HomeMy WebLinkAboutFAI21-0014 078-240-023 OUHSD Las Plumas 1700 WING FA 3.31.23 ALARM AND DETECTION REPORT Page 1 of 5 VOLTAGE' SPEcIAusTs 530-624-4514 C101C16 License#880862 www.VoltageSpecialists.com Inspection # 1-008 ALARM & DETECTION EQUIPMENT TEST REPORT Type of Inspection: ANNUAL Date: 3/31/23 Site: LAS PLUMAS HIGH - 1700 WING Customer: OROVILLE UNION HIGH SCHOOL DISTRICT Street: 2380 LAS PLUMAS Contact: Jim LaGrone City/State: OROVILLE, CA Phone#: 530-682-0444 Fax#: 1. Before Test Notify Proper Authorities: Name Phone # A. Owner or Owner's Rep Jim LaGrone 530-682-0444 B. Fire Department OROVILLE FIRE DEPARTMENT 530-538-6460 C. Central Station D. Central Station Acct# 2. Control Panel Status Yes No Note # A. Is the system monitored by Central Station? I X On Test Time: Return to Service Time: B. Is the Power Light on? X C. Does the Panel indicate Normal conditions? X D. Are all indicating Lamp Bulbs in Operator order? X E. Does the Trouble Light operate? X F. Does the Silence Switch Operate? X G. Battery A.H.8 Date Batteries Installed: 2/24/17 H. Does the Panel have Non-Operational Zones? X I. Does the Panel have Battery Backup? X J. Do the batteries indicate they are Properly Charged? X Condition of Batteries: Note#1 Battery Voltage with AC Power: Battery Voltage without AC Power: K. List any trouble conditions on panel before test: Note# Note# Comments: Note# Note# 3. FACP Manufacturer: SILENT KNIGHT Model# 5207 System Type: HARDWIRE Location of Annunciators: Location of Primary Power Source:Back of Portable Panel# 1204 Breaker 6 Comments: Note# Note# FCPS: Manufacturer: Model# Panel/Breaker# Location: Battery Voltage with A/C Power: w/o A/C Power Date: FCPS: Manufacturer: Model# Panel/Breaker# Location: Battery Voltage with A/C Power: w/o A/C Power Date: FCPS: Manufacturer: Model# Panel/Breaker# Location: Battery Voltage with A/C Power: w/o A/C Power Date: Owner/Rep: Phone#: Date: Inspector: Wyatt C. Phone#: 530 362 2609 Date:3/31/23 Owners Rep Sign: Date:3/31/23 Inspector Sign: ALARM AND DETECTION REPORT Page 2 of 5 Property Site: LAS PLUMAS HIGH - 1700 WING Operational #Tested This Equipment Total# Report Yes N/A Note# 4. Remote Annunciators 5. Zones 5 5 X 6. Manual Stations (Pull) Hardwire 1 1 X Addressable 7. Detectors Photoelectric 8 8 X Ionization Heats/Fixed or R of R 20 20 X Flame Duct(See#15) 8. Horn/Strobe 4 4 X Strobe Only 4 4 X Bell Speakers Horn 2 2 X 9. 10. Automatic Door Release X 11. Water Flow switches X Did W/F Ring Outside Bell? X Did W/F Activate Alarm Panel? X 12. Tamper Switches X 13. PIV X OS &Y X 14. 15. Did test of Duct Detectors shut down air handling units? X 16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X 17. Is system reset for normal conditions? 18. Is system restored to operational service? 19. Have Proper Authorities (see#1)been notified system is back in service? List Proper Authorities:Oroville Fire 20. Indicate %of equipment tested this report 25% 50% 75% VJI00% 21. Indicate %of equipment tested YTD 25% 50% 75% 100% Comments for any"no"answers or explanations (Note#): 3/31/23 Owners Rep Sign: Date: Inspector Sign: ALARM AND DETECTION REPORT Page 3 of 5 Property Site: LAS PLUMAS HIGH - 1700 WING DEVICE zone or SLC DEVICE # TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL HT ROOM 1704 AC X 3-3 HT ROOM 1704 AC X 3-4 HT ROOM 1704 AC X 3-5 HT ROOM 1704 AC X 3-6 HT ROOM 1703 AC X 4-4 HT ROOM 1703 AC X 4-5 HT ROOM 1703 AC X 4-6 HT ROOM 1703 AC X 4-7 HT ROOM 1702 AC X 5-4 HT ROOM 1702 AC X 5-5 HT ROOM 1702 AC X 5-6 HT ROOM 1702 AC X 5-7 HT ROOM 1701 AC X 6-4 HT ROOM 1701 AC X 6-5 HT ROOM 1701 AC X 6-6 HT ROOM 1701 AC X 6-7 HT JANITORS X 8-1 HT STAFF RR X 8-2 HT BOYS RR X 8-3 HT GIRLS RR X 8-4 PS ROOM 1704 X 7-1 Owners Rep Sign: Date: 3/31/23 Inspector Sign: p J ALARM AND DETECTION REPORT LAS PLUMAS HIGH - 1700 WING Page 4 of 5 DEVICE Zone or DEVICE SLC # TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL PSD ROOM 1704 X 3-1 PSD ROOM 1704 X 3-2 PSD ROOM 1703 X 4-1 PSD ROOM 1703 X 4-2 PSD ROOM 1702 X 5-1 PSD ROOM 1702 X 5-2 PSD ROOM 1701 X 6-1 PSD ROOM 1701 X 6-2 Owners Rep Sign: Date: 3/31/23 Inspector Sign: e ALARM AND DETECTION REPORT LAS PLUMAS HIGH - 1700 WING Page 5 of 5 Zone or DEVICE DEVICE SLC # TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL LEGEND PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual Ply—Post Indicator Valve Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo CO-Carbon Monoxide Detector - - - NOTE # COMMENT Discrepancies Found? I i I Yes n No See Discrepancy Report? L] Yes LI No 3/31/23 Owners Rep Sign: Date: Inspector Sign: