HomeMy WebLinkAboutFAI15-0050 041-130-044 Butte College #9 Math Building FM200 6.28.24 Report of Inspection/Test
Annual Special Hazard FM200 System YOL,AGAPEcIALISTs
Date: 6/28/24
Property Owner/Agent
Butte college Butte college C10/16 License#880862 530-624-4514
Math Building
Conducted by: Don Cantrell
Inspection Ref: 1-161
Signatures
Inspector-Printed Don Inspector-Signature Date I state that the information on this form is correct at the
/� time and place of w eftinspection,and that all equipment
on
Cantell ��(''j]//I� 6/28/24 tested at this time was left in operational condition upon
completion of this inspection except as noted.
Owner- Printed Owner-Signature Date Except as noted,the building is occupied with the same
occupancy classification and hazard of contents as last
inspection. Also,the system has remained in service
without modification and been free of actuation of
devices or alarms.
Notifications
To Be Notified I Testing I Time I Phone I Contact
NA ,Start I
End 1 I I
/►�
System and Panel Information
TypeVSH 1230 1315 LBS Amount of Agent I Hazard Computer room
Panel Manufacturer IModel I Serial No. ILocation
Firelite MRP-2002 00014209 5221 Server room
Over current Protection Type Over current Size(Amps) Primary Supply Disconnect Location/Panel#/Breaker#
Breaker I 20 !Same room next to simplex FACP
Cylinder(s)
Cylinder Fill I Inspection-Service
Equip ID Description! Size Manufacturer Weightal > d `o L 0.
Location Model „ o. 3 o g - Y a 3 r, 43 0
U C d .v -- 2 'v 00 3
o R 0, 3 5 u- v` c l°_ C7 a U _
I.- ~ < is 0 I
U m t— N
Server room Viking 1, 22 258lH36OI00okIokloklokIokIokIokINa
Ok-Passes Inspection S-Serviced on site X-Requires Service NA-Not Applicable
Page 1 of 3
Voltage Specialists, 370 Apple Lane,Paradise 96969
Report of Inspection/Test
Annual Special Hazard FM200 System VOLTAG PECIALISTS
Date: 6/28/24
Property: Butte college c10/16 License#880862 530-624-4514
Owner: Butte college Inspection Ref: 1-161
System Function Summary & Test
Function Description Yes No I
Alarm Panel Supervisory Functions
Panel AC Power Loss I Loss of AC power to the alarm panel is detected by the alarm system. I O 0
Panel Sec Power Loss I Loss of Secondary power to the alarm panel is detected by the alarm O ❑
system.
Open Alarm Circuits I Electrical opens in initiating and indicating circuits are detected. I ❑✓ ❑
Short Alarm Circuits I Electrical shorts in initiating and indicating circuits are detected. I I✓I ❑
Panel to Panel Circuits Integrity of single or multiple circuits providing interface between two or I a ❑
more control panels verified.
Ground Faults Detected I Ground faults in alarm and power circuits are detected •
I ✓❑ ❑
Alarm Functions - Chemical Suppression
1st Alarm A single initiating zone shows alarm. ❑✓ ❑
2nd Alarm A 2nd initiating zone shows alarm. n n
Time Delay Delay between 1st alarm and agent discharge. ❑
I Discharge Alarm Audible alarm upon agent discharge. ❑
Agent discharge Actual discharge of chemical fire suppression agent. �✓ ❑
Abort Switch Switch prevents discharge of chemical fire suppression agent. n n
Panel Inspection
Yes ❑✓ No ❑ System was in operation upon arrival?
Yes ❑✓ No ❑ Panel and surrounding equipment, conduit and wiring well secured and in good condition
Yes ElNo ❑ Are all lamps and displays operating correctly?
Yes ❑✓ No ❑ Primary power supply operates properly under full load ?
Yes ❑✓ No ❑ Are drawings and wiring diagrams available at the panel?
Yes ❑✓ No ❑ Are operating instructions posted or available at the panel?
Yes n No ❑ Are zones labeled and identified?
Chemical Suppression Inspection
Yes ElNo El Agent control heads or nozzles are in good condition and properly mounted ?
Yes ❑✓ No ❑ All ceiling and floor panels are in place?
Yes ❑✓ No ❑ Warning signs are proper and visible ?
Central Station Test
Yes ❑ No ✓❑ Type Transmission
Yes ❑ No El Alarm, Trouble and Supervisory indication tested and verified with the central station?
Yes ❑ No ❑ Operator spoke to
Page 2 of 3
Voltage Specialists, 370 Apple Lane,Paradise 96969
Report of Inspection/Test
Annual Special Hazard FM200 System VOLTAG PECIALISTS
Date:6/28/24 c10/16 License#880862 530-624-4514
Property: Butte college
Owner: Butte college Inspection Ref: 1-161
Alarm Device List
Zone Physical Functional
Device Type Address Location Description Manufacture Model Condition Test
Photo smoke detector 1-1 Ceiling I Fike Good Passed
Photo smoke detector 1-2 Ceiling I Fike Good Passed
Photo smoke detector 2-1 Ceiling I Fike Good Passed
Photo smoke detector 2-2 Ceiling IFike Good Passed
Horn strobe N1-1 Inside by door !Wheelock Good Passes
Strobe N1-2 Outside by door Wheelcok Good Passed
Manual 3-1 By door exit Fike Good Passed
Abort 4 By door exit Fike Good Passed
8ah batteries Panel 02/02/2021 Good Passed
Tank measure at 19.25
Tank supervisory 6-1 Tank Control head Viking Good Passed
Alarm Device Summary Number 1 0 IS (teems Serviced 11 C m
of Items IX 'Items Requiring Service I I 1