HomeMy WebLinkAboutFAI15-0089 026-154-013 Sierra Ave FA 9.28.23 ALARM AND DETECTION REPORT Page 1 of 10
VOLTAG PECIALisTs
530-624-4514
C101C16 License#880862 www.VoltageSpecialists.com Inspection # 18-516
ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection: Annual Fire Alarm Date: 9/28/23
site: Sierra Avenue School Customer: Thermalito Unified School District
Street: 1050 Sierra Ave. School Contact: Joyce Dennison
City/State: Oroville, CA Phone#: 530-538-2961
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep Andrew 530-712-0100
B. Fire Department Oroville Fire 530-538-2444
C. Central Station Central Station 1-800-722-0364
D. Central Station Acct# 18-9485
2. Control Panel Status Yes No Note #
A. Is the system monitored by Central Station? X
On Test Time: 3:00 Return to Service Time: 8:45
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H. 18 Date Batteries Installed: 12/2/20
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
Condition of Batteries: Good Note#
Battery Voltage with AC Power: 27.46 Battery Voltage without AC Power: 27.40
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: Simplex Model# 4002 System Type: Hard Wire
Location of Annunciators: NA
Location of Primary Power Source:Electrical Panel# B Breaker 26
Comments: Note#
Note#
FCPS: Manufacturer: Silent Knight Model# EVS-50W Panel/Breaker# Location:Below FACP
B/26
Battery Voltage with A/C Power: 27.25 w/o A/C Power 2717 Date: 10/28/20
FCPS: Manufacturer: Silent Knight Model# EVS-50 Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
FCPS: Manufacturer: Model# Panel/Breaker# Location:
Battery Voltage with A/C Power: w/o A/C Power Date:
Owner/Rep: Phone#: Date:
Inspector: Wyatt C. Phone#: 530-362-2609 Date:9/28/23
Owners Rep Sign: Date:9/28/23 Inspector Sign:
Panel Report Page 1A to Fire Alarm Report VOLTAGE SPECIALISTS
530-624-4514 #880862
VOLTAGE' %PECIALIsTs
530..624.4514
C101C16 License#880862 www.VoltageSpecialists.com
Type of Inspection: FA Annual i.e.Quarterly,Annual Date: 9/28/23
Property Name: Sierra Ave.
Street: Contact:
City & State: Phone:
FCPS: FCPS #1 Manufacturer: Silent Knight Model#: 5496 Panel/Breaker#: Location: Below FACP
Battery Voltage with A/C Power: 27.25 without A/C Power 27.23 Date: 10/28/20
FCPS: FCPS #2 Manufacturer: Silent KniahtModel#: 5496 Panel/Breaker#: Location: Port 26
Battery Voltage with A/C Power: 27.25 without A/C Power 27.20 Date: 10/27/20
FCPS:FCPS #3 Manufacturer: Model#: Panel/Breaker#: Location:
Battery Voltage with A/C Power: without A/C Power Date:
FCPS: FCPS #4 Manufacturer: Model#: Panel/Breaker#: Location:
Battery Voltage with A/C Power: without A/C Power Date:
FCPS: FCPS #5 Manufacturer: Model#: Panel/Breaker#: Location:
Battery Voltage with A/C Power: without A/C Power Date:
FCPS: FCPS #6 Manufacturer: Model#: Panel/Breaker#: Location:
Battery Voltage with A/C Power: without A/C Power Date:
FCPS: FCPS #7 Manufacturer: Model#: Panel/Breaker#: Location:
Battery Voltage with A/C Power: without A/C Power Date:
FCPS: FCPS #8 Manufacturer: Model#: Panel/Breaker#: Location:
Battery Voltage with A/C Power: without A/C Power Date:
FCPS: FCPS #9 Manufacturer: Model#: Panel/Breaker#: Location:
Battery Voltage with A/C Power: without A/C Power Date:
•
9/28/23
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Page 2 of 10
Property Site: Sierra Avenue School
Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators
5. Zones 22 22 X
6. Manual Stations (Pull)
Hardwire 12 12 X
Addressable
7. Detectors
Photoelectric 57 57 X
Ionization
Heats/Fixed or R of R 54 54 X
Flame
Duct(See#15)
8. Horn/Strobe 6 6 X
Strobe Only 27 27 X
Bell
Speakers
Horn 27 27 X
9.
10. Automatic Door Release X
11. Water Flow switches 1 1 X
Did W/F Ring Outside Bell? X
Did W/F Activate Alarm Panel? X
12. Tamper Switches X
13. PIV X
OS &Y X
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X
17. Is system reset for normal conditions? X
18. Is system restored to operational service? X
19. Have Proper Authorities (see#1)been notified system is back in service? X
List Proper Authorities:Oroville Police
20. Indicate %of equipment tested this report 25% 50% 75% VJI00%
21. Indicate %of equipment tested YTD 25% 50% 75% 100%
Comments for any"no"answers or explanations (Note#):
9/28/23
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Page 3 of 10
Property Site: Sierra Avenue School
DEVICE zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PSD Admin N.E. Rm X 2 1
PSD Admin Principal X 2 2
PSD Admin File Rm X 2 3
PSD Admin Main Office X 2 4
PSD Admin Main Office Alcove X 2 5
PSD Nurses Office X 2 6
PSD Nurses Rm X 2 7
PSD Admin Copy Rm X 2 9
PSD Admin Break Rm X 2 10
PSD Admin Hall to RR X 2 11
PSD Kindergarten Rm 2 X 23 1
PSD Kindergarten Rm 2 X 23 2
PSD Kindergarten Rm 1 X 23 5
PSD Kindergarten Rm 1 X 23 6
PSD Kindergarten Rm 1 X 23 7
PSD Rm 5 X 15 3
PSD Rm 5 X 15 4
PSD Rm 4 X 13 1
PSD Rm 4 X 13 2
PSD Library X 13 3
PSD Library X 13 4
PSD Rm 10 X 22 1
PSD Rm 10 X 22 2
PSD Rm 11 X 22 3
PSD Rm 11 X 22 4
PSD Rm 12 X 22 PS
PSD Rm 12 X 22 6
PSD Rm 13 X 22 7
PSD Rm 13 X 22 8
PSD Rm 14 X 21 4
PSD Rm 14 X 21 5
9/28/23
Sign:Owners RepDate: Inspector Sign:
p J
ALARM AND DETECTION REPORT Sierra Avenue School Page 4 of 10
DEVICE Zone or DEVICE
SLC 44
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PSD Rm 15 X 21 6
PSD Rm 15 X 21 7
PSD Rm 9 X 17 1
PSD Rm 9 X 17 2
PSD Rm 8 X 17 3
PSD Rm 8 X 17 4
PSD Rm 7 X 19 1
PSD Rm 7 X 19 2
PSD Rm 6 X 19 3
PSD Rm 6 X 19 4
PSD GYM X 8 1
PSD GYM X 8 2
PSD GYM X 8 3
PSD GYM X 8 4
PSD GYM X 8 5
PSD GYM X 8 6
PSD GYM X 8 7
PSD GYM X 8 8
PSD GYM X 8 9
PSD Stage X 8 10
PSD Stage X 8 11
PSD Stage X 8 12
PSD Gym N.W. Rm X 8 13
PSD Gym S.W. Rm X 8 14
PSD Kitchen S. Exit X 10 5
PSD Kitchen RR X 10 7
9/28/23
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Sierra Avenue School Page 5 of 10
DEVICE Zone or SLC DEVICE
#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
HT Nurses RR X 2 8
HT Admin Mens RR X 2 12
HT Admin Womens RR X 2 13
HT Admin Storage by Mens RR X 2 14
HT Admin Storage by Womens RR X 2 15
HT Kindergarten Rm 2 RR X 23 3
HT Kindergarten Kitchen X 23 4
HT Kindergarten Rm 1 RR X 23 8
HT Kindergarten Rm 1 Storage X 23 9
HT Boys RR by Rm 5 X 15 1
HT Girls RR byRm5 X 15 2
HT Girls RR by Rm 13 X 21 1
HT Boys RR by Rm 13 X 21 2
HT Custodial Rm by Rm 13 X 21 3
HT Maintenance Shop by RM 8 X 17 5
HT Boys RR by Rm 6 X 19 5
HT Staff RR by Rm 6 X 19 6
HT Custodial by Rm 6 X 19 7
HT Girls RR by Rm 6 X 19 8
HT Gym Storage X 10 1
HT Kitchen X 10 2
HT Kitchen X 10 3
HT Kitchen X 10 4
HT Kitchen RR X 10 6
HT Kitchen Custodial X 10 8
HT Kitchen Office X 10 9
HT Gym Electrical X 10 10
HT Gym AC Rm X 10 11
HT Gym AC Rm X 10 12
HT Custodial by Rm 7 Attic X 18 1
HT Custodial by Rm 7 Attic X 18 2
HT Rm 8 Attic X 18 3
HT Rm 8 Attic X 18 4
Owners Rep Sign: Date: 9/28/23
Inspector Sign:
ALARM AND DETECTION REPORT Sierra Avenue School Page of 10
DEVICE Zone or
DEVICE
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
HT Rm 9 Attic X 18 5
HT Rm 9 Attic X 18 6
HT Breezeway between 7 & 8 X 18 7
HT Breezeway between 7 & 8 X 18 8
HT Rm 7 Attic X 20 1
HT Rm 7 Attic X 20 2
HT Rm 6 Attic X 20 3
HT Rm 6 Attic X 20 4
HT Breezeway between 4&5 Attic X 14 1
HT Breezeway between 4&5 Attic X 14 2
HT Rm 4 Attic X 14 3
HT Rm 4 Attic X 14 4
HT Rm 3 Attic X 14 5
HT Rm 3 Attic X 14 6
HT Rm 5 Attic X 16 1
HT Rm 5 Attic X 16 2
HT Rm's 14&15 Breezeway X 21 7
HT Main Office Attic X 3 1
HT Main Office Attic X 3 2
HT Understage X 9 1
HT Understage X 9 2
9/28/23
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Sierra Avenue School Page of 10
DEVICE SLC ZONE
TYPE DEVICE LOCATION PASS FAIL NOTE# Channel #
PS Main Office X 1 1
PS Rm 20 X 5 1
PS Rm 24 X 5 2
PS Rm 25 X 5 3
PS Rm 19 X 6 1
PS Rm 18 X 7 1
PS Rm 17 X 7 2
PS Rm 16 X 7 3
PS Gym E X 4 1
PS Gym N X 4 2
PS Gym S X 4 3
PS Kitchen S Exit X 4 4
WF Stage X 12 1
WF Below Stage X 12 2
9/28/23
Owners Rep Sign: Date: Inspector Sign:
ALARM AND DETECTION REPORT Sierra Avenue School Page of 10
Zone or DEVICE
DEVICE SLC #
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
LEGEND
PSD—Photoelectric Smoke Detector BD—Beam Detector H—Horn V—Visual
ISD—Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS—Tamper Switch
PDD—Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF—Water Flow Switch
IDD—Ion Duct Smoke Detector HT—Fixed Temp Heat Detector CV—Chime Visual DH—Door Holder
DHS—Door Holder&Smoke Detector FD—Flame Detector S—Speaker OSY—Outside Stem&Yoke Tamper Valve
SSD—Signal Station Smoke Detector B—Bell AV—Audible Visual Ply—Post Indicator Valve
Cur-Elevator Curtains FRD-Fire Rolldown Door SDC Smoke Detector&Door Holder Combo
CO-Carbon Monoxide Detector - - -
NOTE # COMMENT
Discrepancies Found? I 1 Yes 1,1 No
See Discrepancy Report? n Yes ✓ No
9/28/23
Owners Rep Sign: Date: Inspector Sign: