INSTALL VINYL END CAPS. (TO BE FIELD LOCATED AS REQUIRED)3-0" (MIN.) OR PERLOCAL FROST DEPTH4"49.4" (VERIFY W/ATS MANUF.)NEW PIPE2.5STD (2.875"OD SCHEDULE 40) H-FRAME POST, TYP. (ALTERNATE INSTALLATION: CONTRACTOR MAY ELECT TO USE EXISTING H-FRAME POST IF AVAILABLE)2"AUTOMATIC TRANSFER SWITCH CAM-LOCKBOXEMERGENCY SHUTOFF SWITCH 12"Ø CONCRETE FOOTING (f'c=2,500 psi) ⅊34x7x7 (4) 12"Ø x 334" EMBED HILTI KWIK BOLT TZ2 STAINLESS STEEL EXPANSION ANCHOR (OR APPROVED EQUAL). REFERENCE ICC-ES ESR-4266 REPORT. 3.75" 3/16 POST FOOT PAD FOR SLAB-TOP INSTALLATION (IF APPLICABLE) 1" DRY PACK, IF REQ'D 5"3"(MIN.) TO EDGE OF SLAB 1" CROWN OR FOOTPAD #2 SOLID, TINNED BARE COPPER WIRE CADWELD POSTS TO GROUND RING GROUND RING ATS LOCATION NOTE: ATS LOCATION SHOWN IN PLANS IS THE BEST AVAILABLE BASED ON THE INFORMATION PROVIDED. ALTERNATIVE LOCATION MAY BE REQUIRED AND SHALL BE APPROVED BY CONSTRUCTION MANAGER AND/OR LANDLORD. THIS DETAIL PROVIDES ALTERNATIVE METHODS OF INSTALLATION (NOT ALL DETAILS MAY BE USED). [MAX. ATS + CAM-LOCK WEIGHT = 210 LBS] GRADE PROPOSED GENERATOR W/ DIESEL FUEL TANK ON CONCRETE PAD VENT PIPE, TYP. OF (3)12' MIN.GENERATOR VENTING DETAIL VENT BRACING TO ENCLOSURE PER MANUFACTURER ATS MOUNTING DETAIL 15" x 12" SIGN PLACE ON (2) VISIBLE SIDES OF PROPOSED GENERATOR TANK UNISTRUT WALL ATTACHMENT: WALL CONSTRUCTION TYPE FASTENER HOLLOW, AT STUD 3/8" DIA. x 2-1/2" EMBED SAE J429 GR.1 LAG SCREW CONCRETE BLOCK (HOLLOW) 3/8" DIA. HILTI HY-270 (ESR-4143) W/ SCREEN, MINIMUM EMBEDMENT 2-3/8" CONCRETE (SOLID) 3/8" DIA. HILTI HY-200 (ESR-3187), MINIMUM EMBEDMENT 2-3/8" NOTES: 1. USE GALVANIZED OR STAINLESS STEEL HARDWARE FOR WALL MOUNT AND CONNECTION OF CHANNELS 2. GC SHALL USE NON-SHRINKING CAULK TO WEATHER SEAL ALL PENETRATIONS INTO OR THROUGH WALL PLACE ON (2) VISIBLE SIDES OF PROPOSED GENERATOR TANK 2 01COLOR: BLUE COLOR: RED COLOR: YELLOW FOR FUEL & OTHER ENVIRONMENTAL EMERGENCIES CALL EH&S 1-800-566-9347 (1-800-KNOW-EHS) AT&T MOBILITY COMBUSTIBLE NO SMOKING NO OPEN FLAMES FUEL TANK CAPACITY 132 GALS DIESEL FUEL **SEE SHEETS E-4.3, E-4.4 FOR VENT PIPES, FUEL FILL, SPILL & ALARM COMPONENTS CFC CFC CFC CFC CFC CFC CALIFORNIA 18" ( V E R I F Y w / MA N U F . )49.4" (VERIFY w/MANUFACTURER)MOUNTING TAB, TYP. OF (4). INSTALL 38"Ø STAINLESS STEEL THRU-BOLTS w/ NUTS AND LOCK-WASHERS. MAX. THRU-BOLT TORQUE = 30 FT-LBS. NEW AUTOMATIC TRANSFER SWITCH w/ CAM-LOCK MOUNTED TO NEW UNISTRUT RAILS w/ THRU-BOLTS. [CAM-LOCK IS SECURED TO ATS BODY AND NOT ATTACHED TO UNISTRUT.] CAM-LOCK NOT SHOWN FOR CLARITY. 1-5/8" P1000T UNISTRUT MOUNTED TO WALL OR TO NEW H-FRAME POSTS W/ FASTENER PER ATTACHMENT TABLE ABOVE AT EACH END NEW MECHANICAL CONNECTION WITH #2 AWG TO EXISTING GROUND RING, SEE SHEET E-3 INS T A L L T O P OF A T S A T 5'-9 " A B O V E GR A D E M A X . MAX . A T S + C A M - L O C K WEI G H T = 2 1 0 L B S GENERAL STRUCTURAL DETAILS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: S-2 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD UL-2085 DOUBLE WALL FUEL TANK BASE SPECIFICATION MH 18481 UL-2085 UL-2085 HSS2x2x14 TUBE, SECURITY TOPPER BEAM 12"Ø A325 BOLT W/ NUT & LOCKWASHER L5x3x14 LEDGER (2) 12"Ø U-BOLTS FENCE POST A-A TYPICAL POST CONNECTIONXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXTOP RAIL LINE POST CHAIN-LINK FABRIC MESH WEATHERTIGHT POST CAP, TYP. TENSION BAR, USE (1) FOR EACH END OR GATE POST, (2) FOR EACH CORNER POST END, GATE, CORNER OR PULL POST TENSION BAND, (1) PER FOOT OF FENCE HEIGHT DIAGONAL ROD WITH STEEL TURNBUCKLE ON GATE & ALL CORNERS WITH HORIZONTAL BRACE SEE LINE POST SPACING SCHEDULE SEE LINE POST SPACING SCHEDULE 0'-0"TOP OF CONCRETE LINE POST BOTTOM TENSION WIRE CONCRETE BRACE RAIL BRACE RAIL, EA. CORNER, EA. WAY 6' TO 8' CHAIN-LINK FABRIC2" MAXCLEARANCE FROMGRADE, TYP.CHAIN-LINK GATE/FENCE SPECIFICATIONS: (INSTALL FENCING PER ASTM F567 / SWING GATES PER ASTM F900)NOTES: GATE POST 4.500" O.D. SCHEDULE 40 PIPE FOR GATE WIDTHS UP T0 6 FEET, PER ASTM F1083. POST & FENCE PIPE SIZES ARE FENCE INDUSTRY STANDARD. ALL PIPE TO BE HOT-DIP GALV. CROSS BRACE ALL POSTS EXCEPT INTERMEDIATES. LINE POST 6' TALL = 2.375" O.D. SCHEDULE 40 PIPE PER ASTM F1083. 8' TALL = 2.875" O.D. SCHEDULE 40 PIPE PER ASTM F1083. CORNER POST 3.500" O.D. SCHEDULE 40 PIPE PER ASTM F1083. TOP RAIL/BRACE RAIL 1.875" O.D. SCHEDULE 40 PIPE, PER ASTM F1083. GATE FRAME 1.875" O.D. SCHEDULED 40 PIPE, PER ASTM F1083. GATE LATCH 1.375" O.D. PLUNGER ROD W/ MUSHROOM TYPE CATCH AND LOCK. CONTRACTOR TO INSTALL (2) GATE HOLDBACKS TO HOLD GATE OPEN DURING USE. FABRIC 9 GA. CORE WIRE SIZE 2" MESH, CONFORMING TO ASTM A392. - TIE WIRE MINIMUM 11 GA. GALVANIZED STEEL AT POSTS AND RAILS A SINGLE WRAP OF FABRIC TIE AND AT TENSION WIRE BY HOG RINGS SPACED MAX. 24" INTERVALS. - TENSION WIRE 7 GA. GALVANIZED STEEL.- BARBED WIRE DOUBLE STRAND 12-1/2" O.D. TWISTED WIRE TO MATCH WITH FABRIC 14 GA. 4 PT. BARBS SPACED ON APPROXIMATELY 5" CENTERS. LOCAL ORDINANCE OF BARBED WIRE PERMIT REQUIREMENTS SHALL BE COMPLIED WITH IF REQUIRED. CHAIN-LINK FENCE DETAIL #2 SOLID, TINNED BARE COPPER WIRE CADWELD CORNER POSTS TO GROUND RING GROUND RING CHAIN-LINK FENCE SECURITY TOPPER HSS2x2x14 TUBE, SECURITY TOPPER BEAM 12"Ø A325 BOLT W/ NUT & LOCKWASHER L5x3x14 LEDGER (2) 12"Ø U-BOLTS FENCE POST A-A TYPICAL POST CONNECTION FOOTPAD, TYP. ⅊34x7x7 (4) 12"Ø x 334" EMBED HILTI KWIK BOLT TZ2 STAINLESS STEEL EXPANSION ANCHOR (OR APPROVED EQUAL). REFERENCE ICC-ES ESR-4266 REPORT. 3.75" 3/16 POST LINE POST FOOTPAD DETAIL 1" DRY PACK, IF REQ'D 5"3"(MIN.) TO EDGE OF SLAB ⅊34x9x9 (4) 12"Ø x 334" EMBED HILTI KWIK BOLT TZ2 STAINLESS STEEL EXPANSION ANCHOR (OR APPROVED EQUAL). REFERENCE ICC-ES ESR-4266 REPORT. 3.75" 3/16 POST GATE/CORNER POST FOOTPAD DETAIL 1" DRY PACK, IF REQ'D 7"3"(MIN.) TO EDGE OF SLAB SEE LINE POST SPACING SCHEDULE LINE POST SPACING SCHEDULE: DESCRIPTION MAXIMUM SPACING 6' TALL MESH ONLY 4'-0" 8' TALL MESH ONLY 3'-0" GATE FRAME TENSION BAR, USE (1) FOR EACH GATE POST DIAGONAL ROD WITH STEEL TURNBUCKLE ON GATE & ALL CORNERS WITH HORIZONTAL BRACE CHAIN-LINK FABRIC MESH 6' TO 8' CHAIN-LINK FABRIC0'-0"FINISH GRADE GATE LATCH W/ PADLOCK WITH HORIZONTAL BRACE 0'-0"FINISH GRADE CONCRETE #2 SOLID, TINNED BARE FENCE & GATE DETAILS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: S-3 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD CONTRACTOR TO COVER ANY GAP BETWEEN THE 6' FENCE & 9' FENCE WITH FENCE SECTION AS REQUIRED (CHAIN-LINK IS NOT REQUIRED BELOW THE GAP) AA CHAIN-LINK MESH, TYP. LEDGER, TYP. CONNECT TO EACH POST NOTE: CONTRACTOR TO CUT HOLES IN MESH FOR GENERATOR VENT PIPES AS REQUIRED OVERLAP MESH & SECURE 3'-0"MAX.SPAN CHAIN-LINK FABRIC MESH ACROSS HSS BEAMS, ADEQUATELY TENSION FABRIC, AND SECURE TO EACH TOPPER BEAM (7) SECURITY TOPPER BEAMS REQUIRED FOR EXPANSION INSTALL TENSION BAR AND TENSION BANDS AT EACH END SIMILAR TO FENCE CORNER DETAIL CONTRACTOR TO INSTALL STEEL PLATE "GATE STOP" ON INSIDE FACE OF GATE FRAME TO ENSURE GATE IS NOT ALLOWED TO OPEN OUTSIDE OF THE COMPOUND. ⅊12"x6"x12" w/ (2) 12"Ø U-BOLTS TO VERTICAL GATE FRAME MEMBER AS SHOWN 112"3"112"GATE FRAME VERT. FENCE END POST SEE PLANS SHEET 9'CHAIN-LINK FABRICEXISTING CHAIN-LINK FENCE COMPOUND w/ SECURITY TOPPER SEE SITE PLAN; SHEET A-2 SEE SITE PLAN;SHEET A-2NEW CONCRETE COMPOUND EXPANSION AGGREGATE NOTES: 1 THE AGGREGATE MATERIAL TO BE USED WILL BE PRODUCED FROM SOUND, TOUGH, DURABLE ROCK AND SHALL BE UNIFORM IN QUALITY AND GRADATION. THE CRUSHED MATERIAL WILL BE REASONABLY FREE FROM SOFT OR DISINTEGRATED PIECES, ORGANIC MATERIALS, AND OTHER OBJECTIONABLE MATTER. 2 THE AGGREGATE MATERIAL WILL SHOW A LOSS LESS THAN 35% IN THE LOS ANGELES ABRASION TEST. 3 THE PERCENTAGE OF SOFT PARTICLES, AS DETERMINED BY THE CLAY LUMPS AND FRIABLE PARTICLES [AASHTO T 112], SHALL NOT BE MORE THAN 5%. 4 THE AGGREGATE MATERIAL USED WILL NOT HAVE A SAND EQUIVALENT LESS THAN 30 IF 5% OR MORE OF THE MATERIAL PASSES THE NUMBER 200 SIEVE. 5 80% OF THE GRAVEL (BY WEIGHT) OF THE COMBINED COURSE AGGREGATE SHALL HAVE THREE OR MORE ROUGH ANGULAR SURFACES AND PRODUCED BY CRUSHING OF THE ROCK. 6 THE PLASTICITY INDEX OF THE FINISHED AGGREGATE PRODUCT SHALL NOT EXCEED 6. AGGREGATE GRADATION CHART: (% BY WEIGHT PASSING SIEVES) SIEVE SIZE 2"-MINUS 34"-MINUS 212"100 - 2"90-100 - 1"55-83 100 34"-90-100 No. 4 30-60 40-65 No. 8 -30-50 No. 30 10-25 - No. 200 0-8 3-9 COMPACTION NOTE: STRUCTURAL FILL SHALL BE GRANULAR FREE-DRAINING MATERIAL FREE OF DEBRIS, ORGANICS, REFUSE AND OTHERWISE DELETERIOUS MATERIALS. MATERIAL SHALL BE PLACED IN LIFTS NO GREATER THAN 12" IN DEPTH AND COMPACTED TO 95% OF MAXIMUM DENSITY AS DETERMINED PER ASTM D1557. CONCRETE COMPOUND EXPANSION DETAIL SEE CONCRETE COMPOUND EXPANSION DETAIL NOTE: SEE SHEET S-1 FOR FOUNDATION / STRUCTURAL NOTES AND SPECIFICATIONS. S4.2 6" #4 BARS @ 12" O.C. EA. WAY CENTERED IN SLAB DEPTH6" SEE SITE PLAN ACI - APPROVED REBAR CHAIRS 3" CLEAR & GRUB UPPER 6" (MIN.) OF EXISTING GROUND SURFACE & REPLACE W/ 6" (MIN.) OF COMPACTED 2"-MINUS STRUCTURAL FILL, SEE GRADATION CHART 9" 3" CLR.1'-9" EXISTING GRADE 24"15"#4 HOOKS @ 12" O.C. TO TURN-DOWN EDGE AS SHOWN, LAP WITH SLAB REBAR (2) #4 HORIZONTAL REBAR IN TURN-DOWN COMPACT EXISTING SOIL; SEE COMPACTION NOTE PROVIDE EXPANSION JOINT BETWEEN PROPOSED AND EXISTING CONCRETE (IF APPLICABLE) 15" MIN. EMBED EXTEND TURN-DOWN EDGE AND HOOKS AS REQUIRED 6" REVEAL ABOVE GRADE COMPOUND EXPANSION DETAIL PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: S-4 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD SINGLE LINE DIAGRAM ALL ELECTRICAL WORK CONDUCTED ON PANELS TO BE VERIFIED WITH CONSTRUCTION MANAGER AND CONDUCTED BY AN APPROVED ELECTRICAL CONTRACTOR LICENSED IN THE STATE. TYP 1 CONDUIT / WIRE SCHEDULE: NO.FROM TO WIRES GROUND CONDUIT SIZE FUNCTION NORMAL POWER SOURCE AUTOMATIC TRANSFER SWITCH (3) W/C (1) W/C (1) W/C NORMAL POWER FEEDER TO ATS (CUT BACK EXISTING) AUTOMATIC TRANSFER SWITCH LOAD CENTER (3) W/C (1) W/C (1) W/C POWER FEEDER FROM ATS TO PANELS GENERATOR AUTOMATIC TRANSFER SWITCH (3) W/C (1) W/C (1) W/C STANDBY POWER FEEDER TO ATS AUTOMATIC TRANSFER SWITCH GENERATOR (2) W/C (1) W/C (1) W/C START CIRCUIT LOAD CENTER (DISTRIBUTION CENTER) GENERATOR, ATS (2) W/C (2) W/C (2) W/C (1) W/C (1) W/C (1) W/C (1) W/C (1) W/C (1) W/C CKT FOR GEN BLOCK HEATER & BATTERY HEATER, CKT FOR BATTERY CHARGER, CKT FOR ATS CONTROLS (SEE BREAKER NOTE) GENERATOR THROUGH ATS TO ALARM BLOCK 12-PAIR 24 AWG OR 2EA 6-PAIR CAT5 N/A 1" ALARM CABLES (1) 12 PAIR 24 AWG. PROVIDE 24" OF SLACK CABLE. FINAL PUNCH DOWN IS BY AT&T TECH. LABEL ALL WIRES AUTOMATIC TRANSFER SWITCH ALARM BLOCK (2) 12-PAIR 24 AWG OR (2) 6-PAIR CAT5 (1) 1-PAIR 24AWG N/A 1" ALARM CABLES (1) 12 PAIR 24 AWG (RUN THRU INTERIOR OF SHELTER OR GROUND EQUIPMENT & INTO ALARM BOX). PROVIDE SINGLE PAIR FOR COMMERCIAL POWER FAIL ALARM. PROVIDE 24" OF SLACK CABLE. FINAL PUNCH DOWN IS BY AT&T TECH. LABEL ALL WIRES CAM-LOCK BOX AUTOMATIC TRANSFER SWITCH (3) W/C (1) W/C (1) W/C STANDBY POWER FEEDER TO ATS (W/C) = SEE WIRE/CONDUIT SIZING TABLE FOR VALUES 1 2 3 4 5 6 7 8 ALARM WIRE IDENTIFICATION CHART: WIRE ALARM BROWN BROWN / WHITE GENERATOR RUNNING GREEN GREEN / WHITE CRITICAL FAULT BLUE BLUE / WHITE MINOR FAULT ORANGE ORANGE / WHITE LOW FUEL BROWN * BROWN / WHITE *FUEL LEAK *CAT5 CABLE ONLY, FROM 2ND CAT5 CABLE EXISTING DISTRIBUTION PANEL NEW 66 BLOCK FOR GENERATOR ALARM CIRCUITS (ON EXISTING TELCO BOARD) CONTRACTOR SHALL NOT SUBMIT BIDS OR PERFORM CONSTRUCTION WORK ON THIS PROJECT WITHOUT ACCESS TO THE CURRENT COMPLETE SET OF DRAWINGS LISTED IN THE TITLE-SHEET INDEX. EXISTING 200A MAIN SERVICE DISCONNECT M G N NEW ARTICLE 702 30KW GENERATOR 120/240, 1PH, 60Hz G 150A EXISTING 120/240, 1PH, 200A DISTRIBUTION PANEL AT EQUIPMENT EQUIPMENT AREA INTERCEPT EXISTING CONDUIT AND CONDUCTORS PRIOR TO MAIN PANEL AND RE-ROUTE TO NEW ATS NEW CAM-LOCK BOX FOR PORTABLE GENERATOR CONNECTION 20A 20A 20A 7 PANEL w/ ROOM FOR BREAKERS (2) OR (3) NEW 20A WITH ADEQUATE KAIC RATING FOR AFC AT PANEL PANEL NOTES: 1.CONTRACTOR TO LABEL WIRES WITH P-TOUCH OR SIMILAR LABELS ONLY. ABSOLUTELY NO HANDWRITTEN LABELS. 2.CONTRACTOR SHALL PERFORM A POWER STUDY ON EXISTING AC PANEL PRIOR TO INSTALLING, CHANGING, ALTERING, OR REMOVING ANY BREAKER. NO WORK SHALL BE COMPLETED ON AC PANEL WITHOUT PROPER INSPECTOR OR ENGINEER APPROVED DOCUMENTATION CONFIRMING CAPACITY ON SITE. ALL WORK SHALL CONFORM TO NEC VERSION ENFORCED BY A.H.J. AT TIME OF INSTALLATION. 3.CONTRACTOR SHALL VERIFY THAT THE MAXIMUM DEMAND FOR ALL CONNECTED EQUIPMENT AT THIS SITE AS CALCULATED PER NEC DOES NOT EXCEED THE GENERATOR OUTPUT CIRCUIT BREAKER RATING. (SEE NOTE #4 ALSO.) 4.IF MAXIMUM DEMAND OF GENERATOR OUTPUT CIRCUIT BREAKER RATING AS CALCULATED PER NEC IS CONTINGENT ON THE TWO HVAC UNITS NOT OPERATING CONCURRENTLY, THEN CONTRACTOR SHALL VERIFY THAT THE HVAC LEAD/LAG CONTROLLER IS CONFIGURED TO PREVENT CONCURRENT OPERATION. IF NOT, THEN CONTRACTOR SHALL RECONFIGURE IT AS NEEDED TO PREVENT TRIPPING THE CIRCUIT BREAKER. 5.SEE REQUIRED LABELING & SIGNAGE; SHEET S-2. 5 3 6 4 5 5 1 2 8 WIRE/CONDUIT SIZING: FEEDER MAX 1-WAY LENGTH IN FEET WIRE SIZE 150A OCP 120/240V 1P 150A OCP 120/208V 1P 150A OCP 208Y/120V 3P 200A OCP 120/240V 1P 200A OCP 120/208V 1P 200A OCP 208Y/120V 3P GROUND WIRE SIZE CONDUIT SIZE 1/O 192 166 192 ---#4 1-1/2" 2/O 227 196 227 ---#4 2" 3/O 284 246 284 213 185 213 #4 2" 4/O 337 292 337 253 220 254 #4 2" 250 KCMIL 378 328 378 284 246 284 #4 2-1/2" 300 KCMIL 423 367 423 318 275 318 #3 2-1/2" 350 KCMIL 471 408 471 354 307 354 #2 2-1/2" 400 KCMIL 510 442 510 383 332 383 #2 3" 500 KCMIL 581 503 581 436 378 436 #1 3" 600 KCMIL 625 541 625 469 406 469 1/O 3-1/2" 750 KCMIL 694 601 694 521 451 521 2/O 3-1/2" 1000 KCMIL 781 677 781 586 508 586 3/O 4" FEEDER MAXIMUM LENGTH VALUES SHOWN ARE FOR MAX. FEEDER VOLTAGE DROP OF 2.5%. NOTE THAT A 30KW GENERATOR REQUIRES NO MORE THAN 150A OCP. MAX. ONE-WAY LENGTH VS. WIRE SIZE FOR 20A CKT, AND NEC REQ'D INCREASED GROUND WIRE SIZE - BELOW GROUND WIRE SIZE DISTANCE GROUND WIRE SIZE CONDUIT SIZE #12 0 - 51 FT #12 1" #10 52 - 85 FT #10 1" #8 86 - 130 FT #8 1" #6 131 - 203 FT #6 1" FOR LONG RUNS, PER NEC 300.3(B)(1), FOR CONDUCTORS 1/O AND LARGER, CONTRACTOR MAY ELECT TO INSTALL EQUIVALENT SETS OF PARALLEL CONDUCTORS (UPSIZE GROUND WIRE AND CONDUIT ACCORDINGLY). SMALLER CONDUCTORS REQUIRING UPSIZING MUST BE REPLACED w/ ADEQUATELY SIZED LARGER CONDUCTORS. (IF REQ'D) NOTE: ALL CONDUCTORS TO BE COPPER UNLESS NOTED OTHERWISE. ATS POLE NOTE: NEW ATS/CAMLOCK ARE CONFIGURABLE FOR SINGLE OR THREE PHASE OPERATION. IN SINGLE PHASE INSTALLATIONS, 3-POLE ATS TO BE INSTALLED WITH ONE POLE NOT CONNECTED (UNUSED) AND TO BE CONFIGURED FOR DUAL-POLE USE. NEUTRAL SHALL NOT BE SWITCHED. BREAKER QUANTITY NOTE: "ATS CONTROLS" CIRCUIT MAY NOT BE REQUIRED TO POWER ATS. CONTRACTOR TO FIELD-VERIFY PER APPLICATION ON EQUIPMENT. GENERATOR NEUTRAL SHALL NOT BE BONDED TO GROUND AT THE GENERATOR. IT SHALL BE SOLIDLY CONNECTED THROUGH THE ATS, WITH NO SWITCHING DEVICE INSERTED IN THE CONDUCTOR, TO THE UTILITY SERVICE NEUTRAL. (OPEN TRANSITION, FLOATING NEUTRAL AT GENERATOR) THIS GENERATOR IS NOT INTENDED TO BE A SEPARATELY DERIVED SYSTEM. EXISTING METER EXISTING MAIN SERVICE FEED 200A 200A BOND TO EXISTING SITE LIGHTNING PROTECTION GROUNDING SYSTEM USING #2 AWG BARE SOLID TINNED COPPER GROUND PROTECTED IN RIGID OR INTERMEDIATE METAL CONDUIT (RMC/IMC) OR RIGID PVC CONDUIT, TYP. IF METALLIC IS USED, CONDUCTOR MUST BE BONDED TO BOTH ENDS OF CONDUIT. NEW LOCKABLE EMERGENCY SHUTOFF SWITCH NEW 120/240, 1PH, 60 Hz 200A NEMA 3R ATS RATED 25kAic, SEE ATS POLE NOTE. IF UTILITY SPECIFIED AFC IS GREATER THAN 25kAic, THIS DESIGN WILL NEED REVISIONS. CEC CEC CEC CEC CEC ELECTRICAL DETAILS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-1 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD EXISTING 120/240, 1PH, 200A INTEGRATED LOAD CENTER (ILC) WITH AC DISTRIBUTION PANEL (2) OR (3) PROPOSED 20 AMP BREAKERS FOR BLOCK HEATER, BATTERY HEATER, AND BATTERY CHARGER ON NEW AT&T GENERATOR (INSTALL FILLER PLATES ON ANY OPEN SLOTS) G CONDUIT COUPLING SLIP JOINT (IF REQUIRED PER NEC) CONDUIT ELBOW CONDUIT PLUG FOR SPARE CONDUIT PROPOSED CONDUIT U.L. SYSTEM NO. C-AJ-1150 CONDUIT THROUGH BEARING WALL SIMILAR TO U.L. DESIGN NO. U902 F RATING = 3 HR T RATING = O HR 1.FLOOR OR WALL ASSEMBLY : MINIMUM 4-1/2" THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAMETER OF OPENING IS 4". (SEE CONCRETE BLOCKS 9CATZ) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. 2.THROUGH PENETRATIONS : ONE METALLIC PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE ANNULAR SPACE SHALL BE MINIMUM 0". (POINT CONTACT) TO MAXIMUM 1-3/8". THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR CONDUITS MAY BE USED: A. STEEL PIPE-NOMINAL 6" DIAMETER (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE B. IRON PIPE-NOMINAL 6" DIAMETER (OR SMALLER) CAST OR DUCTILE IRON PIPE. C. CONDUIT - NOMINAL 4" DIAMETER (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR NOMINAL 3-1/2" DIAMETER (OR SMALLER) STEEL CONDUIT. 3.PACKING MATERIAL: MINIMUM 6" THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATTING INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. 4.FILL, VOID, OR CAVITY MATERIAL*: SEALANT: MINIMUM 1/4" THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR AND WITH BOTH SURFACES OF WALL. AT THE POINT CONTACT LOCATION BETWEEN PIPE AND CONCRETE, A MINIMUM 1/2" DIAMETER BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE CONCRETE/PIPE INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH SURFACES OF WALL. W-RATING APPLIES ONLY WHEN CP601S OR CP604 SEALANT IS USED. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC. : CP601S, CP604, CP606, OR FS-ONE SEALANT. * BEARING THE UL CLASSIFICATION MARK A A 4 2 3 2 4 4 NOTE: 1.IF EXISTING CONSTRUCTION VARIES FROM THIS DETAIL, AN EQUAL 3-HR U.L. PENETRATION APPROPRIATE FOR THE EXISTING WALL TYPE SHALL BE CONSTRUCTED 2.GC SHALL USE NON-SHRINKING CAULK TO WEATHERSEAL ALL PENETRATIONS INTO OR THRU SHELTER WALL. OUTER WALL PENETRATION DETAIL (IF APPLICABLE) UTILITY TRENCH SECTION (IF APPLICABLE) SLIP JOINT DETAIL (IF APPLICABLE) CONDUIT NOTES: 1.VERIFY WIRE AND CONDUIT QUANTITY & SIZES WITH GENERATOR MAKE & MODEL # PRIOR TO INSTALLATION. VERIFY ELECTRICAL REQUIREMENTS WITH LOCAL UTILITY PROVIDER. 2.ALL CONDUIT ABOVE GRADE OR IN AREAS OF HIGH TRAFFIC SHALL BE SCH 80 PVC. 3.PROVIDE SCH 40 PVC CONDUIT BELOW GRADE EXCEPT AS NOTED BELOW. 4.PROVIDE SCH 80 PVC CONDUIT AND ELBOWS AT STUB UP LOCATIONS (I.E. SERVICE POLE, BTS EQUIPMENT, ETC.) 5.INSTALL UTILITY PULLBOXES PER NEC. BACKFILL MATERIAL COMPACTED TO 95% RELATIVE DENSITY PER STANDARD PROCTOR COMPACTED SAND TO 95% RELATIVE DENSITY PER STANDARD PROCTOR26" MIN30" MAX1'-0"1'-0"1'-6" 8" UNDISTURBED SOIL ELECTRICAL CONDUIT(S) CONDUIT NOTES: 1.VERIFY WIRE AND CONDUIT QUANTITY & SIZES WITH GENERATOR MAKE & MODEL # PRIOR TO INSTALLATION. VERIFY ELECTRICAL REQUIREMENTS WITH LOCAL UTILITY PROVIDER. 2.ALL CONDUIT ABOVE GRADE OR IN AREAS OF HIGH TRAFFIC SHALL BE SCH 80 PVC. 3.PROVIDE SCH 40 PVC CONDUIT BELOW GRADE EXCEPT AS NOTED BELOW. 4.PROVIDE SCH 80 PVC CONDUIT AND ELBOWS AT STUB UP LOCATIONS (I.E. SERVICE POLE, BTS EQUIPMENT, ETC.) 5.INSTALL UTILITY PULLBOXES PER NEC. SECTION A-A CONTRACTOR SHALL NOT SUBMIT BIDS OR PERFORM CONSTRUCTION WORK ON THIS PROJECT WITHOUT ACCESS TO THE CURRENT COMPLETE SET OF DRAWINGS LISTED IN THE TITLE-SHEET INDEX. ELECTRICAL WARNING TAPE CONTRACTOR TO MATCH EXISTING GRADE CONDITIONS AFTER TRENCH PLACEMENT AND COMPACTION (FOR PAVEMENT) CONTRACTOR TO SAW-CUT AND REMOVE EXISTING PAVEMENT. UPON REPLACEMENT, CONTRACTOR TO MATCH EXISTING PAVEMENT THICKNESS, PLACEMENT DETAILS AND DRAINAGE CONDITIONS AFTER TRENCH PLACEMENT AND COMPACTION GALVANIZED CHANNEL WITH PIPE CLAMP PER MANUFACTURER CONDUIT COOPER B-LINE DURA-BLOK SLEEPER (OR SIMILAR) AT 5'-0" O.C. MAXROOF DECK ROOF CONDUIT MOUNTING DETAIL (IF APPLICABLE) 3 4 2 3 1 4 2 1 2 3 4 CONDUIT (TYP) P1119 OR P2558 CLAMP EXISTING WALL/CEILING CONDUIT WALL MOUNT DETAIL (IF APPLICABLE) "UNISTRUT" P1000T. REQUIRED LENGTH BASED ON QUANTITY OF CONDUIT TO BE MOUNTED. INSTALL AT 5'-0" O.C. MAX. W/ FASTENER PER ATTACHMENT TABLE AT EACH END. 1 UNISTRUT WALL ATTACHMENT: WALL CONSTRUCTION TYPE FASTENER HOLLOW, AT STUD 3/8" DIA. x 2-1/2" EMBED LAG SCREW CONCRETE BLOCK (HOLLOW) 3/8" DIA. HILTI HY-270 (ESR-4143) WITH SCREEN, MINIMUM EMBEDMENT 2-3/8" CONCRETE (SOLID) 3/8" DIA. HILTI HY-200 (ESR-3963), MINIMUM EMBEDMENT 2-3/8" NOTES: 1. USE GALVANIZED OR STAINLESS STEEL HARDWARE FOR WALL MOUNT AND CONNECTION OF CHANNELS 2. GC SHALL USE NON-SHRINKING CAULK TO WEATHER SEAL ALL PENETRATIONS INTO OR THROUGH WALL CEC CEC CEC ELECTRICAL DETAILS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-2 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD EXISTING EQUIPMENT SHELTER OR PAD PROPOSED AUTOMATIC TRANSFER SWITCH & CAM-LOCK BOX PROPOSED GENERATOR TYP. OF (2) 250 MCM BCW GROUND WIRES TO TO EXISTING CONCRETE SLAB GROUND RING. GROUND GENERATOR PER MANUFACTURER'S RECOMMENDATIONS. FOR SAFETY REASONS, ALL CONCRETE AND NEW GROUNDING SHALL BE PLACED/INSTALLED PRIOR TO SECURING GROUNDING CONNECTION TO EXISTING RING. COORDINATE WITH PG&E PRIOR TO MAKING FINAL CONNECTION TO GROUND GRID. EXISTING GROUND WIRE, TYP. EXISTING BURIED EQUIPMENT GROUND RING (FIELD LOCATE) #2 AWG GROUNDED TO FENCE IF LESS THAN 6FT ELECTRICAL SYMBOLS LEGEND ALL CONNECTIONS TO EXISTING GROUND RING MUST BE APPROVED DMC GROUNDLOK COMPRESSION CONNECTORS. MECHANICAL TYPE CONNECTION, AS APPROVED BY PG&E NEW GROUNDING EXISTING GROUNDING GROUNDING NOTES: 1.IF MORE THAN 20' FROM EXISTING GROUND RING, INSTALL GROUND ROD (5/8" x 10' SS). ROD SPACING: 10' MIN. TOP OF ROD AND GROUND WIRE TO BE BELOW FROST LINE. 2.CONTRACTOR SHALL COORDINATE INCOMING SERVICES WITH LOCAL UTILITIES PRIOR TO TRENCHING. 3.ALL CONDUCTORS SHALL BE COPPER, 75 DEGREES C RATED, AND CONDUCTOR INSULATION BE THWN OR THHN. 4.ALL TERMINATION SHALL BE LISTED AND IDENTIFIED FOR USE WITH 75°C RATED CONDUCTORS OPERATING AT 75°C. 5.GROUND FAULT PROTECTION REQUIRED FOR UTILITY RECEPTACLES. 6.GENERATOR NEUTRAL SHALL NOT BE GROUNDED AT THE GENERATOR. REFER TO SINGLE LINE DETAIL, SHEET E-1. 7.EQUIPMENT LOCATED OUTSIDE OR EXPOSED TO MOISTURE SHALL BE NEMA 3R RATED. 8.CONTRACTOR SHALL USE SCHEDULE 80 PVC CONDUIT THROUGH CONCRETE AND ABOVE GROUND, UNLESS OTHERWISE NOTED. 9.ALL NEWLY INSTALLED EQUIPMENT SHALL BE RATED "AT 10K AIC" MINIMUM. HIGHER RATINGS SHALL BE REQUIRED WHERE AVAILABLE FAULT CURRENT EXCEEDS THIS VALUE. EXACT FAULT CURRENT AVAILABLE SHALL BE COORDINATED WITH LOCAL UTILITY BASED ON EXACT CONDITIONS (XFMR SIZE, PERCENT IMPEDANCE, LENGTH OF CONDUCTORS, ETC). GROUND ROD DETAILS TYPICAL GROUNDING DIAGRAM GROUND ROD NOTES: 1.GROUND RODS MAY BE: - COPPER CLAD STEEL - SOLID COPPER 2.GROUND RODS SHALL HAVE A MAXIMUM SPACING TWICE THE LENGTH OF ROD 3.SEE RESISTIVITY REPORT FOR VERIFICATION AS AVAILABLE 4.A LARGER CONDUCTOR SHALL BE REQUIRED IN AREAS HIGHLY PRONE TO LIGHTNING AND/OR AREAS WITH HIGHLY ACIDIC SOIL 5.GROUND RODS INSTALLED WITHIN CLOSE PROXIMITY TO TOWER OR WHEN SOIL IS AT OR BELOW 2,000 OHM-CM, SHALL BE GALVANIZED TO PREVENT GALVANIC CORROSION OF TOWER, (SEE ANSI/TIA-EIA-222) 6.PROVIDE (1) GROUND LEAD TO EACH SIDE OF THE GENERATOR MECHANICAL CONNECTION GRADE #2 AWG BCW GROUND RING GROUND ROD 58"Ø x 10'-0" LONG MAX. CONTRACTOR SHALL NOT SUBMIT BIDS OR PERFORM CONSTRUCTION WORK ON THIS PROJECT WITHOUT ACCESS TO THE CURRENT COMPLETE SET OF DRAWINGS LISTED IN THE TITLE-SHEET INDEX. 18" OR 6" BELOW FROST LINE, WHICHEVER IS DEEPER, PLACED AS APPROVED BY PG&E FENCE GROUNDING: 1.SEE FENCE & GATE DETAILS SHEET FOR ADDITIONAL GROUNDING (IF APPLICABLE) PG&EPGE PG&E NOTES: 1.IF THIS GROUNDING DIAGRAM CONFLICTS WITH PG&E REQUIREMENTS, PG&E GROUNDING PLAN WILL SUPERSEDE. 2.CONTRACTOR TO EXERCISE CAUTION AROUND EXISTING GROUND SYSTEM. ANY DAMAGE DONE TO PG&E CONDUCTORS/GROUND COMPONENTS MUST BE REPAIRED/REPLACED TO THE SATISFACTION OF PG&E AT THE EXPENSE OF THE CONTRACTOR. GROUND ROD CONNECT REBAR TO GROUND GRID WITH (2) 250 MCM BCW USING APPROVED DMC CONNECTORS (IF APPLICABLE)RB RB RB CONCRETE PAD 2'-0" TYP. PG&E GROUNDING DESIGN TO SUPERSEDE ALL GROUNDING DESIGNS. PG&E GRID DESIGN TO FOLLOW. ELECTRICAL DETAILS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-3.0 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD E-3 PG&E GROUND GRID SEE SHEETS E-3.1, 3.2, ETC. ON SHEETS E-3.1, 3.2, ETC. ANY ADDITIONAL GROUNDING AS SPECIFIED BY PG&E; SEE SHEETS E-3.1, 3.2, ETC. PG&E GROUNDING SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-3.1 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLYDESIGN PENDING PG&E GROUNDING SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-3.2 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLYDESIGN PENDING PG&E GROUNDING SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-3.3 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLYDESIGN PENDING 3G 2.2 GENERAC 30KW GENERATOR SPECIFICATIONS* All measurements are approximate and for estimation purposes only. Specification characteristics may change without notice. Please contact a Generac Power Systems Industrial Dealer for detailed installation drawings. NOTE: IT IS RECOMMENDED THAT BATTERY BE WITHIN LEAK CONTAINMENT BOX OR TRAY SD030 |2.2L |30 kW INDUSTRIAL DIESEL GENERATOR SET EPA Certified Stationary Emergency SPEC SHEET1 of 6 Powering AheadCodes and Standards Not all codes and standards apply to all configurations. Contact factory for details. UL2200, UL508, UL489, UL142 CSA C22.2 BS5514 and DIN 6271 SAE J1349 NFPA 37, 70, 99, 110 NEC700, 701, 702, 708 ISO 3046, 7637, 8528, 9001 NEMA ICS10, MG1, 250, ICS6, AB1 ANSI C62.41 ® Standby Power Rating 30 kW, 38 kVA, 60 Hz Prime Power Rating* 27 kW, 34 kVA, 60 Hz *EPA Certified Prime ratings are not available in the US or its Territories For over 50 years, Generac has provided innovative design and superior manufacturing. Generac ensures superior quality by designing and manufacturing most of its generator components, including alternators, enclosures and base tanks, control systems and communications software. Generac gensets utilize a wide variety of options, configurations and arrangements, allowing us to meet the standby power needs of practically every application. Generac searched globally to ensure the most reliable engines power our generators. We choose only engines that have already been proven in heavy-duty industrial applications under adverse conditions. Generac is committed to ensuring our customers' service support continues after their generator purchase. CONTROL SYSTEM Digital H Control Panel- Dual 4x20 Display Program Functions .Programmable Crank Limiter .7-Day Programmable Exerciser .Special Applications Programmable Logic Controller .RS-232/485 Communications .All Phase Sensing Digital Voltage Regulator .2-Wire Start Capability .Date/Time Fault History (Event Log) .Isochronous Governor Control .Waterproof/Sealed Connectors .Audible Alarms and Shutdowns .Not in Auto (Flashing Light) .Auto/Off/Manual Switch .E-Stop (Red Mushroom-Type) .NFPA110 Level I and II (Programmable) .Customizable Alarms, Warnings, and Events .Modbus® Protocol .Predictive Maintenance Algorithm .Sealed Boards .Password Parameter Adjustment Protection .Single Point Ground .16 Channel Remote Trending .0.2 msec High Speed Remote Trending .Alarm Information Automatically Annunciated on the Display Full System Status Display .Power Output (kW) .Power Factor .kW Hours, Total, and Last Run .Real/Reactive/Apparent Power .All Phase AC Voltage .All Phase Currents .Oil Pressure .Coolant Temperature .Coolant Level .Engine Speed .Battery Voltage .Frequency Alarms and Warnings .Oil Pressure .Coolant Temperature .Coolant Level .Engine Overspeed .Battery Voltage .Alarms and Warnings Time and Date Stamped .Snap Shots of Key Operation Parameters During Alarms and Warnings .Alarms and Warnings Spelled Out (No Alarm Codes) ENGINE SYSTEM .Oil Drain Extension .Air Cleaner .Fan Guard .Stainless Steel Flexible Exhaust Connection .Factory Filled Oil and Coolant .Radiator Duct Adapter (Open Set Only) .Critical Silencer (Enclosed Unit Only) .Engine Coolant Heater Fuel System .Fuel Lockoff Solenoid .Primary Fuel Filter Cooling System .Closed Coolant Recovery System.UV/Ozone Resistant Hoses.Factory-Installed Radiator .Radiator Drain Extension.50/50 Ethylene Glycol Antifreeze Electrical System .Battery Charging Alternator.Battery Cables.Battery Tray.Rubber-Booted Engine Electrical Connections.Solenoid Activated Starter Motor ALTERNATOR SYSTEM .UL2200 GENprotect .Class H Insulation Material .2/3 Pitch .Skewed Stator .Brushless Excitation .Sealed Bearing .Rotor Dynamically Spin Balanced .Amortisseur Winding (3-Phase Only) .Full Load Capacity Alternator .Protective Thermal Switch GENERATOR SET .Internal Genset Vibration Isolation .Separation of Circuits - High/Low Voltage .Separation of Circuits - Multiple Breakers .Wrapped Exhaust Piping .Standard Factory Testing .2 Year Limited Warranty (Standby Rated Units) .1 Year Limited Warranty (Prime Rated Units).Silencer Mounted in the Discharge Hood (Enclosed Unit Only) ENCLOSURE (If Selected) .Rust-Proof Fasteners with Nylon Washers to Protect Finish.High Performance Sound-Absorbing Material (Sound Attenuation Enclosures).Gasketed Doors .Stamped Air-Intake Louvers .Upward Facing Discharge Hoods (Radiator and Exhaust).Stainless Steel Lift Off Door Hinges .Stainless Steel Lockable Handles .RhinoCoat - Textured Polyester Powder Coat Paint FUEL TANKS (If Selected) .UL 142/ULC S601 .Double Wall .Normal and Emergency Vents .Sloped Top.Sloped Bottom.Factory Pressure Tested.Rupture Basin Alarm.Fuel Level.Check Valve In Supply and Return Lines.RhinoCoat- Textured Polyester Powder Coat Paint .Stainless Steel Hardware STANDARD FEATURES SPEC SHEET2 of 6 EMERGENCYSTOP COMMON ALARM AUTO OFF MANL LEVEL 2 ACOUSTIC ENCLOSURE Run Time - Hours Usable Capacity - Gal (L) L x W x H - in (mm) Weight - lbs (kg) Enclosure Only Steel Aluminum No Tank -94.8 (2,407) x 38.0 (965) x 61.1 (1,551) 510 (232) 341 (155) 19 54 (204)94.8 (2,407) x 38.0 (965) x 74.1 (1,881) 47 132 (501)94.8 (2,407) x 38.0 (965) x 86.1 (2,186) 75 211 (799)94.8 (2,407) x 38.0 (965) x 98.1 (2,491) 107 300 (1,136)94.8 (2,407) x 38.0 (965) x 98.1 (2,491) Rust-Proof Fasteners with Nylon Washers to GENERAC INDUSTRIALPOWER SD030 |2.2L |30 kW INDUSTRIAL DIESEL GENERATOR SET EPA Certified Stationary Emergency GENERAC INDUSTRIALPOWER GENERATOR SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-4.0 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLY UL-2085 . , UL-2085 PGE GENERAC UL-2085 TANK SPECIFICATIONS PG&E GENERATOR REQUIREMENTS • GENERATOR FUEL STORAGE WILL REQUIRE A PRIMARY ENCLOSURE RATED UL2085 (CONCRETE ENCASED FUEL TANK) • GENERATOR MUST HAVE A SECONDARY ENCLOSURE RATED UL2200 • GENERATOR MUST BE EQUIPPED WITH A HEAT SENSOR AND LEAK DETECTION DEVICES WHICH WILL DISABLE THE GENERATOR IN CASE OF FUEL LEAKAGE, FIRE, OR OTHER EXTERNAL CIRCUMSTANCES • GENERATOR MUST HAVE A FIRE DETECTION SHUT-OFF VALVE GENERATOR SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-4.1 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLY PGE SHEET NOT USED GENERATOR SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-4.2 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLY GENERAC GENERATOR SPECIFICATIONS OVERFILL PREVENTION VALVE INSIDE TANK (FACTORY-INSTALLED) GENERAC 0J7671 TUBE CUT LENGTH UPPER TUBE CUT TO LENGTH 157±2 (ASSEMBLED LENGTH) FLOAT ASSEMBLY FUEL SPILL/FILL DRAIN OUTSIDE TANK (FACTORY-INSTALLED) GENERAC 0J7606A REMOTE 90% FUEL ALARM (FACTORY-INSTALLED) GENERAC OF2908$ LED YELLOW w/ HOLDER DECAL ALARM HORN RESET DECAL ALARM HORN TEST SWITCH, TOGGLE DPOT MOMENTARY ENCL NEMA 3R 6"H 4"W 4"D PIEZO BUZZER PANEL MNT DECAL 90% FUEL LEVEL ALARM 11 4 5 3 9 8 3 2 7 12 6 1 11 4 4 10 10 9 10 4 REVISION : CN-0019649-W DATE ; 9/4/18 10 EXPLODED VIEW : EV VENT EXT AGRP 2"3 ATT DRAWING NO. : 0K9817A (FIRST 6 DIGITS ONLY) IN THE SYSTEM FOR CORRECT MATERIAL AND COLOR. (FOR REFERENCE SEE GUIDELINE 0H7169). * CUSTOMER: WHEN ORDERING REPLACEMENT PARTS, ENTER BASE NUMBER * MANUFACTURING: FOR CORRECT MATERIAL AND COLOR REFER TO AS400 BOM. (1) SHEET METAL PARTS LISTED IN THE BOM TABLE ARE REPRESENTING CENERIC PARTS (NO COLOR). NOTES (UNLESS OTHERWISE SPECIFIED) NUT HEX FL WHIZ 3/8-162G06410112 VENT CAP EMERG 3"NPT2072989J11 PIPE NIPPLE 3"X72" SCH40 PNTBK40H145410 BOLT U 3/8-16 X 3.50" W/SADDLE20E42649 COUPLING FULL 2-11.5 BLACK1068640B8 NUT HEX M6-1.0 G8 CLEAR ZINC2G0498137 SCREW HWHT M6-1 X 30 W/MKS20C2454B6 VENT OEM 2"1G0211785 COUPLING PIPE 3 ZINC4100000166764 PIPE 2"VENT EXTENSION 72"LG20G30453 KIT, SADDLE AND BOLT 2 1/2"10C79472 BRACKET VENT EXT AGRP 2"3 ATT10G3036YST0R(1)1 DESCRIPTIONQTY.PART#ITEM GROUP HDRAWING #:0K9817A EXPLODED VIEW: EV VENT EXT AGRP 2"3 ATT EMERGENCY VENT PIPE ASSEMBLY GENERATOR SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-4.3 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLY CONTACT 98.6 REF BUNA N COMPRESSION GASKET NYLON NUT 5/8-11 THD 15/16 FLATS #22AWG LEAD WIRES 610MM EXTENSION INSTALLATION NOTE: HAND TIGHTEN + ONE QUARTER TURN. LEAK DETECTION MUST BE INSTALLED IN THE NORMALLY OPEN (N.O.) POSITION AS SHOWN FOR IT TO FUNCTION CORRECTLY IN GENERAC'S UL TANK SECONDARY CONTAINMENT LEAK DETECTION APPLICATION. OVER TIGHTENING WILL RESULT IN DAMAGE TO THE LEAK DETECTOR AND IMPROPER OPERATION. SPEC: MATERIAL: NYLON VENDOR P/N AND VENDOR: 165900, GEMS SENSORS MOUNTING ATTITUDE: HORIZONTAL RECOMMENDED HOLE SIZE: Ø 0.875", 1/32"-5/32" THICK PANEL. OPERATING TEMPERATURE: -40°F TO 250°F MAX. OPERATION PRESSURE: 100 PSIG AT 70°F THIS SWITCH IS U.L. RECOGNIZED - FILE #E45168, CSA LISTED - 30200 CONTACT RATING: 0.17 AMP, 120 V, 60 Hz, RESISTIVE 0.08 AMP, 240 V, 60 Hz, RESISTIVE 20 VA PILOT DUTY DC ELEC. RATING: 0.3 AMP MAX @30 VDC GENERAC 096500B FUEL LEAK DETECTOR ALARM (FACTORY-INSTALLED) GENERAC GENERATOR SPECIFICATIONS GENERAC EMERGENCY VENT CAPS GENERATOR SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-4.4 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLY G GENERAC ATS SPECIFICATIONS STEEL CONSTRUCTION =NEMA 3R ENCLOSURE WITH HINGED "PADLOCKING" DOORS = STAINLESS STEEL HARDWARE = CAMLOCK "QUICK CONNECT" CAPABILITY =OPERATIONAL STATUS VIEW VIA 6 INCH TOUCH SCREEN = TEST FUNCTION - FAST TEST & NORMAL TEST = UL1008 LISTED - FOR EMERGENCY SYSTEMS = EXTENDED WARRANTY = THREE-PHASE VOLTAGE CONFIGURATIONS Features Optional Features TTS Series Switches TAS200 200 Amps 600 VAC 200A Automatic Transfer Switch = The Generac TAS200 Automatic Transfer Switch Flexibility for multiple application installations Multiple generator support with 3 source panel improved user interface Camlock functionality for mobile generator sources Generac products are designed to the following standards: UL1008, UL508, UL50, CSA C22.2 No. 178 NEC 700, 701 and 702 NEMA 250 Codes and Standards Cabinet Specifications Dimensions 24"W x 12"D x 48"H Weight 210 lbs. Construction Single Chamber with Main Door Steel UL Type / NEMA 3R Rated Powder Coat Finish for Corrosion Resistance C-UL-US Listed - Automatic Transfer Switch Stainless Steel Hardware 3-Point Latching System with Pad-Lockable Handles Mounting Options Wall H-frame Installed Pre-wired alarm terminal strip Electrical Specifications Voltage/Phase/Amps 120/240 Single-Phase, 200A 120/208 3-Phase, 200A 120/240 3-Phase, 200A Breaker Eaton 200 amp Utility Breaker Eaton 200 amp Generator Breaker Maximum RMS Symmetrical Fault Current - Amps 25k AIC Rated Protective Device Continuous Rating (Max) Amp 200 Input to Generator 350MCM - #6 AWG Output to Site 350MCM - #6 AWG Generator Annunciator Connector Deutsch DTM04-12PA-L012 Alarm Terminal Board Generator Run Alarm Generator Fail - Shutdown Alarm Generator Fail - Non Shutdown Alarm Low Fuel Alarm Generator Theft Alarm AC Utility Fail Alarm Application and Engineering Data ® Designed with a 6 inch touch screen controller for GENERAC INDUSTRIAL POWER ATS SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-5.0 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLY G CAM-LOCK BOX SPECIFICATIONS Camlock Component Camlock Component Shipped loose for multiple installation options Dimensions 9" W x 9.4" D x 24.25" H 200A Camlock Generator Connection Single-Phase: Black L1, Red L2, White-Neutral, Green-Ground 3-Phase: Black L1, Red L2, Blue L3, White-Neutral, Green-Ground Uses 4 CH E1016 Male Connectors Mating Connector - CH E1016 Female TTS Control Systems INDICATORS AND BUTTONS System Ready indicator Standby Operating indicator Utility Available indicator GEN/UTIL Switch Position indicator TVSS status Normal Test button Fast Test button Return to Normal button Reset button Exercising indicator DETAILS SCREEN System Settings: . System Voltage/Phases: - 120/240V single phase (standard) - 120/208V three phase (optional) - 120/240V three phase (optional) . Utility Fail Monitor: - Under Voltage: 75-95% of nominal voltage - Over Voltage: 105%-125% of nominal voltage - Pickup (hysteresis): fixed at 5 volts - Delay time: 0-60s . Utility Interrupt Delay: 0-60s . Return to Utility Timer: 1-30 minutes . Transfer: - In-phase, or - Time-Delay-Neutral at 0.0-10.0s in 1 second increments Engine Settings: . Engine Warm-up timer: 0-20 minutes . Generator Load Accept: - Time-Delay-Neutral at 0.0-10.0s in 1 sec increments - Voltage: 85-95% of nominal - Frequency: 85-95% of nominal . Engine Minimum Run Timer: 5-30 minutes . Engine Cooldown Timer: 0-20 minutes Exercise Settings: . Time of day . Day of week . Exercise: - Exercise with/without load - Exercise once every 1, 2, or 4 weeks. - Exercise time-of-day - Exercise day of week - Exercise duration: 15-30 minutes Screen Settings: . Brightness & Contrast button . Screen Calibration button . Startup/Clean screen Diagnostics: . Digital I/O bits status . Voltage A/D readings Mimic Diagram: . System Ready . Transfer switch position . Utility available . Standby available . Maintenance/Auto switch position . Generator source TS position . TVSS status GENERAC INDUSTRIALPOWER CAM-LOCK BOX SPECIFICATIONS PO BOX 2621, BOISE, ID 83701 530.539.4787 CONTACT@GEOSTRUCTURAL.COM WWW.GEOSTRUCTURAL.COM 0 07/05/23 ISSUED FOR CONSTRUCTION BM SHEET TITLE: SHEET NUMBER: E-5.1 REV DATE DESCRIPTION INT REVISIONS SITE INFORMATION: 200 FEET NORTH OF ORO QUINCY HIGHWAY OROVILLE, CA 95966 GENERATOR INSTALLATION PROJECT OLIVE HIGHWAY 10132952 CHECKED BY:JAD THE INFORMATION CONTAINED IN THIS SET OF DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO THE CLIENT NAMES IS STRICTLY PROHIBITED. at t & GENERAL DYNAMICS Information Technology 09/30/25 JURISDICTION USE: DATE SIGNED: 10/30/23 1 10/30/23 ISSUED FOR CONSTRUCTION JAD FOR INFORMATION ONLY